User Manual of TI10 Series Variable Frequency Drive
- 32 -
Parameter
Name
Setting range
Factory value
Register
address
Properties
drop detection
level of
Variable
Frequency
Drive
P30.08
Output load
drop detection
time of
Variable
Frequency
Drive
0.0s~3600.0s
1.0s
0x3008
●
P30.09
Selection of
automatic
reset times
0~100
0: no automatic reset
function
0
0x3009
●
P30.10
Automatic
reset interval
time
0.1s~100.0s
1.0s
0x300A
●
P30.11
Selection of
fault relay
action
Ones: during automatic
reset
0: action
1: no action
Tens: under-voltage
period
0: action
1: no action
00
0x300B
●
P30.12
Option of
enhanced
protection
function
Ones: output phase
lack detection
0: forbidden
1: action
Tens: input phase lack
detection
0: forbidden
1: action
Hundreds: motor
overload detection
0: forbidden
1: action
000
0x300C
●