Refrigeration Service Procedures
130
Gauge Manifold Sets
Gauge manifold sets that show the correct
pressure-temperature relationship should be used.
Gauge manifolds and manifold hoses used with
other Thermo King refrigerants maybe used but
extreme care should be taken to prevent
contamination of the R404A systems with other
refrigerants. Purge manifold and hoses with dry
nitrogen before using.
Never use equipment that
may be contaminated with automotive type
Polyalkylene Glycol (PAG) oils.
Refrigerant Recovery
Systems used for the recovery of R404A should
be dedicated to the recovery of this refrigerant.
Consult the manufacturer of your recovery
equipment for details.