Timberwolf TB42 Installation And Operation Manual Download Page 1

FRENCH PG. 75

W415-2882 / A / 12.10.20

ADD MANUAL TITLE 

Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030

Phone 1 (866) 820-8686 • www.timberwolffi replaces.com • ask@timberwolffi replaces.com

CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS: 

CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS APPLIANCES

INSTALLER: 

Leave this manual with the appliance

CONSUMER: 

Retain this manual for future reference

ADD PRODUCT CODE HERE (TRADE GOTHIC LT STD FONT)

NATURAL GAS MODELS:

PROPANE GAS MODELS:

Product Name / Code

(MUST use title from Price Book)

ADD ____ ILLUSTRATED

ADD PRODUCT IMAGE

CSA / 

INTERTEK

LOGO

SAFETY INFORMATION

- Do not store or use gasoline or other 

fl ammable vapors and liquids in the vicinity of 

this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

:

•  Do not try to light any appliance.

•  Do not touch any electrical switch; do not 

use any phone in your building.

•  Immediately call your gas supplier from a 

neighbour’s phone. Follow the gas    

supplier’s   instructions.

•  If you cannot reach your gas supplier, call 

the fi re department.

- Installation and service must be 

performed by a qualifi ed installer, service 

agency, or the supplier.

This appliance may be installed in an aftermarket, 

permanently located, manufactured home (USA 

only) or mobile home, where not prohibited by 

local codes.

This appliance is only for use with the type of gas  

indicated on the rating plate. This appliance is 

not convertible for use with other gases, unless 

a certifi ed kit is used. 

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly 

could result in serious injury, death, or 

property damage.

WARNING

!

ENGLISH 

$10.00

FOR INDOOR USE ONLY

IF INSTAL OPERATION, ADD SERIAL 

NUMBER LABEL HERE

IF SEPARATE MANUALS, ADD “PLACE 

BARCODE LABEL ON THE OWNER’S MANUAL”

TB42NTR / TB42NTRE

TB42PTR / TB42PTRE

INSTALLATION AND 

OPERATION MANUAL

TB42

SAFETY

 BARRIER

ÉCRAN DE PROTECTION

SERIENNUMMER VOM KARTON AUFBRINGEN

Seriennr.

MODELL-NR.

BRENG HET SERIENUMMER VAN DE DOOS AAN

Serienr.

MODELNR.

Summary of Contents for TB42

Page 1: ...e Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the supplier Thisappliancemaybeinstalledinanaftermarket permanently located m...

Page 2: ...ouching hot surfaces Even after the appliance is off it will remain hot for an extended period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces These screens and guards must be fastened to the floor Any safety screen guard or barrier removed for servicing the appliance must be replaced prior to operating the appliance ...

Page 3: ...barrier for this appliance Installation and repair should be done by a qualified service person It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean For outdoor products only this appliance must not be installed indoors or within any structure that prevents or inhibits the exhaust gases from dissipating in the outside atmosphere If appli...

Page 4: ...ing vertical vents 39 5 0 electrical information 40 5 1 electronic wiring diagram 40 5 2 battery back up installation 41 5 3 optional wall switch 42 6 0 gas installation 43 7 0 operation electronic 44 7 1 pilot on demand 45 8 0 operation millivolt 46 9 0 finish framing 47 9 1 minimum framing dimensions 47 10 0 finishing 48 10 1 safety barrier door removal and installation 48 10 2 front hood instal...

Page 5: ... source This appliance is a decorative product It is not a source of heat and not intended to burn solid fuel A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance and must be installed note Batteries must be disposed of according to the local laws and regulations Some batteries may be recycled and may be accepted for disposal at your local recycl...

Page 6: ...he appliance 2 Install rough framing see rough framing section 3 Place the appliance in its final position 4 Install appliance venting see venting installation section 5 Install all electrical wirings see electrical information section 6 Install gas lines see gas installation section 7 Test appliance 8 Complete framing see finish framing section 9 Complete finishing see finishing section 1 2 insta...

Page 7: ...aled combustion product The installation must conform with local codes or in absence of local codes the National Gas and Propane Installation Code CSA B149 1 in Canada or the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the United States Suitable for mobile home installation if installed in accordance with the current standard CAN CSA Z240MH Series for gas equipped mobile homes in Canada or ANSI ...

Page 8: ...cun matériau devant entretien contact avec les flammes autre que celui qui est fourni avec cet appareil par le fabricant Maximum horizontal extension X See installation manual for greater extensions minimum vent lengths and maximum vent lengths L extension horizontale maximale X Référez au manuel d installation pour des extensions plus grandes les longueurs d évacuation minimaux et maximum The app...

Page 9: ...INLET 34 5 8 879mm 18 5 16 465mm 7 3 16 182mm 1 13 16 46mm GAS INLET B35 ILLUSTRATED B42 ILLUSTRATED 42 1067mm 18 7 8 480mm 11 5 16 288mm 127mm 8 203mm 35 890mm 11 5 16 288mm 34 5 8 879mm SAFETY BARRIER SAFETY BARRIER 24 1 8 613mm 4 102mm 178mm 7 1 5 dimensions front view side view top view ...

Page 10: ...structed homes particularly those in cold climates For optimum flame appearance and appliance performance keep the vent length and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstructed and undamaged Rigid and flexible venting systems must not be combined Different venting manufacturer com...

Page 11: ...nimum 1 4 rise per foot or 21mm rise per meter using flexible venting For safe and proper operation of the appliance follow the venting instructions exactly A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings Local codes or regulations may require different clearances Do not allow the inside liner...

Page 12: ...W415 2882 A 12 10 20 EN 12 venting requirements REAR VENT See venting section 40 ft 12m maximum 3 ft 1m minimum 16 40 6cm minimum 20 50 8cm maximum 24 1 8 61 3cm 24 1 8 61 3cm minimum plus rise ...

Page 13: ...ion sleeve is not required with a stove appliance 8 1 TOP VENT REAR VENT 30 MINIMUM 12 MINIMUM TOP EXIT INSTALLATION REAR EXIT INST 30 MINIMUM MAXIMUM 10FT VENT LENGTH 20 50 8cm MAXIMUM 20 50 8cm MAXIMUM 12 MINIMUM TALLATION REAR EXIT INSTALLATION 30 MINIMUM 12 MINIMUM MAXIMUM 10FT VENT LENGTH 6 152mm RISE MINIMUM m M m M 6 152mm RISE MINIMUM 2 2 2 corner termination 12 30 5cm minimum to grade 12 ...

Page 14: ...ch deck or overhang N 16 40 6cm 16 40 6cm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without openings Q 3 0 9m 3 0 9m See chart for wider wall dimensions R 6 1 8m 6 1 8m See chart for deeper wall dimensions The terminal shall not be installed on any wall that has an opening between the termi...

Page 15: ...se is equal to or greater than the horizontal run Vertical rise is less than horizontal run Vertical rise is equal to or greater than the horizontal run Vertical rise is less than horizontal run 3 5 times the vertical rise equal to or greater than the horizontal run 3 times the vertical rise equal to or greater than the horizontal run Horizontal run vertical rise to maximum of 40 feet 12m Horizont...

Page 16: ...FT 0 6m HR H1 H2 2 5 FT 0 8m 2 FT 0 6m 4 5 FT 1 4m HO 03 three 90 elbows 90 03 270 90 5 4 FT 1 7m HT HR HO 4 5 FT 1 4m 5 4 FT 1 6m 9 9 FT 3m HT VT 9 9 FT 3m 11 FT 3 4m 20 9 FT 6 4m Formula 1 HT VT 9 9 FT 3m 11 FT 3 4m Formula 2 HT VT 40 FT 12 2m 20 9 FT 6 4m 40 FT 12 2m Since both formulas are met this vent configuration is acceptable See graph to determine the required vertical rise VT for the req...

Page 17: ... 75 FT 7 5m Since both formulas are met this vent configuration is acceptable The shaded area within the lines represents acceptable values for HT and VT 90 V1 H1 H2 90 Example V1 4 FT 1 2m V2 1 5 FT 0 5m VT V1 V2 4 FT 1 2m 1 5 FT 0 5m 5 5 FT 1 7m H1 2 FT 0 6m H2 1 FT 0 3m H3 1 FT 0 3m H4 1 5 FT 0 5m HR H1 H2 H3 H4 2FT 0 6m 1FT 0 3m 1FT 0 3m 1 5FT 0 5m 5 5 FT 1 7m HO 03 four 90 elbows 90 03 360 90...

Page 18: ... shaded area within the lines represents acceptable values for HT and HT HT VT For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 9 FT 2 7m V2 6 FT 1 8m VT V1 V2 9FT 2 7m 6FT 1 8m 15FT 4 6m H1 3 FT 0 9m H2 2 FT 0 6m H3 1 5 FT 0 5m HR H1 H2 H3 3FT 0 9m 2FT 0 6m 1 5FT 0 5m 6 5FT 2m HO 03 four 90 elbows 90 03...

Page 19: ...0 feet 12 Example 1 V1 3 FT 0 9m V2 8 FT 2 4m VT V1 V2 3FT 0 9m 8FT H1 2 5 FT 0 8m H2 2 FT 0 6m HR H1 H2 2 5FT 0 8m 2FT HO 03 three 90 elbows 90 HT HR HO 4 5FT 1 4m 5 4 HT VT 9 9FT 3m 11FT 3 4m Formula 1 HT VT 9 9FT 3m 11 Formula 2 HT VT 40 F 20 9FT 6 4m Since both formulas are met this 0 2 5 0 8 5 1 5 7 5 2 3 10 3 1 12 5 3 8 HT VT Simple venting configuration only one 90 elbow See graph to determ...

Page 20: ... VT 14 2 For vent configurations requiring one or more 90 elbows top exit or one or more 90 elbows rear exit the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 5 FT 1 5m V2 6 FT 1 8m V3 10 FT 3 1m VT V1 V2 V3 5FT 1 5m 6FT 1 8m 10FT 3 1m 21 FT 6 4m H1 8 FT 2 4m H2 2 5 FT 0 8m HR H1 H2 8FT 2 4m 2 5FT 0 8m 10 5FT 3 2m HO 03 four 90 elbows 90 03 360 90 8 1 FT 2 5m HT...

Page 21: ...1 FT 2 5m HT HR HO 8FT 2 4m 8 1FT 2 5m 16 1FT 4 9m HT VT 16 1FT 4 9m 4 5FT 1 4m 20 6FT 6 3m Formula 1 HT 3 5 VT 3 5 VT 3FT 0 9m x 4 5FT 1 4m 13 5 FT 4 1m 16 1FT 4 9m 13 5 FT 4 1m Since this formula is not met this vent configuration is unacceptable Formula 2 HT VT 40 FT 12 2m 16 1FT 4 9m 13 5 4 1m Since only formula 2 is met this vent configuration is unacceptable and a new fireplace location or v...

Page 22: ...rough the venting to the outdoors note 22 EN W415 1293 F 11 23 17 3 11 rear exit WARNING FAILURE TO CREATE A SEAL TO THE FIREBOX WITH THE EXHAUST COLLAR ASSEMBLY WILL CAUSE THE APPLIANCE TO FUNCTION IMPROPERLY AND CAN CAUSE INJURY OR PROPERTY DAMAGE A Remove the safety screen and glass front refer to SAFETY SCREEN DOOR REMOVAL AND INSTALLATION section B Remove the contents from the firebox and set...

Page 23: ... outer cover without knock out over the 7 178mm exhaust collar assembly and secure L From inside the firebox install the 4 102mm exhaust collar up through the top of the firebox and secure with the the four hex head 3 8 thread cutting screws M Reattach the top deflector log set glass door and safety barrier EXHAUST FLUE COLLAR FLUE PIPE WITH GASKET INTAKE COLLAR ASSEMBLY GASKET OUTER COVER TO TOP ...

Page 24: ...ucted entirely of non combustible materials Materials consisting entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof are suitable Materials that are reported as passing ASTM E136 standard test method for behaviour of materials in a vertical tube furnace at 1382ºF 750ºC and UL763 shall be considered non combustible materials Minimum clearance to combusibles...

Page 25: ... top of the vent pipe on all horizontal runs to combustibles is required VERTICAL VENT SECTIONS A minimum of 1 25mm all around the vent pipe on all vertical runs to combustibles is required except for clearances in appliance enclosures See minimum enclosure clearances section The minimum clearances from the top of the horizontal vent pipe to combustible materials may be reduced from 3 76mm to 1 25...

Page 26: ...SE 1 25mm 3 76 2mm 3 76 2mm 501 2 128 3c 54 137 2cm PLAFOND MIN 345 8 87 9cm TOP EXIT ENCLOSURE The appliance requires a minimum enclosure height of 50 1 2 128 3cm For temperature requirements the enclosure space around and above the appliance must be left unobstructed See minimum framing dimension section for details on reducing vent pipe top clearances These parameters also apply to the illustra...

Page 27: ...around and above the appliance must be left unobstructed MINIMUM REAR VENT CLEARANCES For rear vent termination not exceeding 10 254mm of horizontal vent run 241 8 61 3cm MINIMUM PLUSRISE COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 7 178mm MINIMUM PLUSRISE 10 20 254mm 508mm VENTRUN 415 8 105 7cm 1 10 25mm 254mm VENTRUN 345 8 87 9cm ...

Page 28: ...ove the appliance must be left unobstructed MAXIMUM REAR VENT CLEARANCES EXAMPLE 1 For rear vent termination exceeding 10 254mm COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 7 178mm 415 8 105 7cm 10 20 254mm 508mm VENTRUN 111 2 292mm 241 8 61 3cm MINIMUM PLUSRISE 345 8 87 9cm COMBUSTIBLE INCOMBUSTIBLE BRIQUE See venting section ...

Page 29: ...s the enclosure space around and above the appliance must be left unobstructed MAXIMUM REAR VENT CLEARANCES EXAMPLE 2 241 8 61 3cm MINIMUM PLUSRISE COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76mm BRICK 0 0MM IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 7 178mm 415 8 105 7cm 10 20 254mm 508mm VENTRUN 111 2 292mm 415 105 345 8 87 9cm See venting section ...

Page 30: ... rough framing place the appliance in its final position A B For heavier finishing materials such as marble we recommend adding extra support to the frame Ensure there is adequate floor support for the appliance and finishing material note Ref Minimum rough framing dimensions A 18 9 16 47 2cm B 42 1 2 108 cm Based on 1 2 12 7mm finishing material thickness ...

Page 31: ...allow vent to sag and separate Use vent run supports and connect vent sections per installation instructions Risk of fire do not allow loose materials or insulation to touch the vent pipe Remove insulation to allow for the installation of the attic shield and to maintain clearances to combustibles Do not fill the space between the vent pipe and enclosure with any type of material Do not pack insul...

Page 32: ...d between the pipe and the firestop Bend the tabs for reduced side clearances or move the shield for reduced top clearances dependent on specific appliance clearances Do not fill the air space between the firestop spacer and the exterior wall with any type of insulating material i e spray foam note DETERMINE THE CORRECT HEIGHT CAULKING FIRESTOP SPACER VENT SHIELD FINISHING MATERIAL CAULKING The ab...

Page 33: ...eiling that the venting system passes through Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the fireplace Ensure that both spacer and shield maintain the required clearance to combustibles Once the vent pipe is installed in its final position apply red RTV silicone W573 0002 not supplied between th...

Page 34: ...o account the additional length needed for the finished wall surface Apply a heavy bead of the red RTV silicone W573 0002 not supplied to the inner sleeve of the air terminal Slip the vent pipe a minimum of 2 50 8mm over the inner sleeve of the air terminal and secure with a minimum of 3 screws B Using the outer flex pipe slide over the outer combustion air sleeve of the air terminal and secure wi...

Page 35: ...re possible cover the sides and top edges of the flashing with roofing material F Aligning the seams of the terminal and air terminal connector place the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal Secure with a minimum of three screws when 4 7 5 8 and 3 5 venting is used and a minimum of six screws when using 8 10 or 8 11 venting G Apply a...

Page 36: ...through the firestop maintaining the required clearance to combustibles Apply a heavy bead of Red RTV Silicone W573 0002 not supplied to both the inner sleeve and outer sleeve of the air terminal Slide the terminal sleeves into the rigid pipes a minimum of 1 1 4 Holding the air terminal lettering in an upright readable position secure to the exterior wall and make weather tight by sealing with cau...

Page 37: ... and to the sides of the air terminal connector Place the flashing over the air terminal connector and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly centered within the flashing giving a 3 4 19 1mm margin all around Fasten to the roof Do NOT nail through the lower portion of the flashing Make weather tight by sealing with caulking W...

Page 38: ...the air intake flex liner and the exhaust collar must be connected to the exhaust flexible liner Both Simpson Duravent and Selkirk co linear to co axial adaptors have been approved on this appliance Follow vent manufacturer s installation instructions Different manufacturer s venting components must not be combined Once the preferred manufacturer s appliance adaptor has been attached the remainder...

Page 39: ...he plate will pivot at the slot up into the exhaust outlet D Depending on the amount of restriction desired the restrictor plate can be left flat for most restriction or bent up for varying degrees of restriction 1 2 3 1 Most restriction 2 Moderate restriction 3 Least restriction Exhaust collar Restrictor Mounting screws Firebox top Firebox top Restrictor Top view 8x hex head sheet metal screw 4 4...

Page 40: ...ITCH WIRED IN SERIES WITH EITHER THE EXISTING SWITCH OR OPTIONAL WALL SWITCH THERMOSTAT OR REMOTE Do not wire 110 volts to the valve or wall switch WARNING This appliance comes equipped with a battery back up If this backup is used install 4 AA batteries not sup plied into the holder and connect to the wire harness Connect the battery holder to the wire harness before using the appliance Place nea...

Page 41: ...ntrol compartment of the appliance to the battery housing F Place the battery housing into the control compartment ensuring that the battery housing is placed in a clean and easily accessible location G Reinstall the safety barrier The safety barrier must be installed at all times during the appliance operation H Turn the gas and electrical power back on to begin operating the appliance Red wire B...

Page 42: ...venient location Route a 2 strand solid core millivolt wire from the valve to the wall switch or millivolt thermostat The recommended maximum lead length depends on wire size WIRE SIZE MAX LENGTH 14 gauge 1 8mm 100 feet 30 5m 16 gauge 1 5mm 60 feet 18 3m 18 gauge 1 2mm 40 feet 12 2m Disconnect the existing wires from terminals 1 and 3 from the ON OFF switch and replace with the leads from the wall...

Page 43: ...ange Installation and servicing to be done by a qualified installer Move the appliance into position and secure If equipped with a flex connector the appliance is designed to accept a 1 2 13mm gas supply Without the connector it is designed to accept a 3 8 9 5mm gas supply The appliance is equipped with a manual shut off valve to turn off the gas supply to the appliance Connect the gas supply in a...

Page 44: ...lectrical power to the appliance and re install the batteries into the transmitter Set thermostat to desired setting if equipped I Turn on the remote wall switch to the appliance J If the appliance will not operate follow instructions TO TURN OFF GAS and call your service technician or gas supplier A Set thermostat to lowest setting if equipped B Turn off the remote wall switch to the appliance C ...

Page 45: ...pilot if the appliance is not used This countdown will reset anytime the appliance main burner is used Therefore if the appliance is regularly used day to day the pilot will remain on However this system does not require the user to remember to turn the pilot off as summer approaches and avoids unnecessary fuel consumption while still readily turned back on when the cold weather returns Your appli...

Page 46: ...nue to burn repeat steps E through I J With pilot lit turn gas knob counter clockwise to the ON position K If equipped with the flame adjustment valve push and turn the knob to high L Turn on all electrical power to the appliance and re install the batteries into the transmitter if equipped Set thermostat to desired setting if equipped A Set thermostat to desired setting if equipped B Turn off all...

Page 47: ...0 47 9 0 finish framing 421 2 108cm 35 88 9cm GAS INLET LOCATION 189 16 47 2cm 501 2 128 3cm ENCLOSURE TOP FINISHING MATERIAL ELECTRICAL CONNECTION DESSUS DEL ENCEINTE 2 3 16 56mm 7 3 16 182mm 9 1 minimum framing dimensions ...

Page 48: ...tion of louvres or doors or access for service Observe all clearances when applying combustible materials Before door is removed turn the appliance off and wait until appliance is cool to the touch Doors are heavy and fragile so handle with care WARNING A barrier designed to reduce the risk of burns from the hot viewing glass is provided for the appliance and shall be installed Before the glass do...

Page 49: ...ve safety door and barrier B Remove the securing screws from the top of the firebox as shown C Install the front hood ensuring it is angled downward when installed D Reinstall the previously removed securing screws note This hood must be installed if it has not already been factory installed ...

Page 50: ... If greater projections are desired increase the clearance to the sides bottom and top by 2 50 8mm for every additional 1 25 4mm of projection If using an optional surround the same rule applies starting from the top of the surround Ensure clearances are maintained for surround removal as it must lift off the appliance for maintenance Door Optional surround Top of appliance 4 101 6mm 6 152 4mm 2 5...

Page 51: ...01 6mm 2 50 8mm 6 152 4mm 8 203 2mm 34 5 8 88cm M A N T E L H E I G H T 0 2 50 8mm 2 4 6 8 10 12 MANTEL DEPTH INCHES 4 101 6mm 6 152 4mm 10 254mm 12 30 5cm 8 203 2mm WARNING 45 4 Risk of fire Maintain all specified air space clearances to combustibles Failure to comply with these instructions may cause a fire or cause the appliance to overheat Ensure all clearances i e back side top vent mantel fr...

Page 52: ...ectronic device or other materials the effect of direct heat on the electronics or other materials will be reduced Follow mantel height and depth instructions for proper clearances B Refer to minimum mantel clearances section for more detailed mantel clearance information Installing a television or other electronics above the appliance may cause discolouration melting or damage to the electronics ...

Page 53: ...ling tabs you must first determine the thickness of your finishing material i e drywall This will determine the dimension from the front edge of the corner post to the nailing tab Once the nailing tab is in the desired location and secure using an appropriate fastener Additional fasteners may be installed ADD IMAGE HERE 37 1 NAILING TABS 1 2 FINISHING MATERIAL 3 4 FINISHING MATERIAL ...

Page 54: ...B2 located on the right side of the support tray Place log 3 W135 0695 onto C1 and C2 located on the left side of the support tray Place log 1 W135 0693 firmly onto A1 and A2 located on the rear of the support tray PINS Ensure log 1 sits flat and does not cover the pilot opening Place two pins in the holes located on the top of log 1 Stud Log 1 Burner Ports Pilot Opening Pilot Opening A1 C1 C2 B1 ...

Page 55: ...the pin located on the right side of log 1 Rest the other end of log 6 in the notch of log 2 Place the hole in the bottom of log 7 W135 0696 onto the pin located on the left side of log 1 Rest the other end of log 7 in the notch of log 3 Place log 8 W135 0689 in the notches of log 3 and log 4 Place log 9 W135 0690 on log 6 and log 2 notches 1 2 4 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8...

Page 56: ...Use only certified glowing embers and PHAZER logs available from your local authorized dealer distributor WARNING Completely blocking the burner ports can cause an incorrect flame pattern carbon deposits and delayed ignition 22 2 Randomly place the charcoal embers along the front and sides of the log support in a realistic manner Fine dust found in the bottom of the bag should not be used WARNING ...

Page 57: ...ttom of the blower to avoid the blower rubbing against the floor of the appliance G Pivot the blower into the bottom of the appliance Ensure the gasket remains in place between the blower and outer shell while sliding the blower against the left side of outer shell into the blower mounting tab Secure in place using one screw see Figures 4 and 5 NOTE WiTH THE ZiP TiE suPPliEd ENsurE all WirEs rEmai...

Page 58: ...mm TO 1 2 12 7mm OF FLAME SENSOR PILOT BURNER ELECTRODE FLAME SENSOR 3 8 1 2 9 5mm 12 7mm ELECTRONIC ILLUSTRATED 3 8 1 2 flamE musT ENVElOP uPPEr 3 8 TO 1 2 12 7mm 9 5mm Of THErmOcOuPlE THErmOPilE 9 5mm 12 7mm 3 8 1 2 la flammE dOiT ENVElOPEr la ParTiE suPÈriEurE du THErmOcOuPlE ET dE la THErmOPilE dE 3 8 À 1 2 9 5mm 12 7mm 9 5mm 12 7mm MILLIVOLT ILLUSTRATED Adjust the pilot screw to provide prope...

Page 59: ...NSTALLER AIR SHUTTER OPENING VENTURI BURNER ORIFICE 33 1 It is important that the orifice is securely inserted into the venturi note 12 2 venturi adjustment It s important to periodically perform a visual check of the pilot and burner flames Compare them to the illustration provided If any flames appear abnormal call a service person ADD IMAGE HERE 36 1 9 5mm 12 7mm Flame must envelop upper 3 8 to...

Page 60: ...burner ignites completely on all ports when turned on A 5 to 10 second total light up period is satisfactory If ignition takes longer consult your local authorized dealer dis tributor 9 Visually inspect the appliance for carbon build up Using a small whisk or brush brush off the carbon and vacuum up or sweep into garbage 10 This step is not applicable for Vent Free appliances Check to see that the...

Page 61: ... glass should ever crack or break while the fire is burning do not open the door until the fire is out Do not operate the appliance until the glass has been replaced Contact you local authorized dealer distributor for replacement parts DO NOT SUBSTITUTE MATERIALS 5 1A Vinegar based glass cleaners have demonstrated an ability to provide a clean streak free glass surface note Do not clean glass when...

Page 62: ...ty replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of appliance Installation date of appliance Part number Description of part Finish Parts part numbers and availability are subject to change without notice Parts identified as stocked will be delivered within 2 to 5 ...

Page 63: ...fety barrier assembly Safety barrier assembly Rear log GL 705 W135 0693 11 18 W010 3554 Door latches X4 20 W010 3490 SER 4 exhaust flue pipe assembly W290 0282 Gasket flue pipe assembly 10 Yes W570 0135 Shoulder screws X4 19 For replacement parts see valve train assembly section W715 1046 SER Top finishing trim W018 0180 SER Front baffle Front left log GL 705 W135 0688 Left middle log GL 705 W135 ...

Page 64: ...e NG Yes 14 W725 0063 886 Proflame valve P Yes 15 W010 2763 Pilot assembly NG 15 W010 2808 Pilot assembly P 16 W750 0270 Wire assembly W455 0068 Pilot orifice 35 P Yes W720 0062 Pilot tube w fittings Yes W240 0013 Ignitor w wire Yes W290 0029 Pilot gasket Yes Yes Yes W455 0070 Pilot orifice 62 NG Yes 9 3 W290 0248 Valve train gasket 4 W432 0046 Manifold flex pipe 5 6 7 8 W190 0175 Control board Ye...

Page 65: ...ilot assembly P 16 W750 0112 Wire assembly W725 0025 Valve NG Yes W725 0026 Valve P Yes W357 0001 Push button ignitor Yes W010 0801 Pilot NG Yes W010 0800 Pilot P Yes W680 0004 Thermopile Yes W680 0005 Thermocouple Yes Yes Yes 9 W290 0029 Pilot gasket Yes 3 4 W290 0248 Valve train gasket 5 W432 0078 Manifold flex pipe Yes 6 6 7 W335 0039 Pilot hood Yes 8 W455 0070 Pilot orifice 62 NG Yes W455 0068...

Page 66: ...e Surround 19 20 SFKM Shore Fire Kit 03 11 19 H Variable speed switch Blower kit Thermodisc MRKM BFKS Beach Fire Kit Mineral Rock Kit Left side bevelled trim BT42K Safety screen Black Zen Decorative Safety Barrier Side trim x2 TK42 Magnet x16 TK42 Black Heritage Decorative Safety Barrier Top bottom trim x2 TK42 Right side bevelled trim BT42K Top bevelled trim BT42K Yes Yes Yes 12 13 DBPB42OH Decor...

Page 67: ...ging on the glass logs rocks media or combus tion chamber Ensure the media is positioned correctly in the appliance Open air shutter to increase the primary air Check the input rate check the manifold pressure and orifice size as specified by the rating plate Ensure door gaskets are not broken or missing and the seal is tight Ensure vent liners are free of holes and well sealed at all joints Check...

Page 68: ...er if equipped Reset program hold reset button on receiver and wait for 2 beeps Release after second beep Press small flame button on remote within 20 seconds you will hear an additional beep this signals a successful reset Replace receiver Valve Check valve and replace if necessary Do not to overtighten thermocouple Burner continues to spark and pilot lights but main burner does not light Short o...

Page 69: ...ate Minimal voltage from thermocou ple or resistance in circuit ports Parts include ON OFF switch receiver thermocurrent connec tions or temperature switches Measure the voltage it should read a least 5mV The spade connector is on the outer surface beside the magnet nut Verify with manufacturer the drop time after thermocouple is heated measure the drop time No pilot ignition 5 second continuous b...

Page 70: ...URE TO TURN SCREWS CLOCKWISE FIRMLY TO RESEAL DO NOT OVER TORQUE Leak test with a soap and water solution Air shutter improperly adjusted Return air shutter to specified opening see venturi adjustment section Carbon is being deposited on glass logs rocks media or combustion chamber surfaces Air shutter is blocked Ensure air shutter opening is free of lint or other obstructions Flame is impinging o...

Page 71: ...aulty Loosen and tighten thermocouple Clean thermocouple and valve connection Replace thermocouple Replace valve Faulty valve Replace Pilot burning no gas to main burner gas knob is on HI wall switch thermostat is on Thermostat or switch is defective Connect a jumper wire across the wall switch terminals if main burner lights replace switch thermostat Wall switch wiring is defective Disconnect the...

Page 72: ... rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans furnaces clothes dryers etc Any damages to the appliance combustion chamber heat exchanger plated trim or other components due to water weather damage long period...

Page 73: ...EN W415 2882 A 12 10 20 73 notes 29 1 ...

Page 74: ...Produced and distributed by 24 Napoleon Road Barrie Ontario Canada L4M 0G8 Tel 1 866 820 8686 timberwolffireplaces com ...

Page 75: ... d entretien ou le fournisseur Cet appareil peut être installé dans une maison préfabriquée mobile déjà installée à demeure si les règlements locaux le permettent Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque d homologation Cet appareil ne peut être converti à d autres gaz sauf si une trousse de conversion est utilisée RISQUE D INCENDIE OU D EXPLOSION Incapaci...

Page 76: ...its passants et loin des meubles et des rideaux Les meubles ou autres objets doivent être gardés à une distance d au moins 4 pieds 1 22m du devant de l appareil Assurez vous de disposer de mesures de sécurité adéquates pour empêcher les jeunes enfants de toucher aux surfaces chaudes Même une fois que l appareil est éteint l appareil demeurera chaud pendant un temps prolongé Consultez votre détaill...

Page 77: ...tion et la réparation devraient être effectuées par un technicien qualifié Il est impératif que les compartiments de contrôle le brûleur et les passages de circulation d air soient gardés propres afin de fourni une combustion et une circulation d air adéquates Produits pour l extérieur seulement Cet appareil ne doit pas être installé à l intérieur ni dans une structure qui empêche la dissipation d...

Page 78: ...minée existante 113 4 4 1 renstreignant des évents verticaux 114 5 0 information électrique 115 5 1 schéma de câblage électronique 115 5 2 installation du sauvegarde de pile 116 5 3 interrupteur mural optionnel 117 6 0 branchement de gaz 118 7 0 fonctionnement électronique 119 7 1 veilleuse sur demande 120 8 0 fonctionnement millivolt 121 9 0 encadrement fini 122 9 1 dimensions minimaux de l encad...

Page 79: ... Cet appareil ne peut être converti à un autre type de gaz à moins d utiliser un ensemble de conversion certifié L emballage de protection sur les pièces s enlève mieux lorsque l assemblage est à température ambiante ou lorsqu il est chauffé à l aide d un séchoir à cheveux ou d une autre source de chaleur similaire Cet appareil est un produit décoratif L appareil n est pas une source de chaleur et...

Page 80: ...ition finale 4 Installez l évacuation de l appareil voir la section installation d évacuation 5 Installez toutes câblages électrique voir la section information électrique 6 Installez les conduites de gaz voir la section branchement du gaz 7 Testez l appareil 8 Complétez l encadrement voir la section encadrement fini 9 Complétez les finitions voir la section finitions 1 2 vue d ensemble d installa...

Page 81: ...étecteur de monoxyde de carbone est requis dans toutes les pièces contenant des appareils alimentés au gaz L appareil n est pas approuvé pour installation dans une chambre à coucher ou une salle de bain à moins d être un appareil avec une chambre de combustion scellée à évacuation directe L installation doit se conformer aux codes locaux En l absence de codes locaux l installation doit être confor...

Page 82: ...flammes autre que celui qui est fourni avec cet appareil par le fabricant Maximum horizontal extension X See installation manual for greater extensions minimum vent lengths and maximum vent lengths L extension horizontale maximale X Référez au manuel d installation pour des extensions plus grandes les longueurs d évacuation minimaux et maximum The appliance must be vented using the appropriate Nap...

Page 83: ...8 5 16 465mm 7 3 16 182mm 1 13 16 46mm GAS INLET B35 ILLUSTRATED B42 ILLUSTRATED 42 1067mm 18 7 8 480mm 11 5 16 288mm 127mm 8 203mm 35 890mm 11 5 16 288mm 34 5 8 879mm SAFETY BARRIER SAFETY BARRIER 24 1 8 613mm 4 102mm 178mm 7 1 5 dimensions vue de face vue de côté vue de dessus ÉCRAN DE PROTECTION ÉNTRÉE DU GAZ ...

Page 84: ...nférence de chaque joint dans le système de ventilation Cela garantira les meilleures performances dans chaque application et évite les problèmes de performance ou de condensation qui peuvent survenir dans les maisons construites étroitement en particulier dans les climats froids Pour une performance optimale de l appareil et une apparence optimale des flammes gardez la longueur des évents et le n...

Page 85: ...s courses horizontales devraient avoir un élévation minimum de 1 4 par pied ou 21mm par mètre lors d utilisation d évacuation flexible Afin d assurer un fonctionnement sécuritaire et adéquat de l appareil vous devez observez les instructions d évacuation à la lettre Une terminaison ne doit pas être installée directement au dessus d un trottoir ou d une entrée pavée située entre deux maisons unifam...

Page 86: ...5 2882 A 12 10 20 86 FR exigences d évacuation 2 1 installations typiques d évents 16 40 6cm minimum 40 pi 12m maximum 3 pi 1m minimum ÉVACUATION SUR LE DESSUS 8 203mm minimum 24 61cm maximum 34 5 8 87 9cm ...

Page 87: ...A 12 10 20 87 exigences d évacuation FR ÉVACUATION SUR L ARRIÈRE Voir la section évacuation 40 pi 12m maximum 3 pi 1m minimum 16 40 6cm minimum 20 50 8cm maximum 24 1 8 61 3cm 24 1 8 61 3cm minimum plus la pente ...

Page 88: ...i dessous de l évacuation sur le sessus utiliser seulement lorsqu ils sont fournis avec l appareil Un manchon isolant n est pas requis avec une appareil poêle 8 1 ÉVACUATION SUR LE DESSUS ÉVACUATION SUR L ARRIÈRE 2 2 2 installation en coin 12 30 5cm minimum au niveau du sol 12 30 5cm minimum au niveau du sol 30 76 2cm minimum 30 76 2cm minimum 34 5 8 87 9cm Lorsque l évent est installé en coin la ...

Page 89: ... murs adjacents incluant les maisons voisines P 8 2 4m 8 2 4m Le toit doit être incombustible et sans ouvertures Q 3 0 9m 3 0 9m Voir le tableau pour les dimensions d un mur plus large R 6 1 8m 6 1 8m Voir la tableau pour les dimensions d un mur plus profond La terminaison ne doit pas être installée sur quelconque mur ayant une ouverture entre la terminaison et le côté ouvert de la structure S 12 ...

Page 90: ...le La course verticale est plus petite que la course horizontale La course verticale est plus grande ou égale à la course horizontale La course verticale est plus petite que la course horizontale La course horizontale la course verticale jusqu à un maximum de 40 pieds 12 2m La course horizontale la course verticale jusqu à un maximum de 24 75 pieds 7 5m La course horizontale la course verticale ju...

Page 91: ...QUISE EN PIEDS MÈTRES VT LONGUEUR DES COURSES HORIZONTALES PLUS LES DÉVIATIONS EN PIEDS MÈTRES HT Lorsque la configuration de l évacuation exige plus d un coude de 90 les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 3 PI 0 9m V2 8 PI 2 4m VT V1 V2 3PI 0 9m 8PI 2 4m 11PI 3 4m H1 2 5 PI 0 8m H2 2 PI 0 6m HR H1 H2 2 5PI 0 8m 2PI 0 6m 4 5 PI 1 4m HO 0 03 tr...

Page 92: ...6 7PI 5 1m 24 75 PI 7 5m Puisque les deux formules sont respectées cette configuration d évacuation est acceptable La section ombragée à l intérieur des lignes représente des valeurs acceptables pour HT et VT 90 V1 H1 H2 90 Exemple V1 4 PI 1 2m V2 1 5 PI 0 5m VT V1 V2 4PI 1 2m 1 5PI 0 5m 5 5 PI 1 7m H1 2 PI 0 6m H2 1 PI 0 3m H3 1 PI 0 3m H4 1 5 PI 0 5m HR H1 H2 H3 H4 2 PI 0 6m 1 PI 0 3m 1 PI 0 3m ...

Page 93: ...HT La section ombragée à l intérieur des lignes représente des valeurs acceptables pour HT et VT Lorsque la configuration de l évacuation exige plus qu un coude de 90 les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 9 PI 2 7m V2 6 PI 1 8m VT V1 V2 9 PI 2 7m 6 PI 1 8m 15 PI 4 6m H1 3 PI 0 9m H2 2 PI 0 6m H3 1 5 PI 0 5m HR H1 H2 H3 3PI 0 9m 2PI 0 6m 1 5PI...

Page 94: ... HT VT Formula 2 HT VT 40 feet 12 2m Example 1 V1 3 FT 0 9m V2 8 FT 2 4m VT V1 V2 3FT 0 9m 8FT 2 4m H1 2 5 FT 0 8m H2 2 FT 0 6m HR H1 H2 2 5FT 0 8m 2FT 0 6 HO 03 three 90 elbows 90 03 HT HR HO 4 5FT 1 4m 5 4FT HT VT 9 9FT 3m 11FT 3 4m Formula 1 HT VT 9 9FT 3m 11FT 3 Formula 2 HT VT 40 FT 12 20 9FT 6 4m 40 F Since both formulas are met this vent 0 2 5 0 8 5 1 5 7 5 2 3 10 3 1 12 5 3 8 HT VT Simple ...

Page 95: ...tables pour HT et VT Lorsque les configurations de l évacuation exigent plus que zéro coude de 90 évacuation sur le dessus ou un coude de 90 évacuation à l arrière les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 5 PI 1 5m V2 6 PI 1 8m V3 10 PI 3 1m VT V1 V2 V3 5PI 1 5m 6PI 1 8m 10PI 3 1m 21PI 6 4m H1 8 PI 2 4m H2 2 5 PI 0 8m HR H1 H2 8PI 2 4m 2 5PI 0 8...

Page 96: ...4m HO 0 03 quatre coudes 90 90 0 03 360 90 8 1 PI 2 5m HT HR HO 8PI 2 4m 8 1PI 2 5m 16 1 PI 4 9m HT VT 16 1PI 4 9m 4 5PI 1 4m 20 6 PI 6 3m Formule 1 HT 3VT 3VT 3 PI 0 9m x 4 5 PI 1 4m 13 5 PI 4 1m 16 1PI 4 9m 13 5 PI 4 1m Puisque cette formule n est pas respectée cette configuration d évacuation est inacceptable Formule 2 HT VT 40 PI 12 2m 20 6 PI 4 9m 40 PI 12 2m Puisque seulement la formule 2 es...

Page 97: ...s matériels AVERTISSEMENT Ne serrez pas trop les vis Il suffit d appuyer le joint d étanchéité contre la chambre de combustion note Fig 1 Cette déflecteur est installée pour bloquer la vue à travers lévacuation à l extérieur note DÉFLECTEUR 22 EN W415 1293 F 11 23 17 3 11 rear exit WARNING FAILURE TO CREATE A SEAL TO THE FIREBOX WITH THE EXHAUST COLLAR ASSEMBLY WILL CAUSE THE APPLIANCE TO FUNCTION...

Page 98: ...ravers la haut de la chambre de combustion et des quatre vis à tête 3 8 M Réinstallez la déflecteur supérieur avec les quatre vis Installez les ensemble de bûches vitre de la porte et l écran de protection EXHAUST FLUE COLLAR FLUE PIPE WITH GASKET COLLET D ÉVACUATION JOINT D ÉTANCHÉITÉ COUVERTURE D EXTÉRIEUR TO TOP VENT FLUE PIPE WITH GASKET COQUILLE D EXTÉRIEUR COUVERCLE F I D E E PLAQUE DE COUVE...

Page 99: ...ne combinaison de ces matériaux sont appropriés Les matériaux répondant à la norme ASTM E 136 méthode de test standard du comportement des matériaux dans une fournaise avec tube vertical à 1382 F 750 C et à la norme UL763 sont considérés comme étant des matériaux non combustibles Afin d éviter un risque d incendie les dégagements minimaux aux matériaux combustibles doivent être maintenus L enceint...

Page 100: ...des dégagements à l intérieur de l enceinte de l appareil Voir la section dégagements minimaux de l enceinte 3 1 dégagements minimaux de l ossature Do not put objects in front of the appliance minimum distance of 4 feet 4 2 1 2 1 0 8 c m 5 6 1 2 1 4 3 5 c m 40 101 6cm 42 1 2 108cm 2 51mm 18 9 16 47 2cm Ne placez pas d objets devant l appareil distance minimale de 4 pieds Les dégagements minimaux e...

Page 101: ... PLAFOND MIN 3 76 2mm MINIMUM 345 8 87 9cm ENCEINTE AVEC ÉVACUATION SUR LE DESSUS L enceinte de l appareil doit avoir une hauteur minimale de 50 1 2 128 3cm Afin de respecter les contraintes de température l espace à l intérieur de l enceinte autour de l appareil et au dessus doit demeurer sans obstruction Voir la section dimensions minimale de l ossature pour plus d informations sur la réduction ...

Page 102: ... à l intérieur de l enceinte autour de l appareil et au dessus doit demeurer sans obstruction DÉGAGEMENTS MINIMAUX D ÉVACUATION À L ARRIÈRE Pour la ventilation ne dépassement pas 10 254mm de section horizontale de ventilation PLUSRISE 1 10 25mm 254mm VENTRUN INCOMBUSTIBLE 0 0MM SILESMATÉRIAUX SONTINCOMBUSTIBLES COMMEDELABRIQUE ETDELAPIERRE BRIQUE 1 10 25mm 254mm ÉVENTS 241 8 61 3cm MINIMUM PLUSLAP...

Page 103: ...ur de l enceinte autour de l appareil et au dessus doit demeurer sans obstruction DÉGAGEMENTS MAXIMAUX D ÉVACUATION À L ARRIÈRE EXEMPLE 1 Pour la ventilation arrière dépassement de 10 254mm 10 20 254mm 508mm VENTRUN COMBUSTIBLE 1 25mm 3 76mm 7 178mm 415 8 105 7cm 10 20 254mm 508mm ÉVENTS 111 2 292mm 241 8 61 3cm MINIMUM PLUSLAPENTE 345 8 87 9cm INCOMBUSTIBLE 0 0MM SILESMATÉRIAUX SONTINCOMBUSTIBLES...

Page 104: ... température l espace à l intérieur de l enceinte autour de l appareil et au dessus doit demeurer sans obstruction DÉGAGEMENTS MAXIMAUX D ÉVACUATION À L ARRIÈRE EXEMPLE 2 TIBLE SED K 241 8 61 3cm MINIMUM PLUSLAPENTE COMBUSTIBLE INCOMBUSTIBLE 1 25mm 3 76mm BRIQUE 7 178mm 415 8 105 7cm 10 20 254mm 508mm ÉVENTS 111 2 292mm 345 8 87 9cm 0 0MM SILESMATÉRIAUX SONTINCOMBUSTIBLES COMMEDELABRIQUE ETDELAPIE...

Page 105: ... placez l appareil dans sa position finale A B Pour les matériaux de finition plus lourds comme du marbre nous vous recommandons d ajouter un support additionnel à l ossature Assurez vous que le support de plancher est adéquat pour l appareil et le matériau de finition note Réf Dimensions minimales de l encadrement approximatif A 18 9 16 47 2cm B 42 1 2 108 cm Basé sur la 1 2 12 7mm matériau de fi...

Page 106: ...e se séparer Utilisez des supports de conduit et racoordez les sections de conduits selon les instructions d installation Risque d incendie Évitez que l isolant touche au conduit d évacuation Retirez l isolant pour permettre l installation de l écran protecteur du grenier et pour maintenir les dégagements aux matériaux combustibles Ne remplissez pas l espace entre le conduit d évent et la charpent...

Page 107: ...tuyau et le coupe feu L espaceur coupe feu doit être installé avec l écran protecteur orienté vers le haut La terminaison ne doit pas être enchâssée dans le mur ou le revêtement extérieur plus que l épaisseur de la bride de la plaque de montage L écran protecteur doit être fixé en place en fixant l écran protecteur prolongé aux languettes de courbure à l aide des attaches fournies AVERTISSEMENT Pl...

Page 108: ...utrage tout autour et placez un espaceur coupe feu par dessus le protecteur de conduit d évacuation pour empêcher l arrivée d air froid dans la pièce ou autour de l appareil Assurez vous que l espaceur coupe feu et le protecteur de conduit d évacuation conservent le dégagement nécessaire aux matériaux combustibles Une fois que le conduit d évacuation est en place appliquez une scellant silicone ro...

Page 109: ...r fini Appliquez un généreux joint de scellant à haute température Mill Pac W573 0007 non fourni Glissez la gaine flexible sur le manchon intérieur de la terminaison en assurant un chevauchement minimal de 2 50 8mm et fixez à l aide d une minimum de trois vis B Installez la gaine flexible extérieure en la glissant sur le manchon extérieur de la terminaison et fixez à l aide d une minimum de trois ...

Page 110: ...c des matériaux de couverture F Alignez les joints de la terminaison et du connecteur de terminaison et placez la terminaison par dessus le connecteur de terminaison en vous assurant que le manchon pénètre dans le trou de la terminaison Fixer avec au moins de trois vis lorsque vous utilisant une évent de 4 7 5 8 et 3 5 ou une minimum de six vis lorsque vous utilisant une évent de 8 10 ou 8 11 G Ap...

Page 111: ... coupe feu en respectant les dégagements aux combustibles requis Appliquez un généreux joint de scellant à haute température rouge W573 0002 non fourni à la fois le manchon intérieur et le manchon extérieur du terminaux d air Faites glisser le manchon du terminaux dans les évents rigides d un minimum de 1 1 4 En soutenant la terminaison les inscriptions étant à l endroit et lisibles fixez la au mu...

Page 112: ...s et les côtés du connecteur de terminaison Placez le solin par dessus le connecteur de terminaison et glissez le sous les côtés et le bord supérieur des bardeaux Assurez vous que le connecteur de terminaison est bien centré dans le solin en laissant une marge de 3 4 19 1mm tout autour Fixez le au toit NE clouez PAS à travers la partie inférieure du solin Imperméabilisez le en le scellant avec du ...

Page 113: ...doit être raccordé au conduit flexible de prise d air et le collet d évacuation de la terminaison au conduit flexible d évacuation Les adaptateurs colinéaire à coaxial Simpson Duravent et Selkirk sont approuvés pour cet appareil Suivez les instructions d installation du fabricant du système d évacuation Des composants d évacuation de différents fabricants ne doivent pas être combinés Une fois que ...

Page 114: ...s l orifice d échappement D Selon la quantité de restriction souhaitée la plaque de bride peut être laisée à plat pour la plupart restriction ou tordues à différents degrés de restriction 1 2 3 1 Restriction optimale 2 Restriction modérer 3 Restriction minimal Le col d évacuation Restriction Vis muni L haut de la chambre de combustion Vue au sommet Restriction L haut de la chambre de combustion Vi...

Page 115: ...ANCHEZ CES RACCORDS DE L INTERRUP TEUR MARCHE ARRÊT BRANCHEZ LES AU THERMOSTAT OPTIONNEL OU LE TÉLÉCOMMANDE ET SI PERMIS AVEC CETTE APPAREIL UN ADAPTATEUR POUR ÉVENT B MISE À LA TERRE ALIMENTATION CC ANNEAU DE MISE À LA TERRE Cet appareil est équipé avec un boîtier de piles Si le boîtier de piles est utilisé installez quatre piles AA non fournies dans le support et branchez le au harnais de fils B...

Page 116: ...de de pile soit sur l âtre du l appareil dans le compartiment de contrôles Assurez vous que l endroit est propre et facilement accessible G Garantir que l écran de protection soit réinstaller L écran de protection doivent être installer tous le temps pendant l opération de l appareil H Branchez l alimentation électrique et du gaz à l appareil avant l opération Red wire Black wire Battery housing C...

Page 117: ...peut être installé à un endroit pratique Passez un fil millivolt à deux brins noyau solide de la soup ape à l interrupteur mural ou au thermostat millivolt La longueur maximale dépend du calibre du fil DIAMÈTRE DU FIL LONGUEUR MAX calibre 14 1 8mm 100 pieds 30 5m calibre 16 1 5mm 60 pieds 18 3m 1calibre 8 1 2mm 40 pieds 12 2m Déconnectez les fils des bornes 1 et 3 du soupape de l interrupteur marc...

Page 118: ...pape ont été faits en usine ne les modifiez pas L installation et l entretien doivent être effectuées par un installateur qualifié Mettez l appareil en place et fixez le Si l appareil est muni d un raccord flexible celui ci est conçu pour recevoir une conduite de gaz de 1 2 13mm Sans raccord flexible l appareil est conçu pour recevoir une conduite de gaz de 3 8 9 5mm L appareil est muni d une soup...

Page 119: ... plus bas si équipé B Tournez l interrupteur murale de l appareil à la position OFF C Coupez l alimentation électrique à l appareil si un travail d entretien doit être faites D Tournez le soupape fermeture manuelle vers la gauche OFF Ne forcez pas Coupez l alimentation en gaz à l appareil Ouvrez les fenêtres N allumez aucun appareil Ne touchez à aucun interrupteur électrique n utilisez aucun télép...

Page 120: ...int Une minuterie commencera alors le décompte pendant environ sept jours avant d éteindre la veilleuse si l appareil n est pas utilisé Ce décompte se réinitialisera chaque fois que le brûleur principal de l appareil sera allumé Par conséquent si l appareil est utilisé régulièrement sur une base journalière la veilleuse restera allumée Ce système ne requiert donc pas que l utilisateur se souvienne...

Page 121: ...outon de contrôle du gaz pendant que vous allumez la veilleuse en appuyant sur le bouton poussoir d ignition Gardez le bouton de contrôle du gaz enfoncé pendant une minute puis relâchez le Si la veilleuse ne reste pas allumée répétez les étapes E à I J Lorsque la veilleuse est allumée enfoncez et tournez le bouton de contrôle du gaz vers la gauche à ON K Si votre foyer est muni d une soupape d aju...

Page 122: ...t 9 0 encadrement fini 421 2 1 189 16 47 2cm 421 2 108cm 35 88 9cm EMPLACEMENT DEL ENTRÉE DUGAZ 189 16 47 2cm 501 2 128 3cm DESSUS DEL ENCEINTE MATÉRIAU DEFINITION RACCORDEMENT ÉLECTRIQUE 2 3 16 56mm 7 3 16 182mm 9 1 dimensions minimaux de l encadrement ...

Page 123: ...les persiennes ni au fonctionnement des persiennes ou des portes ni l accès pour l entretien Respectez tous les dégagements aux matériaux combustibles Avant d enlever la porte éteignez l appareil et attendez que ce dernier soit froid au toucher Les portes sont lourdes et fragiles manipulez avec soin AVERTISSEMENT Une barrière conçu à réduire le risque de brûlures à partir du chade la vitre est à c...

Page 124: ...ion B Retirez les vis de fixation de la partie supérieure de l appareil comme illustré C Installez l avant hotte Assurez vous qu elle est inclinée vers le bas lorsqu il est installé D Reinstallez les vis de fixation précedement enlever note Cette hotte doit être installé si elle n a pas déjà été installée en usine VUE DE CÔTÉ HOTTE ...

Page 125: ...2 50 8mm pour chaque pouce 24 5mm supplémentaire de projection Si vous utilisez un moulure optionelle les même règles s applique commençant du sommet du moulure Garantir que les dégagements sont maintenus pour l enlèvement du moulure vous devez l enlever de l appareil pour l entretien Section A A Section B B 0 0mm 4 101 6mm 6 152 4mm 2 50 8mm 5 127mm 3 76 2mm 4 101 6mm 6 152 4mm 2 50 8mm 5 127mm B...

Page 126: ...5 8 88cm M A N T E L H E I G H T 0 2 50 8mm 2 4 6 8 10 12 MANTEL DEPTH INCHES 4 101 6mm 6 152 4mm 10 254mm 12 30 5cm 8 203 2mm AVERTISSEMENT 45 4 Rique d incendie Conservez tous les dégagements aux matériaux combustibles spécifiés Incapacité de se conformer à ces instructions peut causer un incendie ou une surchauffe Assurez vous que tous les dégagements arrière côtés dessus évents tablette façade...

Page 127: ...au dessus de l appareil peut provoquer une décoloration la fonte détérioration ou des autres dommages aux composants électroniques Utiliser les autorisations que les lignes directrices et référer aux instructions qui se trouvent dans le manuel d installation du fabricant de votre électroniques AVERTISSEMENT note Augmentation de la longueur horizontale du manteau réduira davantage l intensité de la...

Page 128: ...e sur le côté droit du plateau de support Placez bûche 3 W135 0695 sur C1 et C2 située sur le côté gauche du plateau de support Placez bûche 1 W135 0693 fermement sur A1 et A2 située à l arrière du plateau de support ÉPINGLES Assurez vous que bûche 1 repose à plat et ne couvre pas l ouverture de veilleuse Placez deux épingles dans les trous au sommet de bûche 1 Tige Bûche 1 Orifices du Brûleur Ouv...

Page 129: ...é sur le côté droit de bûche 1 Restez l autre extrémité de bûche 6 dans l encoche de bûche 2 Placez le trou au fond de bûche 7 W135 0696 sur l épingle situé sur le côté gauche de bûche 1 Restez l autre extrémité de bûche 7 sur l encoche de bûche 3 Placez bûche 8 W135 0689 dans les encoches de bûche 3 et bûche 4 Placez bûche 9 W135 0690 sur bûche 6 et bûche 2 1 2 4 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6...

Page 130: ...MD disponible de votre détaillant autorisé locale AVERTISSEMENT Obstruez pas ni fermer les orifices du brûleur Le blocage des orifices du brûleur peut créer une flamme irrégulière des dépôts de carbone et un retard d allumage 10 9 braises de charbon 10 10 mise en place du logo 22 2 Éparpillez les braises à l avant et sur les côtés du support à bûches de façon à créer un effet réaliste N utilisez p...

Page 131: ...s fixer utilisants le rondelle de blocage Prenez le bouton de l interrupteur et installez le en position Fig 3 9 Pour installez l IVV le support de l interrupteur à vitesse variable doivent être installez Enlevez les deux vis du support du piezo installez le support IVV puis fixez en place utilisant les deux vis précedement enlever Fig 3 10 Branchez le connecteur de l IVV dans la prise corresponda...

Page 132: ... 3 8 1 2 9 5mm 12 7mm ÉLECTRONIQUE ILLUSTRÉ MILLIVOLT ILLUSTRÉ Ajustez la vis de la veilleuse pour obtenir une flamme de taille normale Tournez vers la droite pour réduire l apport de gaz Vérifiez la pression Pour vérifier la pression d arrivée tournez la vis A vers la gauche deux à trois tours puis emboîtez le tube du manomètre sur la pointe d essai Le manomètre doit indiquer la pression comme dé...

Page 133: ...e du venturi Il est important d effectuer périodiquement une inspection visuelle de la flamme de la veilleuse et du brûleur Comparez les à ces illustrations Si des flammes paraissent anormales contactez un technicien de service ADD IMAGE HERE 36 1 MILLIVOLT ILLUSTRÉ 3 8 1 2 9 5mm 12 7mm Flame must envelop upper 3 8 to 1 2 12 7mm 9 5mm of thermocouple 3 8 1 2 9 5mm 12 7mm La flamme doit envelopper ...

Page 134: ...cipal allume sur tous les orifices lorsque le bouton de contrôle du gaz est à ON Un temps d allumage total de 5 à 10 secondes est satisfaisant Si l allumage prend plus de temps consultez votre revendeur agréé ou du distributeur 9 Inspectez visuellement l appareil pour des dépôts de carbone À l aide d une balayette ou d une brosse enlevez le carbone et aspirez le avec un aspirateur ou mettez le au ...

Page 135: ...ez et jetez des débris de verrou des composants endommagés Assurez vous d aspirer tous les débris deverre à l intérieur de l appareil avant de le faire fonctionner Ne frappez pas ne claquez pas et n égratinez pas la porte vitrée Ne faites pas fonctionner l appareil lorsque la porte vitrée est enlevée fissurée brisée ou égratignée 38 1 1 Ensemble de verre cadre de remplacement est remplacé complète...

Page 136: ... pièce sous garantie une photocopie de la facture originale sera requise afin de pouvoir honorer la demande Lorsque vous commandez des pièces donnez toujours l information suivante Modèle et numéro de série de l appareil Date d installation de l appareil Numéro de la pièce Description de la pièce Fini Pièces numéro des pièces et s il soit disponible peut changer sans préavis Parties identifiées co...

Page 137: ...emblage de l Écran de Protection Bûche arrière GL 705 W135 0693 11 18 W010 3554 Loquet de porte X4 20 W010 3490 SER Assemblage de conduit d évacuation 4 W290 0282 Assemblage de tuyau de joint d étanchéité 10 Oui W570 0135 Vis à épaulement X4 19 Pour les pièces de rechanges voir la section l assemblage de la soupape W715 1046 SER Garniture de finition supérieure W018 0180 SER Déflecteur supérieure ...

Page 138: ...63 Ensemble de veilleuse GN 15 W010 2808 Ensemble de veilleuse P 16 W750 0270 Interrupteur du fils W455 0068 Injecteur de veilleuse 35 P Oui W720 0062 Tube de veilleuse raccord Oui W240 0013 Allumeur avec fils Oui W290 0029 Joint d étanchéité de veilleuse Oui Oui Oui W455 0070 Injecteur de veilleuse 62 GN Oui 9 3 W290 0248 Joint d étanchéité de soupape 4 W432 0046 Connecteur flexible 5 6 7 8 W190 ...

Page 139: ...26 Soupape P Oui W357 0001 Bouton d allumage Oui W010 0801 Veilleuse NG Oui W010 0800 Veilleuse P Oui W680 0004 Thermopile Oui W680 0005 Thermocouple Oui Oui Oui 34 W290 0029 Joint d étanchéité de veilleuse Oui 23 24 W290 0248 Joint d étanchéit de soupape 29 W432 0078 Flexible du collecteur Oui 30 30 31 W335 0039 Hotte de veilleuse Oui 32 W455 0070 Injecteur de veilleuse 62 GN Oui W455 0068 Inject...

Page 140: ...ur à vitesse variable Soufflerie Thermodisque MRKM BFKS Ensemble Beach Fire Ensemble Mineral Rock Garniture biseautée du côté gauche BT42K Écran de protection Façade décorative Zen noire Garniture du côté x2 TK42 Aimants x16 TK42 Façade décorative Héritage noire Garniture supérieure inférieure x2 TK42 Garniture biseautée du côté droite BT42K Garniture biseautée du dessus BT42K Oui Oui Oui 12 13 DB...

Page 141: ...neuse Le volet d air est réglé incorrectement Voir la section réglage du venturi pour le réglage de l ouverture du volet d air dans le manual d installation Du carbone se dépose sur la vitre les bûches les roches les composants décoratifs ou les parois de la chambre de combustion Le volet d air est bloqué Assurez vous que l ouverture du volet d air n est pas bloquée par des fibres ou autres obstru...

Page 142: ...essus d étincelles plusieurs fois ou purger la conduite d alimentation de la veilleuse Le module n est pas mis à la terre Assurez le bon polarité du thermocouple si fourni Vérifiez si les assemblages de le veilleuse et de la soupape sont bien mis à la terre Récepteur si équipé Réinitialisez la programme tenir le bouton de réinitialiser sur le récepteur attendre pour 2 bips Relâcher le bouton après...

Page 143: ...vaise position si équipé Vérifiez que le récepteur est dans la position milieu La télécommande ne fonctionne pas Vérifiez les pile ainsi que leur orientation fils sont courbeés Câblage de la soupape est endommagée Remplacez la soupape symptôme problème solution Le guide suivant est pour le système de SIT seulement La veilleuse ne s allume pas Aucun bruit et aucune étincelle au brûleur de la veille...

Page 144: ...PRIS LA LECTURE DES PRESSIONS ASSUREZ VOUS DE TOURNER FERMEMENT LES VIS VERS LA DROITE POUR SCELLER NE SERREZ PAS TROP FORT Vérifiez pour des fuites en appliquant une solution d eau savonneuse Le volet d air est mal réglé Voir la section réglage du venturi pour le réglage de l ouverture du volet d air Du carbone se dépose sur la vitre les bûches les roches les composants décoratifs ou les parois d...

Page 145: ...uple de se refroidir Le système n est pas purgé correctement Purgez la conduite de gaz Plus de propane Remplissez le réservoir La flamme de la veilleuse n est pas assez puissante Augmentez la flamme de la veilleuse La flamme de la veilleuse n enveloppe pas le thermocouple Tournez légèrement la tête de la veilleuse pour améliorer la flamme autour du thermocouple Le thermocouple cause un court circu...

Page 146: ...es ventilateurs d évacuation les fournaises les sécheuses de linge etc Tous dommages causés a l appareil à la chambre de combustion à l échangeur de chaleur aux garnitures de laiton ou autres composants par l eau les dommages causés par les intempéries de longues périodes d humidité la condensation des produits chimiques ou produits d entretien nuisibles ne seront pas la responsabilité de Timberwo...

Page 147: ...W415 2882 A 12 10 20 147 FR 19 0 notes 29 1 ...

Page 148: ...Produits et distribués par 24 Napoleon Road Barrie Ontario Canada L4M 0G8 Tél 1 866 820 8686 timberwolffireplaces com ...