20
ENGLISH
Priming the pump
To prime the oil pump simply start up the burner and check
for a flame.
If the burner enters lockout before any fuel reaches it, wait at
least 20 seconds then turn the function selector to "Reset
burner" for at least 1 second before returning it to its original
position. Wait for the burner to complete the entire ignition cy-
cle again, up to the ignition of the flame.
(*)
m
ax
. 4
m
H
H
(*) Automatic shut-off device (if fitted). For details of the
electrical connections, see the “Automatic shut-off de-
vice (DAI)” section on page 25.
H (m)
L (m)
Øi (8mm)
Øi (10mm)
0
35
100
0,5
30
100
1
25
100
1,5
20
90
2
15
70
3
8
30
3,5
6
20
H = Height difference
L = Maximum length of suction hose
Øi = Internal diameter of hose
1
Suction port
2
Return
3
By-pass screw
4
Pressure gauge fitting
5
Pressure adjuster screw
6
Vacuum gauge fitting
7
Valve
8
Auxiliary pressure measurement fitting
7
6 5
4
3
2
1
8