Refrigeration Maintenance
112
Unit Evacuation
NOTE: The electrical system must be energized
throughout this procedure.
1. To prepare the unit for evacuation, recover
any refrigerant to 0 psi (0 kPa). (New Federal
Regulations may require your recovery
machine to pull the system’s pressures lower
then 0 psi [0 kPa]).
2. Close the isolation valve at the thermistor to
isolate the vacuum gauge. Turn the vacuum
gauge on to warm it up.
3. Open the compressor service valves and the
receiver outlet valve.
4. Replace and tighten the valve stem caps on all
three service valves.
5. Open the vacuum valve at the vacuum pump
and start the pump.
6. After evacuating the system for 5 minutes,
open the isolation valve at the thermistor to
access the vacuum gauge.
7. Evacuate the system to 500 microns. Back
seat the suction service valve and then
continue to evacuate the system for one
additional hour.
NOTE: The presence of refrigerant in the
compressor oil may prevent a low micron
reading from being achieved. The oil can
continue to “outgas” for long periods of
time. If the micron level appears to stall after
1/2 hour or 45 minutes between 1000 and
1500 microns, back seat the suction service
valve and observe the micron gauge. A sharp
drop in the micron reading (300 to 500
microns) indicates that refrigerant is in the
oil or a leak exists in the compressor area.
8. After the hour of additional evacuation time,
open the suction service valve. The vacuum
gauge reading will rise. Continue to evacuate
the system back down to 500 microns. When
the system reaches 500 microns, back seat the
suction service valve, close the vacuum valve
at the vacuum pump, and stop the pump.
9. Observe the reading on the vacuum gauge for
5 minutes. The pressure should not exceed
2000 microns. If the pressure exceeds 2000
microns in 5 minutes, a leak is present, or
additional evacuation time is required.
10. If the vacuum level is acceptable, start the
pump and open the vacuum valve. Evacuate
the system for 5 minutes to remove the
pressure rise. Close the vacuum valve and stop
the pump. Observe the vacuum gauge to
confirm that the system remains in a deep
vacuum.
11. Close the isolation valve at the thermistor. The
unit is now ready to charge.
CAUTION: Do not attempt to evacuate a
unit until you are sure that the unit is leak
free. A unit with less than a full
refrigerant charge should be thoroughly
leak checked and all leaks must be
repaired.
Summary of Contents for 920000
Page 4: ......
Page 10: ...Table of Contents 10...
Page 22: ...Specifications 22...
Page 41: ...Unit Description 41 Unit Photographs Figure 12 Front View Figure 13 Top View ARD026 AGA267...
Page 42: ...Unit Description 42 Figure 14 Engine Side Door Open ARD041...
Page 76: ...Electrical Maintenance 76...
Page 132: ...Hilliard Clutch Maintenance 132...
Page 134: ...Structural Maintenance 134...
Page 146: ...Refrigeration Diagnosis 146...
Page 148: ...Remote Evaporator Specifications 148...
Page 150: ...Remote Evaporator Maintenance Inspection Schedule 150...
Page 154: ...Remote Evaporator Unit Description 154...
Page 158: ...Remote Evaporator Structural Maintenance 158...
Page 160: ...Remote Evaporator System Diagnosis 160...
Page 164: ...Wiring and Schematic Diagrams Index 164...
Page 165: ...165 MD RD MT Model 30 w In Cab Schematic Diagram Page 1 of 2...
Page 166: ...166 MD RD MT Model 30 w In Cab Schematic Diagram Page 2 of 2...
Page 167: ...167 MD RD MT Model 30 w In Cab Wiring Diagram Page 1 of 3...
Page 168: ...168 MD RD MT Model 30 w In Cab Wiring Diagram Page 2 of 3...
Page 169: ...169 MD RD MT Model 30 w In Cab Wiring Diagram Page 3 of 3...
Page 170: ...170 MD RD MT Model 30 w In Cab CYCLE SENTRY Schematic Diagram Page 1 of 2...
Page 171: ...171 MD RD MT Model 30 w In Cab CYCLE SENTRY Schematic Diagram Page 2 of 2...
Page 172: ...172 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 1 of 3...
Page 173: ...173 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 2 of 3...
Page 174: ...174 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 3 of 3...
Page 175: ...175 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 1 of 3...
Page 176: ...176 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 2 of 3...
Page 177: ...177 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 3 of 3...
Page 178: ...178 MD RD MT Model 50 w In Cab Schematic Diagram Page 1 of 2...
Page 179: ...179 MD RD MT Model 50 w In Cab Schematic Diagram Page 2 of 2...
Page 180: ...180 MD RD MT Model 50 w In Cab Wiring Diagram Page 1 of 3...
Page 181: ...181 MD RD MT Model 50 w In Cab Wiring Diagram Page 2 of 3...
Page 182: ...182 MD RD MT Model 50 w In Cab Wiring Diagram Page 3 of 3...
Page 183: ...183 MD RD MT Model 50 w In Cab CYCLE SENTRY Schematic Diagram Page 1 of 2...
Page 184: ...184 MD RD MT Model 50 w In Cab CYCLE SENTRY Schematic Diagram Page 2 of 2...
Page 185: ...185 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 1 of 3...
Page 186: ...186 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 2 of 3...
Page 187: ...187 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 3 of 3...
Page 188: ...188 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 1 of 3...
Page 189: ...189 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 2 of 3...
Page 190: ...190 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 3 of 3...