402C1238 Iss.
01
PROVISIONAL INSTRUCTIONS
THORN EMI Heating
MAINTENANCE
Apollo Fanfare 15/30 and 30/50
Wall mounted gas boilers
G.C. Appliance Nos. Apollo Fanfare 15/30 41 789 71 Apollo Fanfare 30/50 41 789 72
(Leave these instructions adjacent to the gasmeter).
General
This booklet describes the annual maintenance procedure, provides instruction on the
replacement of faulty parts and information on fault finding and spare part identification.
Before commencing work slide off the bottom cover and slide the gas valve operating button in the
direction of the arrow to turn off the pilot. Allow the boiler to cool. Isolate the electricity supply
and turn off the gas supply at the service tap, see
frame 36
.
IMPORTANT: ALWAYS test for gas soundness after completing any servicing or exchange of gas
carrying components. Ensure that the inner case seal is intact and the case properly fitted after
servicing or replacement of parts.
NOMINAL BOILER RATINGS
BOILER
OUTPUT
INPUT
BURNER SETTING
kW
Btu/h
kW
Btu/h
mbar
Fanfare
4.4
15 000
5.6
19 200
4.6
15/30
6.6
22 500
8.4
28 700
10.0
8.8
30000
11.0
37500
14.8
Fanfare
8.8
30 000
11.4
38 900
5.6
30/50
11.7
40000
14.9
50900
9.2
14.7
50000
18.3
62 500
13.7