1. Application

The MultiSafe DSP HS11 is a two-pole voltage tester for alternating voltages up to 11 kV AC and direct voltages up to  

16 kV. It is particularly suitable to detect voltage quickly and securely at capacitor banks and links of converters. 

The DSP HS11 is approved for indoor and outdoor applications. 

Voltage is signalised by one LED and the value is indicated digital on the LCD. With the self-test the functions of the 

testing device can be checked easily and quickly. Stand-by and abscence of voltage are signalised by a green LED.

1.1 Intended use

This device is intended for use in applications as described in the operating instructions only.  

Thus, it is imperative to observe the notes on safety and the technical  data in conjunction with the ambient  

conditions. Any other form of usage is not permitted and can lead to accidents or destruction of the unit.  

Any misuse will result in the expiry of all guarantee and warrantly claims. 

2. Safety Precautions

In order to maintain flawless technical safety conditions, and to assure safe use, it is imperative that you read 

these operating instructions thoroughly and carefully before placing your instrument into service, and that you 

follow all instructions contained therein otherwise there is danger of life!
Please observe the following safety precautions:

 

The voltages indicated on the MultiSafe DSP HS11 are rated voltages. The voltage tester may only be  

 

used in systems working within this rated voltage range.

 

Faultless indication of display values is only guaranteed between -15°C ... +55°C. 

 

Hold the instrument only beneath its hexagonal limiting dics, do not touch test probes and test electrodes.

 

The test probes may only be connected up to the red limiting mark to live or grounded plant components.  

 

With all other parts of the voltage tester the distance has to be kept as big as possible. 

 

The maximum on-time of the DSP HS11 is 15 minutes.

 

Only qualified persons may carry out work with these device. The user needs to be farmiliar with  the risks 

 

for measuring voltage and compliance with safety regulations and the proper use of the voltage detector.

 

Workings may only be performed with appropriate personal protective equipment. Observe the minimum 

 

object distance to other plant components that are energized or earthed and use personal protective  

 

equipment as specified by national accident prevention regulations  

 

(in Germany: BGV A3 or EN 50110-1). 

 

Just before they are used, and as possible afterwards as well, voltage testers need to be checked to ensure  

 

they function correctly. Check the instrument at a known voltage source by performing the self-test /  

 

function test. If the display of one or several systems fails in the course of checking, the instrument must  

 

not be used again. 

 

The red LED 

 only serves  as a indication for hazardous voltage and not as measurement  

 value.

 

This voltage detector may not permit to clearly indicate the absence of operating voltage in case of  

 

interference voltage because of its relatively high internal impedance. When the indication “voltage  

 

present” appears on a part that is expected to be disconnected of the installation, it is recommended  

 

confirming by an other means that there is no operating voltage on the part to be tested. 

 

Before use, the battery compartment must be closed. 

 

The voltage tester may only be dismantled by authorized personnel.

 

Before using the device check the housing and connecting line for visible damage. If damages  are visible the  

 

voltage tester may not be placed into operation. In case of strong dirt contamination, the tester must be  

 

cleaned before use.

 

The tester has to be stored in a clean and dry environment. 

Summary of Contents for MultiSafe DSP HS11

Page 1: ...Stra e 18 D 58256 Ennepetal Telefon 49 2333 75989 Telefax 49 2333 75257 info tietzsch de www tietzsch de DSP HS11_BA_11 2014 Bedienungsanleitung User Instructions MultiSafe DSP HS11 Zweipoliger Hochsp...

Page 2: ...m Arbeiten unter Spannung 1 Pr felektrode 2 rote Grenzmarke 3 Begrenzungsscheibe 4 Handhabe 5 Anzeigeeinheit 6 Verbindungsleitung 2 Dieses Ger t darf nicht mit dem Hausm ll entsorgt werden WEEE 2012 1...

Page 3: ...der roten Grenzmarken an spannungsf hrende oder geerdete Anlagenteile gebracht werden mit allen anderen Teilen des Spannungspr fers muss ein m glichst gro er Abstand gehalten werden Die maximal zul s...

Page 4: ...n Sie den Taster los erscheint in der Anzeige TEST Schritt 2 Test des Pr fkreises und der Schutzwiderst nde Halten Sie die beiden Pr felektroden ca 5 Sekunden zusammen Elektroden kurzschlie en Wenn Rd...

Page 5: ...n Sie die Batterie mit CAT IV Schutzhaube aus dem Batteriefach fallen und wechseln Sie die Batterie Schnappen Sie hierzu die Batterieanschlusskontakte auf die neue 9 V Batterie auf und setzen Sie die...

Page 6: ...erm chtigte Werkst tten zul ssig Bei Besch digung des Ger tes Ausfall des Eigentests oder zur detaillierten berpr fung Kalibrierung wenden Sie sich bitte an service tietzsch de oder senden Sie das Ge...

Page 7: ...agen IP 65 Ger t bei Niederschlag verwendbar Betriebstemperatur 15 C 55 C Eigentest Funktion und Schutzwiderst nde obligatorisch vor Anzeige von Messwerten Energiequelle 9 V Block IEC 6LR61 6LF22 6LP3...

Page 8: ...8...

Page 9: ...sch GmbH Co KG Willringhauser Stra e 18 D 58256 Ennepetal Fon 49 2333 75989 Fax 49 2333 75257 info tietzsch de www tietzsch de User Instructions MultiSafe DSP HS11 Two pole high voltage tester DSP HS1...

Page 10: ...formity Device for live working This devices may not be disposed with the domestic waste WEEE 2012 19 EU Please contact service tietzsch de in regard to the return of old devices 10 1 Test electrode 2...

Page 11: ...ng mark to live or grounded plant components With all other parts of the voltage tester the distance has to be kept as big as possible The maximum on time of the DSP HS11 is 15 minutes Only qualified...

Page 12: ...TEST is indicated on the display Step 2 Check test circuit and protective resistors Hold the test electrodes together for about 5 seconds until Rdy appears and the green LED lights up then the MultiS...

Page 13: ...nstrument which secures the battery compartment lid remove the lid Let the battery drop out of the battery compartment with its CAT IV protection cover and exchange it Therefore snap the battery conta...

Page 14: ...ges on the device or failure of the function test according to section 3 2 or for detailed inspec tion calibration please contact service tietzsch de or send the device and a description of failure ba...

Page 15: ...installations Operating temperature 15 C 55 C Self test function and protective resistors obligatory before indication of measurement results Power supply 9 V block IEC 6LR61 6LF22 6LP3146 alkali mang...

Page 16: ...16...

Reviews: