Synergy Controller Technical Manual, Revision H
Page 50
6.4 Special Functions
Special Functions
The Cascade parameters are organized in the
following three folders:
♦
Celsius/Fahrenheit
♦
12/24 Hour Time
♦
Output 11 Control Type
♦
Output 17 Control Type
♦
Output 18 Control Type
♦
Analog Retransmits
♦
PWM Retransmits
♦
On/Off Retransmits
♦
Remote Start/Stop
♦
Analog Programming
♦
Allow Multiple Stop Steps
Celsius / Fahrenheit
The Celsius/Fahrenheit setting sets the temperature units displayed by the Synergy Controller. The setting
is global. All temperature data are automatically displayed according to the C/F setting including currently
loaded program files.
12 / 24 Hour Time
The 12/24 Hour Time setting sets the Synergy Controller’s time display to either AM/PM format or 24 hour
format. The setting is global. All absolute time data is automatically displayed based on this format.
Output 11 Control Type (Ambient Coil)
This setting is used to set the output logic for the Ambient Coil (Output 11) to On/Off control or Time
Proportioning control. In On/Off mode the Ambient Coil is either on or off depending on the controller
demand. When in Time Proportioning mode the Ambient Coil output is between 0% and 100% depending on
the demand required. The default setting is On/Off control mode. On/Off control mode typically enables the
chamber to react faster, sacrificing accuracy. Time Proportioning modes allow greater accuracy but may
slow temperature and humidity ramp.
Time Proportioning Mode (TPM) can be changed in a program on a step-by-step basis by selecting the OT11
checkbox when creating a program step (see
Section 9.0 Programming the Synergy Controller
Output 11 or OT11 TPM (Time Proportioned Mode) can be monitored from within the Events screen. To
monitor the state of the OT11 TPM setting, go to the
Events\Event Output
folder and observe the LED light
next to the
OT11 TPM
label. The light is red when Output 11 is in time proportioning mode, gray when in
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...