background image

W4047H

Installation and Commissioning

Instructions

Note: SENSA SENP required for commissioning

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Electrical Connections

115mm

65mm

Supply

230V
50Hz

Push-to-Make

Mains-Rated

Retractive Switch

Brown

Blue

Orange

White

DSI out (96211279)
DALI out (96238877)
Polarity-free; do not connect to other detectors.

Red

L

N

Sensa Digital Detector,

ceiling mounted

SENSA MRE SEND DSI (96211279)

SENSA MRE SEND DALI (96238877)

 

Thorn Lighting Limited
www.thornlighting.com

T

      Input

      (see overleaf)

Technical Data 

   

RECOMMENDED MAXIMUM MOUNTING HEIGHT: 3.0m
RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height

OPERATING VOLTAGE: 230V 50Hz 
PRODUCT RATING & RECOMMENDED CIRCUIT PROTECTION: 10 Amps
CAPACITY: 8 ballasts  
OUTPUT: 2-wire digital polarity free-max extended cable length: 12m
PHOTOCELL: Regulating
OFF DELAY: 5-35 minutes
DEPTH REQUIRED BEHIND CEILING: 125mm
WEIGHT: 70g approx excluding cable
COLOUR: White
MATERIAL: Flame retardant PC/ABS
IP RATING: IP 40

6.0m

2.5m

Reviews: