User Manual of TI10 Series Variable Frequency Drive
- 34 -
Parameter
Name
Setting range
Factory value
Register
address
Properties
P40 Process PID Control Parameters
P40.00
PID given
mode selection
0: given by P40.01
1: analog input AI1
2: analog input AI2
3: reserve
4: Min[AI1,AI2]
5: Max[AI1,AI2]
6: Sub[AI1,AI2]
7: Add[AI1,AI2]
8: pulse given HDI
0
0x4000
●
P40.01
PID digital
given
0.0%~100.0%
50.0%
0x4001
○
P40.02
PID feedback
mode selection
0: constant zero
feedback input
1: analog input AI1
2: analog input AI2
3: reserve
4: Min[AI1,AI2]
5: Max[AI1,AI2]
6: Sub[AI1,AI2]
7: Add[AI1,AI2]
8: pulse given HDI
1
0x4002
●
P40.03
Proportional
gain Kp1
0.0~100.0
50.0
0x4003
○
P40.04
Integral time
Ti1
0.000s~50.000s
0.500s
0x4004
○
P40.05
Differential
time Td1
0.000s~50.000s
0.000s
0x4005
○
P40.06
Proportional
gain Kp2
0.0~100.0
50.0
0x4006
○
P40.07
Integral time
Ti2
0.000s~50.000s
0.500s
0x4007
○