Thermal Care Aquatherm RQE Operation, Installation, And Maintenance Manual Download Page 7

condensation adds a substantial heat load to the 
cooling system.  
 
The importance of properly sized piping cannot be 
overemphasized. See the ASHRAE Handbook or 
other suitable design guide for proper pipe sizing. In 
general, run full size piping out to the process and 
then reduce the pipe size to match the connections 
on the process equipment. One of the most 
common causes of unsatisfactory unit performance 
is poor piping system design. Avoid long lengths of 
hoses, quick disconnect fittings, and manifolds 
wherever possible as they offer high resistance to 
water flow. When manifolds are required, install 
them as close to the use point as possible. Provide 
flow-balancing valves at each machine to assure 
adequate water distribution in the entire system. 
Install shut-off valves at each machine to allow for 
isolation of the unit. 
 

Installation - Electrical  

All wiring must comply with local codes and the 
National Electric Code. Minimum Circuit Amps (MCA) 
and other unit electrical data are on the unit 
nameplate. A unit specific electrical schematic ships 
with the unit. Measure each leg of the main power 
supply voltage at the main power source. Voltage 
must be within the voltage utilization range given on 
the drawings included with the unit. If the measured 
voltage on any leg is not within the specified range, 
notify the supplier and correct before operating the 
unit. Voltage imbalance must not exceed two 
percent. Excessive voltage imbalance between the 
phases of a three-phase system can cause motors to 
overheat and eventually fail. Voltage imbalance is 
determined using the following calculations: 
 
% Imbalance = (Vavg – Vx) x 100 / Vavg 
 
Vavg = (V1 + V2 + V3) / 3 
Vx = phase with greatest difference from Vavg 
 
For example, if the three measured voltages were 
442, 460, and 454 volts, the average would be: 
 
(442 + 460 + 454) / 3 = 452 
 
The percentage of imbalance is then: 
 
(452 – 442) x 100 / 452 = 2.2 % 

This exceeds the maximum allowable of 2%. 
 
There is a terminal block for main power connection 
to the main power source. The main power source 
should be connected to the terminal block through 
an appropriate disconnect switch. There is a separate 
lug in the main control panel for grounding the unit. 
Check the electrical phase sequence at installation 
and prior to start-up. Operation of the unit with 
incorrect electrical phase sequencing will result in 
improper pump performance. Check the phasing 
with a phase sequence meter prior to applying 
power. The proper sequence should read “ABC” on 
the meter. If the meter reads “CBA”, open the main 
power disconnect and switch two line leads on the 
line power terminal blocks (or the unit mounted 
disconnect). Do not interchange any load leads that 
are from the unit contactors or the motor terminals. 
 

 

WARNING: This equipment contains hazardous 
voltages that can cause severe injury or death. 

 

 

WARNING: This equipment contains hot water or 
coolant under pressure. Accidental release of hot water 
or coolant under pressure can cause personal injury 
and or property damage. 

 

 

WARNING: This equipment may contain fan blades or 
other sharp edges. Make sure all fan guards and other 
protective shields are securely in place. 

 

 

WARNING: The exposed surfaces of motors, piping, 
and other fluid circuit components can be very hot 
and can cause burns if touched with unprotected 
hands. 

 

 

CAUTION: Disconnect and lock out incoming power 
before installing, servicing, or maintaining the 
equipment. Connecting power to the main terminal 
block energizes the entire electric circuitry of the unit. 
Electric power at the main disconnect should be shut 
off before opening access panels for repair or 
maintenance. 

 

 

CAUTION: Wear eye protection when installing, 
maintaining, or repairing the equipment to protect 
against any sparks, debris, or fluid leaks. 

 

 

CAUTION: Wear protective gloves when installing, 
maintaining, or repairing the equipment to protect 
against any sparks, debris, or fluid leaks. 

 

 

CAUTION: Wire the unit ground in compliance with 
local and national codes. 

 

Summary of Contents for Aquatherm RQE

Page 1: ......

Page 2: ......

Page 3: ...Decrease Button 4 Changing Setpoint Temperature 4 Changing Temperature Units 4 Changing Temperature Displayed 4 Using Mold Purge Option 4 Changing User Parameters 5 USB Port 5 Table 1 User Parameters...

Page 4: ...Page Intentionally Blank...

Page 5: ...ng General Mandatory Action Wear Eye Protection Wear Protective Gloves Wear Ear Protection Disconnect Before Carrying Out Maintenance or Repair Connect an Earth Terminal to Ground Only qualified perso...

Page 6: ...ols or any other major component torn loose from its mounting point Record any signs of concealed damage and file a shipping damage claim immediately with the shipping company Most carriers require co...

Page 7: ...his exceeds the maximum allowable of 2 There is a terminal block for main power connection to the main power source The main power source should be connected to the terminal block through an appropria...

Page 8: ...er button to enter the new set point temperature Changing Temperature Units The temperature unit in use shows in the display as F or C following the set point temperature The default temperature unit...

Page 9: ...press the soft key button to save the new selection Press the exit soft key the button under the Exit box on the screen to return to the home screen USB Port The USB port located on the front of the c...

Page 10: ...ssist in deaeration No loop temperature regulation occurs in this state Increase this value if you have an excessively long fluid loop Vent Bypass 120 F 32 to 260 If the process loop is above this tem...

Page 11: ...whether or not mold purge is installed as an option Setpoint Max 250 F 40 to 250 Maximum permitted machine setpoint Setpoint Min 40 F 40 to 250 Minimum permitted machine setpoint Cool Heat Rto 1 25 0...

Page 12: ...y menu according to the installed TCU options Note The unit will not operate properly if the Factory Parameters are incorrectly changed or modified For that reason these parameters can only be changed...

Page 13: ...ning to OFF is considered an operation 9 18 Cooling Water Cooling Water Temperature The cooling water temperature as measured at the end of the valve vent during normal TCU startup Value is saved thro...

Page 14: ...ts remained open when the coil was energized 15 18 Low Pres Time Low Pressure Shutdown Alarms Number of times the running TCU has remained in a low pressure paused state for so long that it created an...

Page 15: ...ference between the process value and the setpoint The goal of the control loop is to reduce this to 0 during operation Start up Every unit is factory set to deliver water in accordance with the stand...

Page 16: ...help regulate the pressure to ensure it does not exceed the pressure rating of the pressure relief valve For further assistance in installing a pressure regulating valve please contact our Customer S...

Page 17: ...es or other possible ignition sources Step 3 Initial Unit Operation Enter the set point temperature Refer to the Control Panel Operation section for further information Changing the set point temperat...

Page 18: ...t there may be a problem with the unit If this is the case refer to the Troubleshooting section of this manual or contact our Customer Service Department 2 Check the pump discharge pressure Investigat...

Page 19: ...upply is of sufficient temperature volume and pressure for the unit Drain cooling water return line is not sufficient Check the drain cooling water return line to ensure there is no restriction preven...

Page 20: ...16 Notes...

Page 21: ...17 Notes...

Page 22: ...18 Notes...

Page 23: ......

Page 24: ...es Customer Service Parts Department 847 966 2260 info thermalcare com 847 966 2260 847 966 9358 fax 847 966 2636 847 966 8560 847 966 9358 fax www thermalcare com info thermalcare com service thermal...

Reviews: