TECHNICAL DATA
20
NA20 - Manual - 04 - 2022
Inverse time
[1]
50N/51N First threshold inverse time (
I
E
>
inv
)
0.002...2.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...2.00
I
En
(step 0.01
I
En
)
I
E
>
inv
within CLP (
I
ECLP>inv
)
0.002...2.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...2.00
I
En
(step 0.01
I
En
)
I
E
>
inv
Operating time (
t
E
>
inv
)
0.02...60.0
s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
IE>> Element
I
ECLP
>> Activation time (
t
ECLP>>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I
E
>> Reset time delay (
t
E
>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50N/51N Second threshold definite time (
I
E
>>
def
) 0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
I
E
>>
def
within CLP (
I
ECLP>>def
)
0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
I
E
>>
def
Operating time (
t
E
>>
def
)
0.03...10.00 s (step 0.01 s)
IE>>> Element
I
ECLP
>>> Activation time (
t
ECLP>>>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I
E
>>> Reset time delay (
t
E
>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50N/51N Third threshold definite time (
I
E
>>>
def
)
0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
I
E
>>>
def
within CLP (
I
ECLP>>>def
) 0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
I
E
>>>
def
Operating time (
t
E
>>>
def
)
0.03...10.00 s (step 0.01 s)
Pickup time
≤
0.03 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.03 s
Pickup
accuracy ±
0.5% with 0.01
I
En
, ±
0.2% with 1
I
En
Operate
time
accuracy
5%
or
±
10 ms
Breaker failure - BF
BF Phase current threshold (
I
BF
>) 0.05...1.00
I
n
(step 0.01
I
n
)
BF Residual current threshold (
I
EBF
>)
0.01...2.00
I
En
(step 0.01
I
En
)
BF Time delay(
t
BF)
0.06...10.00 s (step 0.01 s)
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
I
BF
>Pickup accuracy
±
0.5% with 0.1
I
nL
±
0.2% with 1
I
nL
I
EBF
>Pickup accuracy
± 0.5% with 0.01
I
En
± 0.2% with 1
I
En
Operate time accuracy
5% or ±
10 ms
Note 1
Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t = 0.14 · t
E
>
inv
/ [(I
E
/ I
E
>
inv
)
0.02
- 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 ·
t
E
>
inv
/ [(I
E
/I
E
>
inv
) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t = 80 ·
t
E
>
inv
/ [(I
E
/I
E
>
inv
)
2
- 1]
Long time Inverse Time (IEC 255-3/BS B LI):
t = 120 ·
t
E
>
inv
/ [(I
E
/I
E
>
inv
) - 1]
Moderately Inverse (ANSI/IEEE type MI):
t =
t
E
>
inv
· {0.01 / [(I
E
/I
E
>
inv
)
0.02
- 1] + 0.023}
Very Inverse (ANSI/IEEE type VI):
t =
t
E
>
inv
· {3.922 / [(I
E
/I
E
>
inv
)
2
- 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI):
t =
t
E
>
inv
· {5.64 / [(I
E
/I
E
>
inv
)
2
- 1] + 0.024}
Electromechanical (EM):
t = 0.28 ·
t
E
>
inv
/ [-0.236 · (I
E
/I
E
>
inv
)
-1
+ 0.339]
I
E
:
residual current input
t
:
operate time
I
E
>
inv
:
pickup value;
t
E
>
inv
:
operate time setting
Asymptotic reference value:
1.1
I
E
>
Minimum operate time:
0.1
s
Equation is valid for 1.1 ≤ I
E
/ I
E
>
inv
≤ 20
,
with I
E
>
inv
pickup ≥
0.5
I
En
, the upper limit is
10
I
En