Learn mode
EnOcean devices are learned on the two keys below the
display:
Left, brief pressure: “Enter Learn“: Start learn mode
Left, extended pressure: “Erase“: Delete channel
Right, brief pressure: “Test“: Send test telegram(s)
Right, extended pressure: “Exit Learn“: Quit learn
mode
"Extended pressure" means pressing the key for at least 2
seconds.
When the device is in normal mode, brief pressure on the
left key (
“Enter Learn”
) switches it into learn mode.
Briefly pressing the left key again switches to the next
channel. The display alternates between the current chan-
nel number and the number of connected EnOcean de-
vices. A dot in the center of the display indicates that the
number of EnOcean devices is being displayed. To the
right of the dot is the number of connected devices. If a
further connection to this channel is not possible, the dis-
play shows an “F”. To the left of the dot is the function set
for that particular channel in the parameter settings:
A: Switching
B: Dimming with stop telegram (b)
C: Blind
D: Temperature sensor (d)
E: Window contact
F: Other sensor
In this mode, a transmitting EnOcean device can be con-
nected to a cable if the device type matches the function
defined in the parameter settings.
A connection is created by pressing the learn key (tem-
perature sensor, window contact, light sensor, motion de-
tector, binary input) or the key (switch module) on the
EnOcean device.
If “Switching“, “Dimming“ or “Blind“ is selected in the
channel parameter settings, the channel can be linked
with up to four different rockers or keys (with one-key con-
trol).
For the rocker functions, two opposite keys on a switch
module are grouped to one rocker, so that up to four dif-
ferent rockers can be connected per channel.
By briefly activating the right key (
“Test”
), the communi-
cations objects connected to this channel are sent on the
bus if the communications objects are assigned group ad-
dresses.
The learn mode is terminated with extended pressure on
the right key (
“Exit Learn”
) or automatically if not oper-
ated for over 5 minutes.
Deleting assignments
Links to EnOcean devices are deleted by:
applying extended pressure to the left key
(
“Erase”
) in learn mode (current channel)
programming the application program on the ETS (all
channels)
If the function of a channel is changed, partial program-
ming of the parameters on the ETS clears the links of the
changed channel.
Normal mode
If the telegram of an EnOcean device is received in normal
mode, every channel checks whether this device is as-
signed to it. If so, the number assigned to the respective
channel is displayed briefly on the LCD and one or more
telegrams relating to the function are sent on the bus. The
frequency with which telegrams are sent is determined by
the EnOcean device. The gateway only sends telegrams
on the bus if a corresponding EnOcean telegram was re-
ceived. If a received EnOcean telegram is not assigned to
a channel, a zero appears in the display.
Gateway functions
One of the following functions can be selected for each of
the 32 channels. The selection is made in the Parameters
menu of the ETS.
Switching
The following switching functions can be selected in the
parameter settings:
-
Toggling (Key)
Brief or extended pressure on the key causes the last ON
or OFF telegram sent on the bus to be inverted and sent.
If the write flag of the corresponding communications ob-
ject is set on the ETS, the current value can also be set by
the bus. In this way, the changeover function (toggle) can
also be synchronized with other keys on the bus.
-
Off (Key)
Brief or extended pressure on the key causes an OFF
telegram to be sent.
-
On (Key)
Brief or extended pressure on the key causes an ON tele-
gram to be sent.
-
Value (Key)
Brief or extended pressure on the key causes the value
defined in the parameter settings to be sent (e.g. dimming