Installation and Commissioning
Instructions
Technical Data
OPERATING VOLTAGE: 230V 50Hz
RECOMMENDED CIRCUIT PROTECTION: 10A
TERMINAL CAPACITY: 2 x 2.5mm
MAXIMUM LOAD: 6A per output [not exceeding 10A in total]
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3 metres
RANGE: Cone-shaped detection
pattern, diameter (at floor level)
= 2.4 x mounting height
PHOTOCELL: Adjustable 50-5000 lx via SENP (96004189)
OFF DELAY 1 & 2: 1 minute - 96 hours adjustable (5 - 35 minutes via SENP) and 10 second Walk Test Mode
COLOUR: White
MATERIAL: Flame retardant ABS
WEIGHT: 200g approx
IP RATING: 40
2
POWER CONSUMPTION: <10W
W4235B
Dimensions
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
Note: SENP Programmer (96004189) reqd. for commissioning
User override available via SENRC
Hand-held Controller (96004175)
Setting the Photocell
Washroom Mode
1.
If the lights are not already on, switch them on manually by pressing the
‘
up
’
button of the SENP (96004189).
Fluorescent lights do not reach full output until up to 15 minutes after being switched on, so ensure that the lights are
fully warmed up before continuing. This stage may be omitted if the intention is to operate the detector
’
s photocell
in Passive Mode only [the detector must have already been programmed to Passive Mode].
2.
Wait until the time of day when the natural light level is at the point below which you
want the lights to be on,
and above which you
want the lights to be on.
3.
Start the internal self-programming mechanism by pressing the
‘
Store
’
button of the SENP. The detector takes a
measurement, adds a small amount and stores the value in the Upper Threshold. Then it turns the lights off, makes
another measurement and stores the value in the Lower Threshold.
The lights now switch on again to
acknowledge a successful programming operation.
The two switching thresholds have now been set, and the difference between them is equal to the contribution made by
the electric lighting; this is the perfect amount of hysteresis to ensure that the lights will not oscillate. Please note that
the values are non-specific units i.e. not lx.
The unit may be used in conjunction with a 230V solenoid valve and a trickle valve or
‘
petcock
’
to effect a urinal flush
system. Set the water flow rate by adjusting the petcock so that the cistern
fills within the chosen Off Delay period of
the detector. Note that in this mode, the photocell should be disabled, unless using the dual output unit.
would
would not
just
MSF
MRE
Lights ON =
Lights OFF =
Upper Threshold
Lower Threshold
Natural
Light
Level
Duration of
Off Delay
Note that when the natural light
level exceeds the
‘
upper threshold
’
value, the lights do not immediately
turn off. They will turn off only when
the upper threshold has been
exceeded for the duration of the
programmed Off Delay.
Active Mode
Passive Mode
Occupancy
Area Occupied =
Area Unoccupied =
100mm
10mm deep
(Flange)
62mm
deep
(behind ceiling)
SWITCHLITE MRE SLD2 (96013492)
SWITCHLITE MSF SLD2 (96013493)
Switchlite Dual Circuit detectors, ceiling
mounted, recessed (MRE) or surface (MSF)
(formerly known as S3D2PF and SD2PSM)
Thorn Lighting Limited
www.thornlighting.com
6.0m
2.5m