22
LUNA 2T | MACHINE FEA
TURES
5.1
Consumptions
M
axiMUM
valUes
s
izes
lUna 2T
6
8
10
12
14
16
Electrical
power supply V-Ph-Hz
230-50 230-50 230-51 230-52 230-53 230-54
Compressor
F.L.I. (kW)
1.70
2.80
3.72
3.90
4.79
5.23
F.L.A. (A)
8.10
13.38
17.77
18.63
22.89
24.99
L.R.A. (A)
19.20
19.20
19.20
32.00
32.00
32.00
Cosfi
0.91
0.91
0.91
0.91
0.91
0.91
Pdc system
pump
F.L.I. (kW)
0.06
0.06
0.06
0.06
0.09
0.09
F.L.A. (A)
0.58
0.58
0.58
0.58
0.71
0.71
Fan
F.L.I. (kW)
0.15
0.30
0.30
0.30
0.30
0.30
F.L.A. (A)
0.83
2.05
2.05
2.05
2.05
2.05
Total
F.L.I. (kW)
1.90
3.16
4.08
4.26
5.18
5.62
F.L.A. (A)
9.51
16.01
20.40
21.26
25.65
27.75
L.R.A. (A)
20.61
21.83
21.83
34.63
34.76
34.76
5.2
Performance under varying boundary conditions
The performance of the LUNA 2T units in Heating (winter operation) and Cooling (summer operation)
mode are shown below.
In the tables, the abbreviation
COP
(coefficient of performance) indicates the efficiency of the units
during heating and the abbreviation
EER
(energy efficiency ratio) represents the performance of the
air conditioners during cooling.