Refrigeration Service Operations
86
Installation
1. Place the evaporator coil in the evaporator
housing and install the mounting bolts.
2. Solder the hot gas line and suction line
connections to the evaporator coil.
NOTE: Replace any other refrigeration tubes
that were removed.
3. Solder the distributor to the expansion valve.
4. Replace and connect the sensors.
5. Pressurize the low side and test for leaks. If no
leaks are found, evacuate the low side.
6. Clean the suction line to a bright polished
condition. Install the feeler bulb on the side of
the suction line in its former position. The
feeler bulb must make good contact with the
suction line or operation will be faulty. Wrap
with insulating tape.
7. Replace the upper and lower evaporator
access panels.
8. Open the refrigeration valves and place the
unit in operation. Check the refrigerant charge
and compressor oil. Add as required.
Accumulator
Removal
1. Pump down the low side and equalize the
pressure to slightly positive.
2. Unsolder the inlet and outlet suction lines
from the accumulator.
3. Unbolt and remove the accumulator from the
unit.
Installation
1. Place the accumulator in the unit and tighten
the mounting bolts and nuts.
2. Solder the inlet and outlet suction lines to the
accumulator.
3. Pressurize the low side and test for refrigerant
leaks. If no leaks are found, evacuate the low
side.
4. Open the refrigeration valves and place the
unit in operation. Check the refrigerant charge
and the compressor oil, and add as required.
Suction Vibrasorber
Removal
1. Pump down the low side and equalize the
pressure to slightly positive.
2. Unsolder the suction vibrasorber from the
suction service valve.
3. Unsolder the connection to the accumulator
and remove the vibrasorber from the unit.
Installation
1. Prepare the suction vibrasorber and tube
fittings for soldering by cleaning thoroughly.
2. Solder the vibrasorber to the suction service
valve.
3. Solder the suction hose connection to the
accumulator.
4. Pressurize the low side and check for leaks. If
no leaks are found, evacuate the system.
5. Open the refrigeration valves and place the
unit in operation. Check the refrigerant charge
and the compressor oil, and add as required.
CAUTION: Use a heat sink or wrap
vibrasorber with wet rags to prevent
damaging the vibrasorber.
CAUTION: Use a heat sink or wrap
vibrasorber with wet rags to prevent
damaging the vibrasorber.
CAUTION: Use a heat sink or wrap the
vibrasorber with wet rags to prevent
damaging the vibrasorber.
CAUTION: Use a heat sink or wrap the
vibrasorber with wet rags to prevent
damaging the vibrasorber.
Summary of Contents for Spectrum DE 30-2
Page 4: ...4...
Page 12: ...Safety Precautions 12...
Page 16: ...Specifications 16...
Page 31: ...Unit Description 31 1 Access Panels 2 Defrost Dampers Figure 12 Back View of Unit 1 2 AGA215...
Page 42: ...Operating Instructions 42...
Page 48: ...Electrical Maintenance 48...
Page 106: ...Structural Maintenance 106...
Page 110: ...Mechanical Diagnosis 110...
Page 114: ...Remote Evaporator Specifications 114...
Page 116: ...Remote Evaporator Maintenance Inspection Schedule 116...
Page 122: ...Remote Evaporator Electrical Maintenance 122...
Page 126: ...Remote Evaporator Refrigeration Service Operations 126...
Page 128: ...Remote Evaporator Structural Maintenance 128...
Page 130: ...Remote Evaporator System Diagnosis 130...
Page 134: ...Wiring and Schematic Diagrams Index 134...
Page 135: ...135 Schematic Diagram Page 1 of 2...
Page 136: ...136 Schematic Diagram Page 2 of 2...
Page 137: ...137 Wiring Diagram Page 1 of 4...
Page 138: ...138 Wiring Diagram Page 2 of 4...
Page 139: ...139 Wiring Diagram Page 3 of 4...
Page 140: ...140 Wiring Diagram Page 4 of 4...