Change the AFAM Delay
NOTE: The fresh air exchange time delay should be established by the shipper.
The AFAM delay setting keeps the fresh air vent closed for a preset time when the unit starts. This allows
faster product temperature pull-down. The AFAM delay can be set from 1 to 72 hours in 1-hour
increments.
NOTE: During unit startup, the AFAM delay prevents the AFAM door from opening until the delay
times out. The AFAM delay prevents the AFAM door from opening due to the AFAM Rate or CO
2
system settings.
1. Press the
M
ENU
F4
key to enter the main menu.Press the
F2
or
F3
key to scroll to
Setpoint/Control
Menu and Press
F4
to expand the menu.
2. Press the
F2
or
F3
key to scroll to [AFAM DELAY] line.
3. Press the
F4
key to enter the AFAM DELAY menu. The current setting (“0”) appears in the display.
4. Press the
F2
OR
F3
key to increase or decrease the time delay.
5. Press and hold the
F4
key until you are returned to the main menu. The new time delay is recorded in
the controller and appears in the Display.
6. Press the
F1
key to exit the Setpoint screen.
Change the AFAM Rate
NOTE: The fresh air exchange rate should be established by the shipper.
The AFAM rate sets the desired air exchange rate. The actual door position is based on the AFAM rate
and the power supply frequency (Hertz).
1. Press the
M
ENU
F4
key to enter the main menu.Press the
F2
or
F3
key to scroll to
Setpoint/Control
Menu and Press
F4
to expand the menu.
1. Vent Door Assembly and Damper Motor
2.
Interface Board and Cable (Mounts in Control
Box)
Figure 96: AFAM+ System
WARNING: The vent door and motor actuator arm move immediately again when the a delay is
entered. Keep hands and tools away from the air exchange system components to prevent
personal injury or unit damage.
1
2
Summary of Contents for 098203
Page 2: ......
Page 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Page 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Page 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Page 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Page 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Page 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Page 263: ......