![Thermal Care Aquatherm RQE Operation, Installation, And Maintenance Manual Download Page 12](http://html1.mh-extra.com/html/thermal-care/aquatherm-rqe/aquatherm-rqe_operation-installation-and-maintenance-manual_1103217012.webp)
8
Factory Parameters (continued)
Category
Screen
Number
Parameter
Default
Value
Range
Description
Additiona
l
Settings
2/2
Cooling Cycle
5.0 sec
0.5 to 60.0
Time base for solenoid cooling valve. If Cooling Cycle is set to 5.0s, and
the unit is cooling at 50% capacity, the solenoid cooling valve will
alternate between 2.5s on and 2.5s off.
Heating Cycle 10.0 sec
0.5 to 60.0
Time base for heater contactor. If Heating Cycle is set to 10.0s, and the
unit is heating at 50% capacity, the heater contactor will alternate between
5.0s on and 5.0s off.
Track Health
Yes
No
Yes
Provides machine run statistics and alarm counting for the diagnostics
menu. This can be disabled to decrease processor load or not track these
items.
Diagnostics
No
No
Yes
Select “Yes” to enter the Diagnostics menu. Note: Since you have already
authenticated as a factory user, you will have WRITE access to directly
control outputs for troubleshooting (except for heater output).
Load Defaults No
No
Yes
Select “Yes” if you would like to load defaults for all user AND factory
parameters. If you select “Yes” all your customized settings will be
permanently lost and default user and factory parameters will be used
instead. The controller will reboot after implementing default settings. As a
factory user, you will need to then go back and properly configure the
factory menu according to the installed TCU options.
Note: The unit will not operate properly if the Factory Parameters are incorrectly changed or modified. For that reason these parameters can only
be changed once the Factory Menu is activated in the User Parameter menu (see screen 6/6 under User Parameters). Only qualified technical
personnel familiar with the operation of the unit should change these parameters and then only at the direction of someone from the factory
Customer Service Department.
Table 3 - Diagnostic Screens
Category
Screen
Number
Parameter
Device
Description
Digital
Inputs
1/18
Pres Swtch
Pressure Switch (input U1) Pressure switch input shows "ON" when sufficient pressure.
Pump OL
Pump Overload (input U2) Pump overload input shows "ON" when not tripped.
Pump Aux
Pump Contactor Axillary
Contact (input U3)
Pump contactor auxiliary contact shows "ON" when the pump contactor
is energized and seated.
2/18
Hi Temp
High Temperature Input
Jumper (input U4)
High temperature input shows "ON" when no high temperature
condition exists.
Heater Aux Heater Contactors Auxiliary
Contact (input U5)
Heater contactor auxiliary contactor shows "ON" when heater contactor
is energized and seated.
Spare
Spare (input U5)
Input not used.
Analog
Inputs
3/18
Supply RTD Supply RTD (input U7)
Supply "To Proc" RTD Temperature Probe, units always in °C.
Return RTD Return RTD (input U8)
Return "From Proc" RTD Temperature Probe, units always in °C.
Spare RTD
Spare RTD (input U9)
Spare RTD Temperature Probe, units always in °C.
Spare
Spare (input U10)
Input not used.
Summary of Contents for Aquatherm RQE
Page 1: ......
Page 2: ......
Page 4: ...Page Intentionally Blank...
Page 20: ...16 Notes...
Page 21: ...17 Notes...
Page 22: ...18 Notes...
Page 23: ......