FUNCTIONAL CHARACTERISTICS
4.1 CONFIGURABILITY
The DMC3S multifunctional panel features a modular construction with removable boards.
The panel can be customised for a variety of types of riser; the type of riser can be selected in the
Set \ Base
menu.
The firmware selected on the panel defines the measured values of amperometric channel C2, while
the measurements on voltmetric channel V4 must be selected from UE and V2 in the
Set \ Base
menu.
Measurement channels
Channel
Type of channel
Measurement
V1
Analogue voltage measurement channel
Phase voltage
U
L1
V2
Analogue voltage measurement channel
Phase voltage
U
L2
V3
Analogue voltage measurement channel
Phase voltage
U
L3
V4
Analogue voltage measurement channel
Phase voltage
U
E
/
V
sync
C1
Analogue current measurement channel
Phase current
I
L1
C2
Analogue current measurement channel
Phase current
I
L2
/
I
SQL
/
I
E
C3
Analogue current measurement channel
Phase current
I
L3
C4
Analogue current measurement channel
Residual current
I
E
Channel C2
Correspondence to panel A2
Type of riser
Assignment of channel C2
901
MV line stall
Measurement
I
L2
910
Capacitor stall
Measurement
I
SQL
922
TFN stall
Second measurement channel
I
E
907
Coupler stall
No measurement (
I
L2
)
[1]
905
Transfer bar
No measurement (
I
L2
)
[1]
917
User HV line stall
No measurement (
I
L2
)
[1]
Note 1 The system assigns the measurement to
I
L2
even when the input is not connected
I
L1
I
L2
I
E
I
SQL
CURRENT INPUTS
MA
C1
C2
C3
MA-1
MA-2
MA-3
MA-4
MA-5
MA-6
I
L3
NONE
Depending on the assignment of channel C2, the measurement and protection functions are given
in the table:
Measurement functions of
channel C2
Measurement assigned to C2 Measurement and protection functions Correspondence to panel A2
None
32P (
U
L1
;
U
L2
;
U
L3
;
I
L1
;
I
L3
)
51 (
I
L1
;
I
L3
)
67 (
U
12
;
U
23
;
U
31
;
I
L1
;
I
L3
; -
I
E
)
46 (not used)
51SQL (not active)
905 - 907 - 917
I
L2
32P (
U
L1
;
U
L2
;
U
L3
;
I
L1
;
I
L2
;
I
L3
)
51 (
I
L1
;
I
L2
;
I
L3
)
67 (
U
12
;
U
23
;
U
31
;
I
L1
;
I
L2
;
I
L3
)
46 (
U
L1
;
U
L2
;
U
L3
;
I
L1
;
I
L2
;
I
L3
)
51SQL (not active)
901
I
SQL
32P (
U
L1
;
U
L2
;
U
L3
;
I
L1
;
I
L3
)
51 (
I
L1
;
I
L3
)
67 (
U
12
;
U
23
;
U
31
;
I
L1
;
I
L3
; -
I
E
)
46 (not used)
51SQL
910
Second measurement channel
I
E
(51N)
32P (
U
L1
;
U
L2
;
U
L3
;
I
L1
;
I
L3
)
51 (
I
L1
;
I
L3
)
67 (
U
12
;
U
23
;
U
31
;
I
L1
;
I
L3
; -
I
E
)
46 (not used)
922