Thermal Care Aquatherm RQE Operation, Installation, And Maintenance Manual Download Page 19

15 

Troubleshooting 

Problem 

Possible Cause 

Remedy 

Alternating 
overheating and 
overcooling or 
rapid cycling from 
heat to cool 

Poor water flow 

Check connectors and increase size if necessary. If there are 
a large number of hoses and/or they are long, try to shorten 
hose runs and use as large of a hose as possible to 
minimize water-circuit pressure drop. If quick disconnects 
with check valves are used, remove the check valves to 
reduce pressure drop through water circuit. 

Poor connection or failure of RTD 

Check connection, replace if necessary 

Failure of the microprocessor 

Replace controller 

Unable to heat 
properly 

Cooling valve is stuck in the open position 

Flush out the cooling valve by adjusting the Set Point up 
and down several times to open and close the cooling valve. 
If this does not work, stop the unit and turn off the electric 
power, shut off the cooling source, and take the valve apart 
for cleaning or replacement. 

Leaking connection and/or the manual pressure relief valve 
is in an open condition 

Check for leaks and replace any faulty valves 

Immersion heater is inoperative 

Have a qualified electrician check to see if the heater and/or 
heater contactor are functioning correctly and replace any 
defective components. 

Controller failure 

Replace controller 

Failure of RTD 

Replace RTD 

Unable to cool 
properly 

Cooling water supply is not sufficient 

Check to make sure the cooling water supply is of sufficient 
temperature, volume and pressure for the unit. 

Drain (cooling water return line) is not sufficient 

Check the drain (cooling water return line) to ensure there is 
no restriction preventing water flow to the drain (cooling 
water return line). 

Cooling valve is inoperative 

Check the drain (cooling water return line) and see if you 
can feel or hear a change in the flow as the cooling valve 
opens and closes. If you cannot hear or feel the flow it is 
likely the valve has failed. Replace valve if necessary. 

Plugged heat exchanger (only on models with heat 
exchanger option) 

Clean or replace heat exchanger 

High backpressure in the cooling water system 

Reduce backpressure  

Heater failure 

Unit not filled with water 

Fill unit with water 

Faulty heater 

Replace heater 

Plugged heater tube / flow restriction 

Clear obstruction 

Pressure relief 
valve leaks 

The combined pressure of the incoming cooling water 
pressure and the unit pump pressure exceeds the pressure 
rating of the pressure relief valve 

Install a pressure-reducing valve on the incoming cooling 
water line. Review the start-up procedure for cooling water 
pressure requirements at various operating temperatures. 

Pressure relief valve stuck in open position 

Replace valve 

 

Drawings 

We have prepared a custom set of drawings for your unit and placed them on top of the unit prior to shipment. 
Please refer to these drawings when troubleshooting, servicing, and installing the unit. If you cannot find these 
drawings or wish to have additional copies, please contact our Customer Service Department and reference the 
serial number of your unit. 
 
 

 

Summary of Contents for Aquatherm RQE

Page 1: ......

Page 2: ......

Page 3: ...Decrease Button 4 Changing Setpoint Temperature 4 Changing Temperature Units 4 Changing Temperature Displayed 4 Using Mold Purge Option 4 Changing User Parameters 5 USB Port 5 Table 1 User Parameters...

Page 4: ...Page Intentionally Blank...

Page 5: ...ng General Mandatory Action Wear Eye Protection Wear Protective Gloves Wear Ear Protection Disconnect Before Carrying Out Maintenance or Repair Connect an Earth Terminal to Ground Only qualified perso...

Page 6: ...ols or any other major component torn loose from its mounting point Record any signs of concealed damage and file a shipping damage claim immediately with the shipping company Most carriers require co...

Page 7: ...his exceeds the maximum allowable of 2 There is a terminal block for main power connection to the main power source The main power source should be connected to the terminal block through an appropria...

Page 8: ...er button to enter the new set point temperature Changing Temperature Units The temperature unit in use shows in the display as F or C following the set point temperature The default temperature unit...

Page 9: ...press the soft key button to save the new selection Press the exit soft key the button under the Exit box on the screen to return to the home screen USB Port The USB port located on the front of the c...

Page 10: ...ssist in deaeration No loop temperature regulation occurs in this state Increase this value if you have an excessively long fluid loop Vent Bypass 120 F 32 to 260 If the process loop is above this tem...

Page 11: ...whether or not mold purge is installed as an option Setpoint Max 250 F 40 to 250 Maximum permitted machine setpoint Setpoint Min 40 F 40 to 250 Minimum permitted machine setpoint Cool Heat Rto 1 25 0...

Page 12: ...y menu according to the installed TCU options Note The unit will not operate properly if the Factory Parameters are incorrectly changed or modified For that reason these parameters can only be changed...

Page 13: ...ning to OFF is considered an operation 9 18 Cooling Water Cooling Water Temperature The cooling water temperature as measured at the end of the valve vent during normal TCU startup Value is saved thro...

Page 14: ...ts remained open when the coil was energized 15 18 Low Pres Time Low Pressure Shutdown Alarms Number of times the running TCU has remained in a low pressure paused state for so long that it created an...

Page 15: ...ference between the process value and the setpoint The goal of the control loop is to reduce this to 0 during operation Start up Every unit is factory set to deliver water in accordance with the stand...

Page 16: ...help regulate the pressure to ensure it does not exceed the pressure rating of the pressure relief valve For further assistance in installing a pressure regulating valve please contact our Customer S...

Page 17: ...es or other possible ignition sources Step 3 Initial Unit Operation Enter the set point temperature Refer to the Control Panel Operation section for further information Changing the set point temperat...

Page 18: ...t there may be a problem with the unit If this is the case refer to the Troubleshooting section of this manual or contact our Customer Service Department 2 Check the pump discharge pressure Investigat...

Page 19: ...upply is of sufficient temperature volume and pressure for the unit Drain cooling water return line is not sufficient Check the drain cooling water return line to ensure there is no restriction preven...

Page 20: ...16 Notes...

Page 21: ...17 Notes...

Page 22: ...18 Notes...

Page 23: ......

Page 24: ...es Customer Service Parts Department 847 966 2260 info thermalcare com 847 966 2260 847 966 9358 fax 847 966 2636 847 966 8560 847 966 9358 fax www thermalcare com info thermalcare com service thermal...

Reviews: