31
Error can occur due mulfunctioning of the probe that measures the temperature of exhaust gases,
caused by low exhaust temperatures, insufficient quantity of pellets required for ignition or due to
malfunction of a lighter.
If the exhaust temperature of 40 ° C is not reached in 25 minutes, the stove will not start
operating. Temperature of exhaust gases can be checked by holding the key 2. If the temperature
is lower than the required one the stove will not be able to start operating. It is necessary to check
whether there are enough pellets in the store, as well as checking if the exhaust gas probe is not
interrupted. Possible flaw can be the malfunction of the lighter, or the dispenser might be stuck,
which prevents insertion of pellets.
Check if pellets fall into the burner is only possible visually, by observing the tube through which
the pellets fall into the burner, for about 60 seconds. If there is no insertion of pellets, it is either the
storage is empty or the dozer is stuck. If dozer is try starting up the stove for several times. If you
fail starting it that way, call the service in charge.
Malfunction of the lighter can be noticed when starting the stove there are no sparks or glowing
pellets on sight. Sometimes it is possible to see incandescence of lighter also. In the case of
malfunctioning lighter, the stove can be started with a hepo cube or gel for burning. Contact the
service in charge as soon as possible.
Error due to emptying
pellet’s storage.
The display message will appear as shown in the
following figure (AL 6 NO PELLETS) and alternately will be changed with a message
that reports
a malfunction (MEMORIA ALARME).
Cancel the alarm by pressing the key 4, wait for the stove to cool. Then, proceed according to
instructions described in section 8.7 INITIAL PELLET LOADING and start the stove.
NOTE:
This alarm can occur when pellet stucks du to inadequate size.
Error caused by malfunctioning of the safety thermostat
. Safety thermostat serves to prevent
that loaded in a storage goes on fire. When the safety thermostat is out of order, the display
message will appear as shown in the following figure (AL 7 THERMAL SAFETY) and alternately
will be changed with a message reporting a malfunction (
ALLARME ATTIVO
).