Thermokon PDE2 Series Mounting Instruction Download Page 1

Measured

Differential Air Pressure

Sensor Characteristics

Passive

Sensor Output (s)

ON / OFF

Measuring Range (s)

See Product Range, Page 1

Default TOP Switching Point (s)

See Product Range, Page 1

Differential Gap

See Product Range, Page 1

Repeatability

2%

Over Pressure

Max. 7.5kPa

Switching Cycles

> 1.000.000

Switch Type

Single-pole, change over contact
Screw terminal, max. 2.5mm²

Relay Rating

AC 250V, max. 3A; DC 30V, max. 2A

Connection Nozzle Dimension
Cable Entry

M16, Ø6...Ø8mm cables
Internal, bottom of the housing

Set Point Adjustments

See Product Range, Page 1
No button / Automatically

Housing Cover

White PC, RAL9010 (Pure White), with Clear Window
Grey PC, RAL7042 (Traffic Grey A)

Lock Screws

US:AISI 304; EU: EN X 6 CrNi 18 10; GER: W.N. 1.301

Lock Nuts

Brass

Cable Gland

Red ABS, RAL2002 (Vermilion)

Gland Rubber Seal

White TBS, RAL9010 (Pure White)

Protection Caps

Red ABS, RAL2002 (Vermilion)

User element

Red ABS, RAL2002 (Vermilion)

Connection Nozzle

Grey PC, RAL7042 (Traffic Grey A)
Silicone, emission free

Operation Temperature
Operation Humidity

<85% r.h., no condensation

Transport Temperature

-35

C...+70

Transport Humidity

< 90% r.h.

Storage Humidity

< 85% r.h., no condensation

IP- Rating

IP54 to IEC60529

Safety Class

III to EN 60 730

Product Standard 1

2009/EN 60 730-1

CE Conformities to

2004/108/EG Electromagnetic Compatibility EMV

CE  Electromagnetic Compatibility  Emitted Interference

2000/EN60730-1 Emitted Interference

CE  Electromagnetic Compatibility Interference resistance

2000/EN60730-1 Interference Resistance

RoHS Compatibility

RoHS 2011/65/EC

Operation Climatic Condition 

IEC 60 721-3-3

Operation Mechanical Condition

IEC 60 721-3-2 to class2M2

Transport to Climatic Condition 

IEC 60 721-3-2

Transport Mechanical Condition

IEC 60 721-3-2 to class2M2

Storage Climatic Condition 

IEC 60 721-3-1

Storage Mechanical Condition

IEC 60 721-3-1 to class2M2

Automatic Electric. Controls for household and similar use

Product Standard 2

3250e_MIS

Mounting Instruction

PDE2- Series (dP)

Air Differential Pressure Switch

Terminal Clamp

Mechanical Information

Storage Temperature

-10

C...+70

Norms and Directives

All Information and technical data are subject to alternation

Thermokon

PDE2- Series (dP) V1.2

Page 1/2

The PDE2-Series is designed to measure differential pressure in HVAC systems with non-flammable gases and non-
aggressive gases. The control output is 2-point (ON/OFF). The differential switch has an internal set point adjuster. 

Pr

oduct

 Range

Se

ns

or

 Spe

cificat

ions

Te

chn

ical 

In

for

ma

tion

Ø6.3 x 1.15mm, L=10mm

Sensing Element Position

User Interface

Release Button

Color and Materials

Housing Bottom

Diaphragm

Environmental Conditions

-25

C...+70

Sensor Specification