TLT-Turbo GmbH 

Installation, operating and maintenance instructions. 

For axial flow fans 

Page 1 

Series fan division 

Bad Hersfeld

 

Type AXO ... / ... 

 

of 12 

 

MBW-AXO.DOC 

Issue: 03.2004 

 

 

Installation, operation and  

maintenance instructions 

 

for axial flow fans 

 

AXO . . . / . . . 

 

Standard design 

 

with direct drive 

 

state of the art 

 
 
 
 

 
 
 
 
 
 
 
 

 

 

Summary of Contents for AXO Series

Page 1: ...enance instructions For axial flow fans Page 1 Series fan division Bad Hersfeld Type AXO of 12 MBW AXO DOC Issue 03 2004 Installation operation and maintenance instructions for axial flow fans AXO Sta...

Page 2: ...vice 4 4 Operational safety 4 5 Transport 5 6 Scope of delivery 6 7 Intermediate storage 6 8 Design 6 9 Technical information 6 10 Installation and mounting 7 11 Trial run startup 8 12 Breakdowns 9 13...

Page 3: ...rights regarding the contents of these IOM s and technical changes for technical improvement of our fans 2 Applications The axial fan is build according to the state of the art and it is failsafe The...

Page 4: ...y observed The user has to make sure that only qualified staff work with the fan Necessary works may only be carried out by properly trained staff with sufficient experience and knowledge of the relev...

Page 5: ...ices may only be removed if the fan is out of action For all types of work on the fan as a rule it has to be out of action The impeller has to be locked to prevent turning After repair works you have...

Page 6: ...on air direction D or S Conduit box mounted at the outer wall of the fan housing or on the motor accessible via inspection door The impeller is mounted on the motor shaft end It is not adjustable Fan...

Page 7: ...flexible connections Mount flexible connection exactly not staggered Observe length of installation exactly If the fans are installed on vibration dampers an extension duct is required For installati...

Page 8: ...ection Upon special wish they can be equipped with barretter thermal resistor protection or thermal contacts The required tripping units have to be provided by the customer 11 Trial run startup BEFORE...

Page 9: ...ressure increase and compare the values with the nameplate 12 Breakdowns If after some time the fan starts vibrating the cause may be the following a Particles sticking on the impeller blades Troubles...

Page 10: ...spection book 14 Description of the impeller Impeller hub of aluminum blades of plastic Depending on the desired output they are supplied with 6 8 9 10 or 12 blades The impeller blades are not adjusta...

Page 11: ...disassembled At the same time the winding and other parts should be cleaned The bearings have to be thoroughly cleaned with benzine After evaporation of the detergent first class grease has to be fil...

Page 12: ...act our field staff or the specialists in our Bad Hersfeld plant 17 Annex Assembly of the impeller Slightly grease the end of the shaft Then mount the wheel using a special fitting too Threaded hole i...