8 Specifications
8-4
MIRUS Controller, SW 2.03.02, Additional Information Master (en-GB)
8.2 Supply
Electrical supply
Nominal voltage:
100 to 230 V
AC
± 10%
Frequency:
50 to 60 Hz ± 5%
Power consumption:
< 75 VA
Grounding:
Standard ground stud
Internal emergency battery: Built in USP battery
Sealed lead acid automatic turn ON upon loss of main
supply, when in operation.
Backup time for a max. 15 minutes of operation.
Status information:
On screen
During storage:
To avoid defects of the backup battery by discharging
connect MIRUS Controller to mains supply at least once
a month for at least 24h.
Agent supply
Internal:
Reservoir
Maximum internal reservoir capacity = 270 mL
Reserve internal reservoir capacity = 20 mL
Status information:
On screen
Filling systems:
Proprietary filling system, agent specific
according to ISO 5360.
Filling capacity:
maximum
to „Full“ display = 190 mL
maximum at overfill protection = 250 mL
8.3 MIRUS Controller Connection Interface
Electrical interfaces
Line supply port:
Standard IEC plug. Allows easy adaptation to different
wall plug standards by different power cords.
Grounding port:
Standard ground stud
Mechanical interfaces
Agent Fill port:
Proprietary agent specific keyed and colour coded
port
MIRUS Interface
receptacle:
Proprietary multi lumen receptacle, female