Chapter 2: Installation
14
Installing the Power Supply Unit and Charger
Battery connector (X2)
The Power Supply Unit and Charger can charge a connected battery.
In case of overload and/or missing AC power the power supply seamlessly
delivers power from the connected battery.
The default maximum charging current is 8 A. The default float voltage is
27.2 V at 20° C. These values depend on the size of the battery, check the
documentation for the battery.
The maximum charging current and the float voltage can be configured, for
further details see Customizing battery settings on page 33.
Battery temperature sensor S1 (X9)
In order to optimize the battery charging profile, a temperature sensor may be
mounted on the battery and connected to X9-S1. It is part of the delivery and
available as an option. You can order it from Thrane & Thrane (part number:
406081-010).
BATTERY (X2)
Connector type
Wire terminal
Screw size
5 mm
+
Battery plus
-
Battery minus
M5 in chassis
GND for drain wire (cable shield)
Fuses
One 50 A fuse plate for battery plus and one for the
battery minus. You must use the fuse with the
Thrane & Thrane part number S-33-205377-050.
Note
One battery temperature sensor serves all cross-linked units.
Summary of Contents for Sailor 6081
Page 1: ...INSTALLATION USER MANUAL SAILOR 6081 Power Supply Unit and Charger ...
Page 39: ...Chapter 3 Service and repair 32 Returning units for repair ...
Page 43: ...Chapter 4 Customizing battery settings 36 Changing battery settings ...
Page 61: ...Appendix B Upgrade 54 Upgrading with additional SAILOR 6080 units ...
Page 63: ...Appendix C Approvals 56 Wheelmark ...
Page 68: ...98 130980 A Thrane Thrane A S info thrane com www thrane com ...