TIME MARK A263 Quick Start Manual Download Page 1

DESCRIPTION

 

 

The 

Model  263

 continuously monitors 3-phase power systems 

for  phase loss, low  voltage  and  phase reversal.    The monitor 
consists  of  a  solid-state  sensing  circuit,  driving  an 
electromechanical relay. 

 

Applying  correct  voltage  and  phase  rotation  energizes  the 
relay.  When properly adjusted, a fault condition will cause the 
relay  to  de-energize,  even  when  regenerated  voltage  is 
present. 

 

When  the  fault  is  corrected,  the  Model  263  automatically 
resets.    A  manual  reset  version  is  also  available.  The  SG 
Model  has  silver  with  gold  flash  contacts  for  low  current 
applications. 

 

The Model 263 does not require a neutral connection, and can 
be  used  on Wye  or  Delta systems.   Each of the  five  different 
voltage ranges is adjustable to allow the monitor to be set for 
existing  conditions.  NORMAL  and  TRIP  L E D  indicators  are 
provided to aid in adjustment and system troubleshooting. 
 

   Detects Phase Loss or Reversal 

   and Low Voltage 

   400Hz and Gold Contact Options 

  

 Automatic or Manual Reset 

   UL Recognized and CSA Certified 

MODEL 263 

3-Phase Monitor 

TIME MARK is a division of

 

 

 

 

 

 

 

 

  

 

 

 

 

 

   

 

  

 

11/2011 

© 2011   

TIME MARK CORPORATION

 

 

  

 

SPECIFICATIONS

 

 

 

AUTO Reset 
MANUAL Reset 
GOLD-AUTO Reset 
GOLD-MAN Reset 

A263 

A263M 

A263SG 

A263SGM 

B263 

B263M 

B263SG 

B263SGM 

C263 

C263M 

C263SG 

C263SGM 

D263 

D263M 

D263SG 

D263SGM 

EX263 

EX263M 

EX263SG 

EX263SGM 

Nominal AC voltage 
(phase to phase) 

120VAC 

208/240VAC 

480VAC 

575VAC 

380VAC 

Adjustment Range 

85-120V 

160-240V 

380-480V 

450-575V 

300-400V 

Frequency 

60Hz 

60Hz 

60Hz 

60Hz 

50Hz 

Power Consumption 

0

.

75W 

1

.

5W 

4

.

5W 

7

.

5W 

4.5W 

Transient Protection 

2500 VRMS for 10ms  

Repeat Accuracy 

± 0

.

1% of setpoint   (fixed conditions)  

Response Time 

50ms  

Dead Band 

Approximately 2%  

Output Contacts 

All 

SG

 models:   SPDT    silver w/gold flash    5 amps at 240VAC   resistive 

All other models:   SPDT    10 amps at 240VAC   resistive 

Expected Relay Life   

 

Mech:  

10 million operations 

 

 

Elec:   

100,000 operations at rated load  

Operating Temp 

- 20° to +131° F  

Humidity Tolerance 

0 - 97%   w/o condensation  

Enclosure Material 

ABS plastic  

Mounting 

surface  

Weight 

9

.

5 oz  

Agency Approvals 

ALL VERSIONS - UL Recognized and CSA Certified  

2.08"

.47"

5.5"

.203

dia. typ.

3.0"

3.88"

5.5"

3.0"

3.88"

.203

dia. typ.

Manual Reset Button

(manual version only)

6.06"

DIMENSIONS 

Reviews: