Manual BVS 19 ATEX E 080 X
C3
Edition March 2020
thuba Ltd., CH-4002 Basel
Copyright
Switzerland
1. Stufe
2. Stufe
3. Stufe
Description, Explanation
•
Internal nozzle diameter [mm]:
•
Minimum pressure while pre-purging [mbar]:
During pre-
purging procedure the PS840 monitors a increased pressure
inside of the Ex pzc-housing to achieve the defined flow on
the output valve. This increased pressure is monitored with
this parameter (range = 7.0 mbar ... max. pressure)
Minimum pressure at normal operation [mbar]:
Monitored minimum pressure
Maximum pressure at normal operation [mbar]:
Monitored maximum pressure
Signal pressure at normal operation [mbar]:
Menu code:
Code word to start the main menu.
Ex works: “0001”
It is not possible to deactivate this code with „0000“.
Bypass code:
Code word to start bypass mode.
The code can be disabled with „0000“ . The sequence „9999“
disables the bypass in general
Min.Pres.R
M-Code
Max.PRes
Sig. Pr.
Codes
By-Code
Nozzle
Min.Pres.P.
General
Mounting
inside hazardous area
Ex-protection
II 3G, Ex nA nC ic [pzc] IIC T6 Gc T
a
= 40°C
II 3G, Ex nA nC ic [pzc] IIC T5 Gc T
a
= 60°C
II 3D, Ex tc ic [pzc] IIIB T85°C Dc T
a
= 60°C
II 3D, Ex tc ic [pzc] IIIC T85°C Dc T
a
= 60°C
Ambient temperatures
–20°C ... 40°C at T6
–20°C ... 60°C at T5
Housing
Type of protection
IP65 (without considering purge medium outlet)
Dimensions
H x B x T: 220 mm x 120 mm x 90 mm
Material
Aluminium, lacquered / Ral 7035
electrical
specifications
Ex e Anschluss -
klemme
Power consumption
approx. 2,5 VA without solenoid valve
Main voltage
230 V AC, 115 V AC, 48...62 Hz ±10%
DC 24 V ±10%
Working circuits
terminal 1-4 (potentialfrei)
U
m
= 250V AC I
m
= 5A bei AC1 P
m
= 1500VA
U
m
= 250V AC I
m
= 1,2A bei AC15 P
m
= 300VA
U
m
= 30V DC I
m
= 5A bei DC1 P
m
= 150W
Solenoid valve
Terminal 5/6 Output voltage is equal to mains, protected by internal fuse
Min. and max.
clamping torque
min. 0,3 Nm
max. 0,4 Nm
Min. and max. wire cross-
section
Steep: 0,2 – 2,5 mm²
Flexible: 0,2 – 2,5 mm²
Mounting
Humidity
5–59 %, non-condensing
Technical details
Summary of Contents for PS 830
Page 41: ...Manual BVS 19 ATEX E 080 X 37 Edition March 2020 thuba Ltd CH 4002 Basel Copyright Switzerland...
Page 55: ...Manual BVS 19 ATEX E 080 X D3 Edition March 2020 thuba Ltd CH 4002 Basel Copyright Switzerland...
Page 56: ...Manual BVS 19 ATEX E 080 X D4 Edition March 2020 thuba Ltd CH 4002 Basel Copyright Switzerland...
Page 57: ...Manual BVS 19 ATEX E 080 X D5 Edition March 2020 thuba Ltd CH 4002 Basel Copyright Switzerland...
Page 58: ...Manual BVS 19 ATEX E 080 X D6 Edition March 2020 thuba Ltd CH 4002 Basel Copyright Switzerland...
Page 59: ...Manual BVS 19 ATEX E 080 X D7 Edition March 2020 thuba Ltd CH 4002 Basel Copyright Switzerland...
Page 60: ...Manual BVS 19 ATEX E 080 X D8 Edition March 2020 thuba Ltd CH 4002 Basel Copyright Switzerland...
Page 61: ...Manual BVS 19 ATEX E 080 X D9 Edition March 2020 thuba Ltd CH 4002 Basel Copyright Switzerland...