W4047H
Installation and Commissioning
Instructions
Note: SENSA SENP required for commissioning
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
Electrical Connections
115mm
65mm
Supply
230V
50Hz
Push-to-Make
Mains-Rated
Retractive Switch
Brown
Blue
Orange
White
DSI out (96211279)
DALI out (96238877)
Polarity-free; do not connect to other detectors.
Red
L
N
Sensa Digital Detector,
ceiling mounted
SENSA MRE SEND DSI (96211279)
SENSA MRE SEND DALI (96238877)
Thorn Lighting Limited
www.thornlighting.com
T
Input
(see overleaf)
Technical Data
RECOMMENDED MAXIMUM MOUNTING HEIGHT: 3.0m
RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height
OPERATING VOLTAGE: 230V 50Hz
PRODUCT RATING & RECOMMENDED CIRCUIT PROTECTION: 10 Amps
CAPACITY: 8 ballasts
OUTPUT: 2-wire digital polarity free-max extended cable length: 12m
PHOTOCELL: Regulating
OFF DELAY: 5-35 minutes
DEPTH REQUIRED BEHIND CEILING: 125mm
WEIGHT: 70g approx excluding cable
COLOUR: White
MATERIAL: Flame retardant PC/ABS
IP RATING: IP 40
6.0m
2.5m