User Manual of TI10 Series Variable Frequency Drive
- 22 -
Parameter
Name
Setting range
Factory value
Register
address
Properties
completed
26: PLC stage
completed
27: reserve
28: reaching cumulative
power-on time
29: reaching cumulative
running time
30: reaching the setting
count value
31: reaching the
specified count value
32: reaching the setting
length
33-35: reserve
P11.04
Y output
closing delay
0.0s~3600.0s
0.0s
0x1104
○
P11.05
Y output
disconnecting
0.0s~3600.0s
0.0s
0x1105
○
P11.08
R output
closing delay
0.0s~3600.0s
0.0s
0x1108
○
P11.09
R output
disconnecting
delay
0.0s~3600.0s
0.0s
0x1109
○
P11.12
Logic state
setting of
output terminal
BIT0: Y
BIT2:R
0: positive logic
1: negative logic
00
0x110C
○
P11.13
FDT1
detection
mode
0: check out by
operating frequency
1: check out by output
frequency
0
0x110D
○
P11.14
FDT1 upper
level limit
P11.15~maximum
frequency
2.50Hz
0x110E
○
P11.15
FDT1 lower
level limit
0.00Hz~P11.14
2.00Hz
0x110F
○
P11.16
FDT2
detection
mode
0: check out by
operating frequency
1: check out by output
frequency
0
0x1110
○