- Deactivating the brightness measurement (the bright-

ness has no influence)

- Channel A lighting always switches with presence/

absence.

"SendoPro 868-A" Management remote control, "the-

Senda P" installation remote control

Measurement 

off
Button

Time delay channel A light

Value range

Adjustable values with "SendoPro 868-A" manage-

ment remote control

In the "theSenda P" installation remote control, the 

following values are available

10 s - 60 min

10 s, 30 s, 60 s, 2 

min, 10 min, 20 min, 

60 min

Control for staircase light timer switch 

(0.5 s "on" / 10 s "off")

"SendoPro 868-A"

"theSenda P"

Pulse
Button 

1

Time delay channel H Presence

The presence channel switches on the basis of the presence 

(without brightness as a factor). The relay contact opens once 

the room is vacated after the set time delay expires.

Value range

Adjustable values "SendoPro 868-A"

10 s ... 120 min.

Adjustable values "theSenda P"

10 s, 30 s, 60 s, 2 

min, 10 min, 20 min, 

120 min

Detection sensitivity

The detector has 5 sensitivity increments. The basic setting is 

the middle level (3). 

By selecting the operation mode test presence, the set sensi-

tivity increment is not changed. 

With the „SendoPro 868-A“ management remote control, 

levels 1 to 5 can be selected and sent to the detector.

With the „theSenda P“ installation remote control, the sen-

sitivity can be reduced or increased by one level with every 

button press.

Level

Sensitivity

1

very insensitive

2

insensitive

3

Standard

4

sensitive

5

very sensitive

Group address channel A light

This parameter is applied when using the „theSenda P“ user 

remote control.

A group address can be assigned to the channel A light.

The „SendoPro 868-A“ or „theSenda S“ can be used to pro-

gram the group addresses in the detector.

Group address value range

Adjustable values "SendoPro 868-A"

I, II , III , All

Adjustable values "theSenda S"

I, II

LED display motion

The motion detection can be displayed via the LED.

Value range

No display of motion detection.

Off

The LED switches on when motion is detected, otherwise swit-

ches off.

On

Adjustment possible only with „SendoPro 868-A“.

Factory settings

The theMova P360-101 motion detector is supplied with the 

following parameter values:

Parameter

Value

Brightness switching value Channel A light

300 lux

Lighting time delay

10 min

Presence time delay

10 min

Detection sensitivity (PIR)

Stage 3

Group address channel A light

T

LED display motion

Off

9.  Start-up

Switching behaviour

Every time the power supply is switched on, the motion 

detector first runs through a start-up phase of 30 s, and then 

switches to normal operation. A LED displays the current 

status:

1. Start-up phase (30 seconds)

 

The red LED flashes every second, both switch contacts 
are closed (light and presence on).

 

The detector does not react to remote control commands.

 

When no one is present both contacts open after 30 
seconds.

2. Operation
The detector is ready for operation (LED off).

Test detection area

The test mode detection area is used to test presence detec-

tion and wiring. Presence test mode can be activated with the 

„SendoPro 868-A“ management remote control and with the 