Hygienic circuit control
For reasons of hygiene, stagnant water in the pipe should be avoided. The hygiene circuit is used to
drain the water pipe from the main water valve to the device (see also chapter 6.4.6 “
This function must be set to “ON” in the device settings
System
Humidification
“Hygienic circuit”
. Otherwise, the control has no effect!
There are the following options for control:
Signal type:
Binary
0 = OFF, 1 = ON
Options:
Internal *
If the adiabatic system is switched off (no
water requirement), the function is activated
after the set waiting time in the
Main menu
Wet mode
“Hygienic circuit”
. The function is
only deactivated again after a new requirement
for humidification / wetting.
Via terminal
+ 24 V DC at terminal X7.7 (DI-7), selectable in
the
Device settings
Inputs / Outputs
“
Digital IN basic unit
”
see also chapter 1.4 (Circuit diagram TCS.2)
Via bus
The type of communication bus is set in the
Device settings
BMS bus system
[see also
chapter “4.5 „
The following parameters apply to direct
communication via MODBUS:
Register 1, bit 14 (Bool), (register value 16384)
Off
Function deactivated.
* Factory setting