23
. Venting
(continued)
At Maximum Input Rate
At Minimum Input Rate
AMP
Model
Vent
Dia. (In.)
Flue Gas Flow,
ACFM @ 35%
Excess Air, 180
0
F
Combustion Air,
SCFM @ 35%
Excess Air, 60
0
F
Flue Gas Flow,
ACFM @ 35%
Excess Air, 180
0
F
Combustion Air,
SCFM @ 35%
Excess Air, 60
0
F
1000
8
282
212
56
42
1250
352
265
70
53
1500
423
318
84
63
2000
564
424
113
85
2500
10
705
531
141
106
3000
846
637
169
127
3500
12
987
743
197
148
4000
1129
849
225
170
Notes:
Flow rates are based on the combustion of natural gas.
Table 10: Combustion Air and Flue Gas Flow Rates
Table 11: Approved Vent Manufacturers and Materials
Make
Material
Model
Heat Fab
Stainless Steel
Saf-T Vent EZ Seal*
Z-Flex (Nova Flex Group)
Stainless Steel/
Polypropylene
Z-Vent/Z-DENS
DuraVent
Polypropylene
PolyPro Single Wall Rigid
Centrotherm
Polypropylene
InnoFlue SW Rigid
*Factory supplied flue connection. Adapters are required to transition to alternate vent
materials or manufacturers.
Table 12: Stainless Steel and CPVC Vent Adapters
Stainless Steel to CPVC
Heat Fab to Z-Vent
Vent Diameter (in.)
Thermal Solutions Part #
Z-Flex Part #
8
109510-01
2SVSHF08
10
109510-02
2SVSHF10
12
109510-03
2SVSHF12