57
NOTICE
NOTICE
1. These are suggested piping configurations. It is the installer's responsibility to
conform to local codes and ordinances for additional requirements.
2. Pressure relief valve rating shall not exceed pressure rating of any component
in the system.
3. Some piping components cannot be supported by the pipping. Refer to the
manufactures' installation instructions.
4. Circulation pump must be sized to overcome the pressure drop across the entire
loop.
5. Erosion could occur if common piping is undersized.
!
Hot Water Return
Check Valve
Cold Water Supply
Expansion Tank
Hot Water Supply
Thermometer
Storage Tank
Isolation Valve
Factory Supplied Manifold
Y-Strainer
Heater Circulator
T&P Relief Valve
System
Circulator
Recirculation Filter
Mixing Valve
Thermal Solutions Products LLC
Notes:
1. This is a suggested piping configuration. It is the
installer's responsibility to to conform to local codes
and ordinances for additional requirements.
2. Relief valve shall not exceed the pressure
rating of any components in the system.
3. The circulator shall be sized to overcome the
pressure drop across the entire loop.
5/28/2019
Two AMP/BFIT Water Heaters with One Tank
Figure 26: Two Appliances, Single Tank
AMPW
Model
Number of Appliances
2
3
4
5
6
1000
5"
6"
8"
8"
10"
1250
5"
6"
8"
8"
10"
1500
6"
6"
8"
8"
10"
2000
6"
8"
10"
10"
10"
2500
8"
10"
10"
12"
12"
3000
8"
10"
10"
12"
12"
3500
10"
10"
12"
14"
14"
4000
10"
10"
12"
14"
14"
Note: Nominal pipe sizes are noted. Based on type L copper pipe
Table 30: Required Common Piping Sizes for Multiple Appliances
. Hot Water Supply Boiler Piping
(continued)
Summary of Contents for AMP 1000