background image

Concrete

1/8"

Finished Floor 

Floor Box

 

FIGURE 1

Cut top of Floor Box or Floor 

box Extension (not shown) off

1/8" below finished floor 

FIGURE 2

Data Cables 

1" Conduit

3/4" Conduits

"Through"

Data Cable

FIGURE 3A

FIGURE 3B

Assemble Divider

(Do Not Glue)

Divider
Assembly

68P-EXT-DIV

(Optional,

Sold Separately)

FIGURE 4

Mark edges

of Divider at top of Floor Box

Marked edge 
See Figure 4

Cut

Measure 1/2" then cut Divider 
at next molded score line

Use a Razor Knife 
(Utility Knife) to score 
long groove on side of 
divider or divider 
extension (not shown).
Bend back and forth 
to remove cut portion.

FIGURE 5

Installation Instructions for 68P Dual Voltage Kit

Catalog Numbers

 

68P-DV-KIT-BRS & 68P-DV-KIT-AL

WARNING

BE SURE POWER IS OFF!

PRODUCT DESCRIPTION

• 

The 68P-DV-KIT is a floor box cover and divider kit to be used in the 
Thomas & Betts 68P nonmetallic round floor box. It is designed to 
accommodate one standard duplex or GFCI style receptacle and 
four data/communication jacks. The standard configuration is for 
keystone jacks. Other data plates are available for other jack 
configurations.

• 

The Kit includes the cover, face plate with data plates, mounting ring 
and dual voltage divider. It does not include the receptacle or 
data/communication jacks.

• 

The cover is solid metal construction and features a snap-shut lid.

INSTALLATION INSTRUCTIONS

1) 

Verify that 68P round floor box or 68P-EXT floor box extension has 
been prepared for installing the 68P-DV-KIT. The top surface of the 
floor box or 6” extension will need to be cut 1/8" below finished 
floor height as shown in Figure 1(below). Finished floor may be 
carpet, wood, vinyl or ceramic tile.

2) 

Pull data cable up through opening in box. Pass "through" cable 
to other side of box and through conduit opening(s), see Figure 2.

 

 NOTE:

 

Data cable may enter the box from either the two 1" 

conduit openings (as shown), or it may enter through the four 3/4” 
conduit openings.

 

The 68P-DV-KIT will work with either conduit 

The 68P-DV-KIT will work with either conduit 

arrangement.

arrangement.

3) 

Assemble divider halves, see Figure 3A. Do not glue! Lower divider 
assembly into 68P floor box so that data cables exit the floor box 
on outer sides of the divider assembly. Verify the divider ramp 
covers any data cable that runs through the box. Make sure 
divider assembly is resting on the bottom of the 68P floor box,  
see Figure 4.    

 

 

 

 NOTE:

 

When using the 68P-EXT floor box extension, the 

68P-DVD-EXT Voltage Divider Extension (not included) is required. 
Snap (do not glue) the divider extensions onto top of the Divider 
Assembly provided, see Figure 3B.

4) 

Make a mark on the divider sides where they meet the top of the 
cut floor box, see Figure 4.

5) 

Remove the divider halves or divider extensions from the floor 
box. Make a second mark at 1/2” below or the next molded score 
line on the divider or divider extensions. Score (cut) the divider or 
divider extensions at the second mark and remove the cut portion, 
see Figure 5. 

 

 

 

 

     

NOTE:

 

When reinserted in the floor box, the top of the divider 

assembly should be 1/2” to 9/16” from the top of the 68P floor 
box, see Figure 7.

TA02485  C     Page 1 of 2