SETTING AND COMMISSIONING
159
NA30 - Manual - 04 - 2022
• Press the
Enter
button; the cursor and the LED TRIP turn off (the LED START keeps flashing),
• Press the
Enter
button for a few seconds; new message appears:
Confirm settings?
• Answer to the message
ENTER: YES
to confirm changes or
RESET: NO
to abort.
• The message:
password ok
>>
is displayed
• To exit from password menu use
Left
or
Up
keys: if you press the
Right
button you go back in the
password menu and the password must be entered. The parameter changes are enabled from the
keyboard. After any confirming with (Enter) or abandoning the change (reset button) the password
must be entered again.
• The possibility of modifying the parameters from the keyboard is automatically disabled after about
3 minutes elapsed without pressing any button. If you do not want to wait three minutes of waiting,
it must go back to the password menu and come out without input any data (
Left
and
Right
until the
the message
password not ok
>>
is displayed.
Changing the password
Changing the password is possible only after entering the correct password (
password ok
>>
message); press the
Down
key, a new menu is displayed
change password
that you
access with the
Right
key. Inside this menu the password can be changed.
• Press the
Enter
button for a few seconds; the modification in progress status is highlighted by
flashing of the START and TRIP LEDs and by appearance of the pointer on the bottom
• Change the parameters by means the
Up
(increment) or
Down
(decrement) buttons, using the
Left
and
Right
keys to move to the previous or next character
• Press the
Enter
button; the cursor and the LED TRIP turn off (the LED START keeps flashing),
• Press the
Enter
button for a few seconds; new message appears:
Confirm settings?
• Answer to the message
ENTER: YES
to confirm changes or
RESET: NO
to abort.
Lost password
If password is lost the data base of the device must be restored, proceed with the following steps:
• Activate the session level 1
• Send
Set default settings
command available inside the
Command \ Default settings
menu.
Following the
Set default settings
command the password is reset to
0000
.
7.3 MODULES MANAGEMENT
After installation, the modules must be enabled (working with level 1 session level).
The Thybus modules may be set inside the
Procedure
menu (or by means a click on the icon).
Following up any module configuration an automatic reset is issued and the I/O devices are included
inside the device menu.
[1]
When two MID16 modules are enabled, the hardware address must be
set; the dip-switch layout is showed inside the INSTALLATION section.
Note 1 Binary inputs and output names (ThyVisor):
Binary inputs for devices with two inputs onboard
IN1, IN2 on board
IN3...IN10
with
MRI
module
IN11...IN26
with
one
MID16
module
IN27...IN42
with
two
MID16
modules
Binary inputs for devices with five inputs onboard
IN1...IN5 on board
IN6...IN13
with
MRI
module
IN14...IN29
with
one
MID16
module
IN30...IN45
with
two
MID16
modules
Output relays
K1...K6 on board
K7...K10
with
MRI
module
LEDs:
ON, START, TRIP, L1...L5 on board
L6...L10
with
MRI
module
WARNING
The command Set default settings restores the factory settings, all user- defined adjustments are cleared.
Be carefully to enter the correct parameter !
The device serial number should be set to avoid IP address conflicts for devices connected to the
Ethernet network.