2009-07-09
If the slide switch is selected, the gateway evaluates the
status of the switch every time a telegram is sent. If the
status has changed, the corresponding telegram is sent.
Comm. object
KNX (EIB) type
Size
Channel … : Presence
1.001 (EIS 1)
1 bit
-
Set point adjustment
For the set point adjustment, the temperatures that are to
be sent when the switch is positioned all the way to the left
and right can be set. These two limit values are used to
calculate the values sent for the positions between these
limits. The resolution is 0.5°C. If the right limit is lower than
the left limit, the values are exchanged. The maximum ad-
justable range of the limit values is from -30 °C to +30 °C.
Comm. object
KNX (EIB) type
Size
Channel … : Set point
Temperature
9.001 (EIS 5)
2 bytes
-
Multiple contact switch
Depending on the device type, different functions are
available for the multiple contact switch:
Omnio devices have 4 stages for the "Automatic”, “Day”,
“Night” and “Frost” control modes. If the switch is set to
one of these stages, an ON telegram is sent for that mode.
Comm. object
KNX (EIB) type
Size
Channel … : Automatic
1.001 (EIS 1)
1 bit
Channel … : Day
1.001 (EIS 1)
1 bit
Channel … : Night
1.001 (EIS 1)
1 bit
Channel … : Frost
1.001 (EIS 1)
1 bit
Thermokon devices have 5 stages: “AUTO“, “0“, “I“, “II“
and “III“. If the switch is set to stages “I“, “II“ or “III“, the
percentage set in the parameter settings is sent as a tele-
gram.
If the switch is set to stage “0“, a value of “0%“ is sent. An
OFF telegram is also sent, for example to close the
valves. If the switch is changed from the “0” stage to an-
other stage, an ON telegram is sent, for example to open
the valves again.
If the switch is set to the “AUTO“ stage, an ON telegram is
sent from the corresponding communications object. If the
switch is changed from the “AUTO“ stage to another
stage, an OFF telegram is sent.
Comm. object
KNX (EIB) type
Size
Channel … : Fan stage
5.001 (EIS 6)
1 byte
Channel … : Automatic
1.001 (EIS 1)
1 bit
Channel … : Valves
1.001 (EIS 1)
1 bit
-
Humidity sensor
When this Thermokon series is selected, the relative hu-
midity value delivered by the sensor is transmitted.
Comm. object
KNX (EIB) type
Size
Channel … : Rel. humidity
5.001 (EIS 6)
1 byte
Window contact
Up to 4 EnOcean window contacts can be linked to one
channel. Which telegram is sent when a window is opened
or closed can be set in the parameter settings. When a
single open window is detected, the telegram for open
windows is sent. The telegram for closed windows is not
sent until the last window is closed.
Comm. object
KNX (EIB) type
Size
Channel … : W indow
1.001 (EIS 1)
1 bit
Other sensor
-
Thermokon SR65LI light sensor
If this option is selected, the lux value sent by the sensor
is transmitted to the bus.
Comm. object
KNX (EIB) type
Size
Channel … : Lux
9.004 (EIS 5)
2 bytes
The light measurement range defined using jumpers on
the sensor must be set correctly in the parameter settings.
-
Thermokon SR65DI binary input
If the contact at the sensor input is closed, the gateway
sends an ON telegram. If the contact is opened, it sends
an OFF telegram. The sent value can be inverted by set-
ting a parameter.
Comm. object
KNX (EIB) type
Size
Channel … : Binary input
1.001 (EIS 1)
1 bit
-
Thermokon SR PIR 360° motion detector
If the sensor detects motion, the gateway sends an ON
telegram. It sends an OFF telegram after a time period
that can be set on the sensor. The sending of this tele-
gram after expiration of the time period can be suppressed
in the parameter settings. The telegram to be sent can be
inverted by setting a parameter.
Comm. object
KNX (EIB) type
Size
Channel … : Movement
1.001 (EIS 1)
1 bit