EX-TRAFIRE
®
40SD
Operator Manual, Revision T-15
3-19
Mains power lead
EX-TRAFIRE
®
40SD is supplied with a 3 meter length of 3 core 2�5 mm
2
flexo cable without plug�
Use of an alternative mains power lead is at the discretion of the user� The mains power lead shall
comply with local and national codes of practice� The mains power lead should be installed by a
certified electrician� See the length requirements listed below�
Recommended mains power lead extension
Input voltage
Recommended wire cross-section
Length
100 - 130 VAC (CE) / 1 phase
4 mm2
Up to 15 m
220 - 240 VAC (CE/C-TICK) / 1 phase
2�5 mm2
Up to 40 m
Note:
The system was tested with a 3 meter mains power lead for compliance with EMC standards�
Single-phase mains power lead
CE models are fitted with a 3 wire 2�5 mm
2
mains power lead� To operate the EX-TRAFIRE
®
40SD,
use a plug that complies with national and local codes of practice� A certified electrician or
electrotechnically competent person should connect the mains power lead to the plug�
Installation of single-phase mains power lead
Green-Yellow
Black (Brown)
Blue
UNIT CE
L
Black (Brown)
N
Blue
Earth
Green-Yellow
Strip and prepare the mains power lead as show below:
Summary of Contents for EX-TRAFIRE 40SD
Page 10: ...EX TRAFIRE 40SD Operator Manual Revision T 15 10 Blank page...
Page 65: ...EX TRAFIRE 40SD Operator Manual Revision T 15 12 65 Notes...
Page 66: ...EX TRAFIRE 40SD Operator Manual Revision T 15 12 66 Notes...
Page 67: ...EX TRAFIRE 40SD Operator Manual Revision T 15 12 67 Notes...
Page 68: ...EX TRAFIRE 40SD Operator Manual Revision T 15 12 68 Notes...
Page 70: ...EX TRAFIRE 40SD Operator Manual Revision T 15 12 70 Revision history...