INSTALLATION
50
NA016 - Manual - 05 - 2022
6.5 NOMINAL CURRENT
I
n
SETTING FOR LPCT
LPCT amperometric phase inputs
Factory default settings:
• Primary nominal phase current
I
n
: 300 A
• Nominal residual current
I
En
: 1 A as shown in the previous pages)
To modify the phase rated currents, the dip-switches placed on the rear panel must be set.
[1]
Note 1 For LPCT versions the dip-switch position, located inside the CPU board, concerning the phase 1 A or 5 A current setting are irrelevant
C7
C8
F1
D1
RX
TX
F2
F3
F4
F5
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
A21
A22
B1
B2
B3
B4
B5
B6
B7
B8
E1
3
1
2
LPCT
Setting
(100+200)
300A
EX. In =
50
200
400
100
800
50
200
400
100
800
L3
L2
L1
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
In = 300 A (100 + 200)
Factory default setting
In = 50 A
Minimum setting
In = 1250 A (800 + 400 + 50)
Maximum setting
configurations not allowed !
cursor