Fault
code
Failure
Display
Fault name
Cause
Countermeasure
1
Er.oc1
Over-current in
acceleration
Torque boost value is too
large at scalar control
Reduce torque boost value
Great starting frequency
Reduce the starting
frequency value
Short acceleration time
Prolong acceleration time
Improper setting of motor
parameters
Correct setting of motor
nameplate
Weight overload
Reduce overload
Restart the rotating motor
Reduce the current limit
value or start with speed
search
Output interphase short
circuit or short circuit to
ground
Check motor wiring and
output impedance to
ground
V/F curve is not suitable at
scalar control
Correct set of V/F curve
2
Er.oc2
Over-current
during
deceleration
Short deceleration time
Prolong deceleration time
There is no additional brake
unit and brake resistor
Add braking unit and
resistance
3
Er.oc3
Over current in
constant speed
Small Variable Frequency
Drive power level
Select the appropriate
Variable Frequency Drive
power
Low grid input voltage
Check grid voltage
Weight overload
Reduce overload
4
Er.ou1
Over-voltage
during
acceleration
Abnormal input voltage
Check grid voltage
Short acceleration time
Prolong acceleration time
Large load inertia
Use energy braking
5
Er.ou2
Over-voltage
during
deceleration
Short deceleration time
Prolong deceleration time
Abnormal input voltage
Check grid voltage
Large load inertia
Use energy braking