5.
Troubleshooting
Please find the table which lists the symptoms, possible causes, and recommended action. If our suggested
troubleshooting solutions cannot remedy the problem, please contact your TiMOTION sales representative.
Symptom
Possible cause
Action
Motor runs, but spindle does not
move
Gearing system or spindle
damaged
Please contact your TiMOTION sales
representative.
No motor sound or movement
The actuator is not properly
connected to the power
supply
Check the connection to the power
supply or the external control unit.
Customer fuse burned
Check the fuse
Cable damaged
Please contact your TiMOTION sales
representative.
Excessive power consumption
Misalignment or overload in
the application
Align or reduce the load.
Try running the actuator without load.
The actuator cannot lift the full
load, or the motor runs too slowly
Insufficient power supply
Verify the power supply is properly
plugged in
Load is higher than specified
Reduce the load
No signal or incorrect feedback
output
Cable damaged
Please contact your TiMOTION sales
representative.
Wrongly connected
Check the wiring
The signal is constantly
high/low
Run the actuator to full extension and
retraction
Reconnect the cables and set parallel
configuration again
No signal or incorrect feedback
output
Incorrect feedback
output/level
Connect the actuator to PGMA and
check for the correct feedback option.
Actuator runs in smaller steps
Insufficient power supply
Check the power supply
Load is higher than specified
Reduce the load
Internal safety procedure
activated
Connect the actuator to PGMA and
check the following:
Reason for last stop (detailed in