![Thytronic NV021 Manual Download Page 16](http://html.mh-extra.com/html/thytronic/nv021/nv021_manual_1113995016.webp)
16
NV021 - Manual - 08 - 2012
TECHNICAL DATA
Overvoltage - 59
Common confi guration:
59 Operating logic (
Logic
59)
AND/OR
U> Element
U
> Curve type (
U
>
Curve
)
DEFINITE/INVERSE
[1]
Defi nite time
59 First threshold defi nite time (
U>
def
)
0.50...1.50
U
n
(step 0.01
U
n
)
U>
def
Operating time (
t
U
>
def
)
0.03...100.0
s
0.03...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
59 First threshold inverse time (
U>
inv
)
0.50...1.50
U
n
(step 0.01
U
n
)
U>
inv
Operating time (
t
U
>
inv
)
0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
U>> Element
Defi nite time
59 Second threshold defi nite time (
U>>
def
)
0.50...1.50
U
n
(step 0.01
U
n
)
U>>
def
Operating time (
t
U
>>
def
)
0.03...100.0 s
0.03...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.04 s
Overshoot
time
0.03
s
Pickup accuracy
±
1% ±
1%
U
n
/
E
n
Operate time accuracy
5% or ±
10 ms
Ten minutes overvoltage - 59Uavg
[2]
Common confi guration:
Operating logic (
Logic59Uavg
)
AND/OR
Uavg> Element
Defi nite time
First threshold defi nite time (
U
avg
>
def
)
0.50...1.50
U
n
(step 0.01
U
n
)
Time delay (
t
Uavg
>
def
)
0...1000 s (step 1 s)
Pickup time
according to the reference conditions
[3]
Pickup
accuracy ±
1% ±
1%
U
n
Time delay accuracy
[4]
5%
±
3 s
Negative sequence overvoltage - 59V2
U
2
> Element
Defi nite time
59V2 First threshold defi nite time (
U
2
>
def
)
0.01...0.50
U
n
(step 0.01
U
n
)
U
2
>
def
Operating time (
t
U2
>
def
)
0.07...100.0 s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.04 s
Overshoot
time
0.03
s
Pickup accuracy
±
1% ±
1%
U
n
Operate time accuracy
5% or ±
10 ms
Underfrequency (81U)
f< Element
Defi nite time
81U First threshold defi nite time (
f<
def
)
0.800...1.000
f
n
(step 0.001
f
n
)
f<
def
Operating time (
t
f
<
def
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Voltage control
f< Control enable (
f
<
&
)
ON/OFF
f< Controlled by
U
E
>> start (
f
<
&UE
>>)
ON/OFF
Note 1 The mathematical formula for INVERSE curve is: t = (0.5 ∙
t
U
>
inv
) / [(
U
/
U
>
inv
) - 1]
t = operating time (in seconds)
t
U
>
inv
= operating time setting (in seconds)
U = input voltage
U
>
inv
= threshold setting
Note 2 The function is based on the measurement of the mean of the three phase voltages of 10 minutes with update every three seconds
Note 3 The pickup time depends on the initial and fi nal value of the input voltage; e.g. with a setting of threshold equal to 1.10 Un:
- with initial value 0 and fi nal value 1.1 Uavg> def (1.1x1.1 = 1.21 Un) the pickup time is 498 s
- with initial value 0.9 Uavg>def (0.9x1.1 = 0.99 Un) and fi nal value 1.1 Uavg>def (1.1x1.1 = 1.21 Un) the pickup time is 285 s
Note 4 Since the aggregate value is updated every 3 s, times are only meaningful in multiples of 3 s
—
—
—
•
•
—
•
•