THERMAflow Ltd | THERMAFLOW® ELECTRIC COMBINATION BOILER | 

Tel: 0870 850 5207 

 

 

32 

 
One is fitted above the central heating pump and one further up on the boiler. This second stage over 
temperature thermostat is pre-set to 

90ºC.

  

It should not be tampered with.

 

 
If a failure on one of the thermostats has occurred you can re-set the thermostat by pressing the small 
reset button on the thermostat.  
If the thermostat continues to fail in an overheat condition a fault may have occurred in one or more of 
the control thermostats within the heating elements.  
Take note of which one it is and contact Thermaflow Ltd for spares and advice.   

 

The second is also a manual re-set over temperature thermostat and is fitted on the boiler.  
 
This is the 3rd stage manual re-set master over temperature thermostat. It will break the circuit to the 
contactor on over temperature. 
It is preset to 

95ºC

 and sealed and 

should not be tampered with.

   

 

This will indicate a fault has occurred on one or more of the control thermostats within the 
heating elements and will have to be investigated.  
If it continues to fail in an over-heat condition the fault must be rectified before the appliance is 
turned back on for use.  

If a failure has occurred, contact Thermaflow Ltd for spares and advice. 
 

3.2.12 Checking the heating elements 

 

Check the resistance between live and neutral terminals on the element.  
 
Replace the element if the resistance is greater than 10 m ohms.  

 

3.2.13 Checking circuit breakers 

 

Switch each circuit breaker off in turn and check that continuity is broken to each element. 

 

3.2.14 Checking the contactor 

 

Turn the main isolator off (this should be situated adjacent to the boiler) you should hear a small click 
from the control box marked number 

16 

on the boiler schematic on 

page 9

 of this instruction manual.

 

 

This indicates that the contactor has disconnected the circuit to the heating elements.  
Turn the main isolator on and off a few times and listen for this noise. This will indicate correct operation 
of the contactor.   

 

 

3.2.15 Check the operation of the AQUA STAT  

 
The Aqua Stat is positioned on the cold water inlet entering the boiler. 

Make sure

 

the

 

external controls 

are calling for heat.

 Remove the cover and turn the dial on the thermostat up and down and listen for a 

small click. 
As you turn the thermostat dial up and down check if the central heating pump, (

positioned on the right 

side of the unit

) is switching 

on

 and 

off 

and do the same with the DHW pump on the left hand side

.

 

If 

this is the case, this indicates correct operation of the thermostat. 
 

Summary of Contents for TH6-210U M3

Page 1: ...rst year guarantee and a second year parts guarantee In the instruction envelope is to be found your guarantee registration card which must be completed and returned to Thermaflow Ltd or register your...

Page 2: ...It is TMV3 rated for Anti Scald purposes The combination boiler is able to provide room heating as part of an under floor or central heating system and domestic hot water direct from the cold water s...

Page 3: ...the occupants and shall be positioned away from any electrical devices The position of discharge pipes Tundish drain valves and motorised valves etc must be positioned away from electrical components...

Page 4: ...y 12 2 1 6 Heating system controls 12 2 2 1 Boiler Position 12 2 2 2 Boilers in a compartment 13 2 2 3 Clearances allow for external primary heat transfer kit 14 2 3 1 General notes 14 2 3 2 Safety va...

Page 5: ...3 2 6 Preventing pump seizure in summer 31 3 2 7Checking correct operation of electrical components 31 3 2 8 Low pressure switch 31 3 2 9 Control and high limit manual re set thermostats 31 3 2 12 Ch...

Page 6: ...210 23L for the 250 and 28L for the 330 model The secondary expansion vessel pre charge pressure is between 200 350 KPA 2 3 5 bar and has a volume of 0 5 litres The primary pressure relief valve is s...

Page 7: ...y or wet surfaces IMPORTANT INFORMATION 0 4 TESTING CERTIFICATION The boiler is tested and certified for safety and performance It is therefore important that no alteration is made to the boiler witho...

Page 8: ...lling the Thermaflow They are as follows 1 Flow and return connections to the heating system are 22mm compression 2 Cold water inlet 22mm compression 3 Hot water outlet 22mm compression 4 Pressure rel...

Page 9: ...THERMAflow Ltd THERMAFLOW ELECTRIC COMBINATION BOILER Tel 0870 850 5207 9 1 c 1a 11 2 3 4a 4b 1b 17a a 13a 18 19 14 13b 16 17b 20 10 10a 10b 8 7 6 21 12 5 15 9 Unit Design Protected by Design Rights...

Page 10: ...ater Content Primary 200 Water Content Domestic Secondary 2 Litres 0 44 Gallons Primary Expansion INTERNAL 22 Litres 4 9 Gallons 28 Litres 6 3 Gallons Secondary Expansion Vessel 0 5 Litres 0 11 Gallon...

Page 11: ...utory requirements 2 1 3 DATA The data label is on the front case of the boiler 2 1 4 ELECTRICAL SUPPLY Power supply and wiring The power supply to the premises must meet the minimum requirements of t...

Page 12: ...essible and installed at the origin of the supply to the boiler It should be identified as to its use Means of disconnection should be readily accessible and adjacent to the appliance It should be ide...

Page 13: ...al requirements for cupboards or compartment design are given in the current issue of BS6798 The doorway opening should be of sufficient size to allow for easy removal of the boiler Where the boiler i...

Page 14: ...in table 1 Data an additional expansion vessel should be connected into the system as close as possible to the central heating return connection of the boiler Ref Diagram 2 3 5 The charge pressure sh...

Page 15: ...termined by the volume and pressure of the incoming cold water supply and the primary store temperature 2 4 4 Hard water areas In areas where the water is Hard more than 200 mg litre it is recommended...

Page 16: ...nvironment The connection for the discharge is made at the bottom side of the safety relief valve This must be extended from the safety relief valve with not less than 15mm O D metal pipe to discharge...

Page 17: ...eating then a separate 3 amp supply is not required for the controls as the controls are supplied via the 6 amp MCB in the control box marked No 16 on the boiler schematic on page 9 of this instructio...

Page 18: ...be taken to supply controls as shown NO NEUTRAL OR EARTHS SHOWN FOR CLARITY Requires 240v 3AMP Supply when using Scottish Power Domestic Economy 2000 tariff LINK REMOVED if E2000 Tariff LOW PRESSURE...

Page 19: ...tactor 1 on the Thermaflow boiler Connections onto main wiring terminal on boiler The Off Peak Control allows you to time the boiler to charge during the reduced rate periods on wet electric central h...

Page 20: ...f peak control when using a wet electric tariff other than Domestic Economy 2000 to enable a reduction in running costs IMPORTANT If the boiler is connected to Scottish Power Domestic Economy 2000 tar...

Page 21: ...iagram 5 Standard colours are Brown Live Blue Neutral and the earth should be sleeved with a suitably sized green and yellow earth sleeve Make the earth cable of a greater length so that if the cable...

Page 22: ...AKE SURE THE BOILER AND SYSTEM IS COMPLETELY FULL OF WATER AND ALL AIR IS ELIMINATED BEFORE TURNING ON ANY OF THE POWER SUPPLIES TO THE BOILER Take care not to splash any of the electrical components...

Page 23: ...omatic air eliminator There should be no further need to re pressurise the system after this period If the system requires continuous re pressurisation there may be a leak in the installation 2 7 6 Co...

Page 24: ...CONTINUITY POLARITY SHORT CIRCUIT AND RESISTANCE TO EARTH CHECKS MUST BE REPEATED USING A SUITABLE MULTI METER Type of fault Check No domestic hot water or central heating 230 240V Supply 24HR 230 240...

Page 25: ...1 2 Bar No Yes Increase Pressure Is there continuity through 1st stage and 2nd stage master high limit manual re set safety thermostats No Yes Re set or replace thermostat Is there continuity through...

Page 26: ...alling for heat No Adjust the setting Is temperature above setting on aqua stat Should be set to 30o C No Re check when temperature increases Check thermostat and lock shield Valves on radiators are o...

Page 27: ...of 30 C Is domestic pump operating correctly Are the pump valves in the open position No Yes Open the pump valves If they are open replace the pump Is there circulation through the primary side of th...

Page 28: ...5207 28 Fault Diagnosis E10 or single rate supply R3 LP R1 POWER HL1 HL2 R2 NO POWER LOW WATER PRESSURE HIGH LIMIT 1 TRIPPED E10 HIGH LIMIT 2 TRIPPED E10 OFF PEAK CONTROL IS OFF OR BOILER HAS REACHED...

Page 29: ...ATION BOILER Tel 0870 850 5207 29 Fault Diagnosis E2000 Scottish Power region of Scotland ONLY R3 LP R1 POWER HL1 HL2 R2 NO POWER INTERUPTED SUPPLY E2000 LOW WATER PRESSURE HIGH LIMIT 1 TRIPPED HIGH L...

Page 30: ...oiler and open a hot tap Water will run for a few seconds then stop Connect a pressure gauge to the car tyre type valve on the vessel The pressure should register 200 350 KPA 2 0 3 5 Bar Close the hot...

Page 31: ...ct operation of the low pressure switch drain some water from the central heating system until the pressure falls below 0 5 bar then check continuity between terminals 1 and 2 there should be no conti...

Page 32: ...ack on for use If a failure has occurred contact Thermaflow Ltd for spares and advice 3 2 12 Checking the heating elements Check the resistance between live and neutral terminals on the element Replac...

Reviews: