Thermal Care Aquatherm RQE Operation, Installation, And Maintenance Manual Download Page 11

Table 1 - User Parameters (continued) 

Category  Screen 

Number 

Parameter 

Default 

Value 

Range 

Description 

Additiona
l Settings 

6/6 

Deviation 
Actn 

Warn 

None 
Warn 
Alarm 

Allows the user to select how the TCU responds to a deviation condition (as 
defined in screen 1/6 above). Warnings are visible on the screen, but have no 
effect on machine operation. Alarms shutdown the machine and require user 
intervention to reset. 

Mold Purge 
T/O 

60 sec 

1 to 999  After mold purge is started, this is the max time that it can run before being 

automatically cancelled. Note that the user can stop mold purge at any time.* 
 
*Only visible on menu if mold purge option is installed. 

Diagnostics  No 

No or Yes  Select "Yes" if you would like to enter the diagnostics menu. 

Load 
Defaults 

No 

No or Yes  Select “Yes” if you would like to load defaults for all user parameters. If you select 

“Yes”, all your customized settings will be permanently lost and default 
parameters will be used instead. The controller will reboot after implementing 
default settings. 

Factory 
Menu 

--- 

--- 

Used to enter a password for a factory configuration menu. 

 

Table 2 - Factory Parameters 

Category 

Screen 

Number 

Parameter 

Default 

Value 

Range 

Description 

Included 
Options 

1/2 

MP Installed 

No 

No or Yes 

Allows the factory to set whether or not mold purge is installed as an 
option. 

Setpoint Max 

250°F 

40 to 250 

Maximum permitted machine setpoint. 

Setpoint Min 

40°F 

40 to 250 

Minimum permitted machine setpoint. 

Cool-Heat Rto  1.25 

0.1 to 10.0 

Describes the effectiveness of cooling vs effectiveness of heating. Having 
the correct value here enhances the performance for the PID algorithm. 
For example, if the TCU’s cooling BTU removal happens at twice the rate of 
the TCU’s heating BTU addition, this number should be set to 2.0. Systems 
with small heaters and plentiful, cold cooling water may want a value of 
1.5. Alternatively, warm cooling water or a very powerful heater would 
work best with a value of 0.75. A value of 1.0 means there is no distinction 
between heating/ cooling and the PID works in a very traditional manner. 
Conduct any experimentation to set this value at lower process 
temperatures. 

Dynamic Mult:  1.75 

0.0 to 10.0 

This parameter helps the TCU achieve setpoint quickly and without 
overshoot across the entire temperature range of operation. This factor 
multiples the “Cool-Heat Rto” set in the parameter above at high 
temperatures. For example, if “Dynamic Mult” is set to 1.75, a Cool-Heat 
Rto of 1.25 will actually become 2.19 (1.25 x 1.75 = 2.19) when the TCU is 
running at a process temperature of 250

°

F. Set to zero to disable all 

dynamic effects, in which case parameter “Cool-Heat Rto” will be solely 
responsible and at a fixed value across the entire temperature range. 

 
 

 

Summary of Contents for Aquatherm RQE

Page 1: ......

Page 2: ......

Page 3: ...Decrease Button 4 Changing Setpoint Temperature 4 Changing Temperature Units 4 Changing Temperature Displayed 4 Using Mold Purge Option 4 Changing User Parameters 5 USB Port 5 Table 1 User Parameters...

Page 4: ...Page Intentionally Blank...

Page 5: ...ng General Mandatory Action Wear Eye Protection Wear Protective Gloves Wear Ear Protection Disconnect Before Carrying Out Maintenance or Repair Connect an Earth Terminal to Ground Only qualified perso...

Page 6: ...ols or any other major component torn loose from its mounting point Record any signs of concealed damage and file a shipping damage claim immediately with the shipping company Most carriers require co...

Page 7: ...his exceeds the maximum allowable of 2 There is a terminal block for main power connection to the main power source The main power source should be connected to the terminal block through an appropria...

Page 8: ...er button to enter the new set point temperature Changing Temperature Units The temperature unit in use shows in the display as F or C following the set point temperature The default temperature unit...

Page 9: ...press the soft key button to save the new selection Press the exit soft key the button under the Exit box on the screen to return to the home screen USB Port The USB port located on the front of the c...

Page 10: ...ssist in deaeration No loop temperature regulation occurs in this state Increase this value if you have an excessively long fluid loop Vent Bypass 120 F 32 to 260 If the process loop is above this tem...

Page 11: ...whether or not mold purge is installed as an option Setpoint Max 250 F 40 to 250 Maximum permitted machine setpoint Setpoint Min 40 F 40 to 250 Minimum permitted machine setpoint Cool Heat Rto 1 25 0...

Page 12: ...y menu according to the installed TCU options Note The unit will not operate properly if the Factory Parameters are incorrectly changed or modified For that reason these parameters can only be changed...

Page 13: ...ning to OFF is considered an operation 9 18 Cooling Water Cooling Water Temperature The cooling water temperature as measured at the end of the valve vent during normal TCU startup Value is saved thro...

Page 14: ...ts remained open when the coil was energized 15 18 Low Pres Time Low Pressure Shutdown Alarms Number of times the running TCU has remained in a low pressure paused state for so long that it created an...

Page 15: ...ference between the process value and the setpoint The goal of the control loop is to reduce this to 0 during operation Start up Every unit is factory set to deliver water in accordance with the stand...

Page 16: ...help regulate the pressure to ensure it does not exceed the pressure rating of the pressure relief valve For further assistance in installing a pressure regulating valve please contact our Customer S...

Page 17: ...es or other possible ignition sources Step 3 Initial Unit Operation Enter the set point temperature Refer to the Control Panel Operation section for further information Changing the set point temperat...

Page 18: ...t there may be a problem with the unit If this is the case refer to the Troubleshooting section of this manual or contact our Customer Service Department 2 Check the pump discharge pressure Investigat...

Page 19: ...upply is of sufficient temperature volume and pressure for the unit Drain cooling water return line is not sufficient Check the drain cooling water return line to ensure there is no restriction preven...

Page 20: ...16 Notes...

Page 21: ...17 Notes...

Page 22: ...18 Notes...

Page 23: ......

Page 24: ...es Customer Service Parts Department 847 966 2260 info thermalcare com 847 966 2260 847 966 9358 fax 847 966 2636 847 966 8560 847 966 9358 fax www thermalcare com info thermalcare com service thermal...

Reviews: