13
Specifications
Engine
Model
TK 486
Number of Cylinders
4
Cylinder Arrangement
In-line vertical, number 1 on flywheel end
Firing Order
1-3-4-2
Direction of Rotation
Counterclockwise viewed from flywheel end
Fuel Type
No. 2 diesel fuel under normal conditions
No. 1 diesel fuel is acceptable cold weather fuel
Oil Capacity: Crankcase
13 qt. (12.3 liters) crankcase
Fill to full mark on dipstick
Oil Type
API Classification CI-4 or better
(ACEA Rating E3 or better for Europe)
Oil Viscosity
5 to 122 F (-150 to 50 C): SAE 15W-40
-13 to 104 F (-25 to 50 C): SAE 10W-40
-13 to 86 F (-25 to 30 C): SAE 10W-30
-22 to 32 F (-30 to 0 C): SAE 5W-30
Engine rpm:
Low Speed Operation
1450 ± 25 rpm
High Speed Operation
2200 ± 25 rpm
Engine Oil Pressure
18 psi (127 kPa) minimum in low speed
45 to 57 psi (310 to 390 kPa) in high speed
Intake Valve Clearance
0.006 to 0.010 in. (0.15 to 0.25 mm)
Exhaust Valve Clearance
0.006 to 0.010 in. (0.15 to 0.25 mm)
Valve Setting Temperature
70 F (21 C)
Fuel Injection Timing
10 Degrees BTDC (timed on No. 1 cylinder)
Low Oil Pressure Switch (Normally Closed)
17 ± 3 psi (117 ± 21 kPa)
Engine Coolant Thermostat
180 F (82 C)
Coolant System Capacity
7.5 qt (7.1 liters)
Radiator Cap Pressure
7 psi (48 kPa)
Engine Coolant Type
ELC (Extended Life Coolant), which is “RED”. Use a 50/50
concentration of any of the following equivalents:
Chevron Dex-Cool
Texaco ELC
Havoline Dex-Cool®
Havoline XLC for Europe
Shell Dexcool®
Shell Rotella
Saturn/General Motors Dex-Cool®
Caterpillar ELC
Detroit Diesel POWERCOOL® Plus
CAUTION: Do not add “GREEN” or “BLUE-GREEN”
conventional coolant to cooling systems using “RED”
Extended Life Coolant, except in an emergency. If
conventional coolant is added to Extended Life Coolant,
the coolant must be changed after 2 years instead of
5 years.
Drive:
Model 30
Direct to compressor; belts to fans, alternator, and water
pump
Model 50
Centrifugal clutch to compressor; belts to electric standby
motor, fans, alternator, and water pump
Summary of Contents for 002008
Page 4: ...4 ...
Page 30: ...Unit Description 30 Figure 9 Front View AJA920 ...
Page 31: ...Unit Description 31 1 Access Panels 2 Defrost Damper Figure 10 Back View 1 2 ARA104 ...
Page 114: ...Mechanical Diagnosis 114 ...
Page 116: ...Electric Standby Diagnosis 116 ...
Page 120: ...Remote Evaporator Specifications 120 ...
Page 122: ...Remote Evaporator Maintenance Inspection Schedule 122 ...
Page 128: ...Remote Evaporator Electrical Maintenance 128 ...
Page 132: ...Remote Evaporator Refrigeration Service Operations 132 ...
Page 134: ...Remote Evaporator Structural Maintenance 134 ...
Page 136: ...Remote Evaporator System Diagnosis 136 ...
Page 140: ...Index 140 ...
Page 142: ......
Page 143: ...143 Model 30 Schematic Diagram Page 1 of 2 ...
Page 144: ...144 Model 30 Schematic Diagram Page 2 of 2 ...
Page 145: ...145 Model 30 Wiring Diagram Page 1 of 4 ...
Page 146: ...146 Model 30 Wiring Diagram Page 2 of 4 ...
Page 147: ...147 Model 30 Wiring Diagram Page 3 of 4 ...
Page 148: ...148 Model 30 Wiring Diagram Page 4 of 4 ...
Page 149: ...149 Model 50 Schematic Diagram Page 1 of 2 ...
Page 150: ...150 Model 50 Schematic Diagram Page 2 of 2 ...
Page 151: ...151 Model 50 Wiring Diagram Page 1 of 5 ...
Page 152: ...152 Model 50 Wiring Diagram Page 2 of 5 ...
Page 153: ...153 Model 50 Wiring Diagram Page 3 of 5 ...