TECHNICAL DATA
19
NA30 - Manual - 04 - 2022
IE>>> Element
I
ECLP
>>> Activation time (
t
ECLP>>>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I
E
>>> Reset time delay (
t
E
>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50N/51N Third threshold definite time (
I
E
>>>
def
)
0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
I
E
>>>
def
within CLP (
I
ECLP>>>def
) 0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
I
E
>>>
def
Operating time (
t
E
>>>
def
)
0.03...10.00 s (step 0.01 s)
Pickup time
≤
0.03 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.03 s
Pickup
accuracy ±
0.5% with 0.01
I
En
, ±
0.2% with 1
I
En
Operate
time
accuracy
5%
or
±
10 ms
Residual overvoltage - 59N
Common configuration:
59N Operation from 74VT external (
74
VText59N
)
ON/OFF
U
E
> Element
U
> Curve type (
U
>
Curve
)
DEFINITE/INVERSE
[1]
U
E
>
Reset time delay
(
t
UE>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
59N First threshold definite time (
U
E
>
def
) 0.01...0.70
U
En
(step 0.01
U
En
)
U
E
>
def
Operating time (
t
UE
>
def
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
59N First threshold inverse time (
U
E
>
inv
) 0.01...0.50
U
En
(step 0.01
U
En
)
U
E
>
inv
Operating time (
t
UE
>
inv
)
0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
U
E
>>
Element
U
E
>>
Reset time delay (
t
UE>>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
59N Second threshold definite time (
U
E
>>
def
)
0.01...0.70
U
En
(step 0.01
U
En
)
U
E
>>
def
Operating time (
t
UE
>>
def
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.03 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.04 s
Overshoot time
0.03 s
Pickup
accuracy ±
4% ±
1%
U
En
Operate
time
accuracy
5%
or
±
10 ms
Directional earth fault overcurrent - 67N
Common configuration:
67N Operating mode (
Mode67N
)
I
/
I
∙
cos
67N Multiplier of threshold for insensitive zone (
M
)
1.5...10.0
(step 0.1)
67N Operation from 74VT external (
74VText67N
)
OFF/Block/Not directional
I
ED
> Element
I
ED
>
Curve type
(
I
ED
>
Curve)
DEFINITE
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM
Note 1 The mathematical formula for INVERSE curve is t= (0.5 ∙
t
UE
>
inv
) / [(
U
E
/
U
E
>
inv
) - 1]
t:
operating time (in seconds)
t
UE
>
inv
: operating time setting (referred to
U
E
/
U
E
>
inv
= 1.5 )
U
E
:
residual input voltage (direct or calculated)
U
E
>
inv
: threshold setting
Asymptotic reference value:
1
.
1
U
E
>
inv
Minimum operate time:
0.1
s
Equation is valid for 1.1 ≤
U
E
/
U
E
>
inv
≤ 4