nformation about Smart Acknowledge (SmartACK) 

This bi-directional communication mechanism also allows the building system to send back data to a sensor, i.e. to overwrite 
SR06LCD´s set point. Smart Acknowledge requires that both communication devices do support the Smart Acknowledge 
mechanism. 

Repeaters are not supported, they delay in the telegram transmission. Sensor and gateway must communicate directly with each 
other. 

Additional Information of the used EEP´s with Smart ACK can be found using the following link: 

http://www.thermokon.de/download-archive/Kataloge_Preise_Infos/Allg.%20Dokumente/Informationen/SmartACK-Info_en.pdf

  

T

echnical Data 

Network technology 

 

RS485 Modbus, RTU or ASCII, half-duplex, baud rate 9.600, 19.200, 38.400 or 
57.600, parity none (2 stopbits), even or odd (1 stopbit) 

Radio technology 

 

EnOcean (IEC 14543-3-10) 

Frequency 

 

902 MHz 

Antenna 

 

external transmit- / receive antenna 

Data transmission 

 

bidirectional 

Power supply 

 

15..24 V = (±10%) or 24 V ~ (±10%) 

Power consumption 

 

typ. 0,6 W (24 V =) | 1,5 VA (24 V ~) 

Enclosure 

 

PA6.6, cover PC, transparent with quick lock screws 

Protection 

 

IP42 according to EN 60529 

Cable entry 

 

M20 for cable max. Ø=0.31in. 

Connectional electrical 

 

terminal block, max. 15AWG 

Ambient condition 

 

-4..+140 °F, max. 85% rH non-condensing 

Weight 

without antenna 

3.88oz. 

Delivery content 

 

external transmit- / receive antenna 

Notes 

 

up to 15 devices with Smart Acknowledge (SmartACK) 

 

 

magnetic antenna holder required for better radio range 

M

ounting Advices 

The module enclosure is prepared for direct wall mounting. For the operation a separate external 902 MHz receiving antenna is 
necessary, which is included in shipment as a standard. 

The antenna should be mounted at metallic objects, e.g. at an air tube behind a false ceiling or at an 7.09in. x 7.09in metal plate 
(material: galvanized sheet steel, see accessories). 

If  possible  the  antenna  should  be  mounted  with  a  distance  of  >  4in.  from  the  ceiling  and  from  a  wall.  The  distance  to  other 
transmitters (e.g. GSM / DECT / wireless LAN / EnOcean sender) should be minimum 1.6ft. 

The  antenna should  be  vertically  aligned  downwards.  The  antenna  cable should  be  wired  in  an  electric conduit.  A  crushing  of 
cable shall be absolutely avoided. The minimal bend radius of the extension cable is 2in. 

As for the cable laying the use of an active pull-up device should be avoided, in order to avoid any damages to the sheathing 
respectively to the connectors. 

 

 