Delay humidification ON
Switch-on condition for spray level [No] which defines a delay in minutes after the preconditions (
①
and
③
) have been met. This delay prevents constant switching on and off of the respective spray
level and gives the controller the necessary time to “settle in”.
Editable from … to:
1 … 600 s
Factory setting:
60 s
Water excess factor
Specifies the value by which the required amount of evaporation water is multiplied. This is necessary
to guarantee the long-term moistening of the mats and to limit the risk of deposits and soiling due to
drying out. The factor can be edited in the range 1.0 to 3.0.
If the adiabatic system is activated, it needs more water in the startup phase as the paper
mats first have to soak up. Therefore, the excess water is set to 2.5 in the first 30 minutes. If
the excess is generally over 2.5, it remains unchanged.
efficiencySLIDE
The
efficiencySLIDE
generally regulates how often and how long the adiabatic system is used
during the year. In the
water-saving
position, the adiabatic is only activated in case of peak load,
when the fan speed limit is reached. With
energy-saving
operation, the adiabatic switches on earlier
and is also active longer and more often. The slide can be moved anywhere between these points.
Its colour indicates the mode of operation and a numerical value (0-10) indicates the position. The
position of the slide is also shown in the
Mat menu
Precise pre-setting of the switch-on and switch-off limits and the ratio (speed - possible pre-
cooling) in the efficiencySLIDE settings is of great importance in order to use the slide
effectively!