High-performance switch actuators  

RM 4 H FIX1  

RM 8 H FIX2

 

 
 
 

 

4940212 

 

 

 

4940217 

 
 
 

 

 

Summary of Contents for RM 4 H FIX1

Page 1: ...2018 07 30 KNX manual High performance switch actuators RM 4 H FIX1 RM 8 H FIX2 4940212 4940217 ...

Page 2: ...tabase 7 4 2 Overview of communication objects 8 4 3 Description of communication objects 10 4 4 Parameter pages overview 15 4 5 General parameters 16 5 Typical applications 34 5 1 2x switching with push button interface 34 5 2 Temperature controlled domestic water heating 36 6 Appendix 38 6 1 The scenes 38 6 2 Conversion of percentages to hexadecimal and decimal values 41 ...

Page 3: ...dicator for each channel Manual operation on device Adjustable features e g switching delayed switching pulse function Links type of contact NC contact NO contact and participation in central commands such as permanent On permanent Off Central switching and save call up scene Switch functions e g On Off pulse On Off delay staircase light with forewarning Logical links e g block AND release OR Acti...

Page 4: ...buttons on the device A status LED displays the current switching status All bus telegrams are ignored with manual operation switched on manual button and the channels are to be operated exclusively via the buttons Once the bus voltage has been connected or after a bus reset it might take a few seconds until the relays switch ...

Page 5: ...tput min 0 17 W 0 26 W Type of contact μ contact floating NO contact contact gap 3 mm NO contact the switching of any phase is permitted Switching capacity 25 A at 240 V AC cos ϕ 1 16 A at 250 V AC cos ϕ 0 6 Minimum load 12 V 100 mA Switching SELV Possible if all channels of a module connect protective low voltage SELV Protection rating IP 20 Protection class II subject to designated installation ...

Page 6: ...lel compensated 2500 W 200 μF2 Fluorescent lamps EVB 1650 W Compact fluorescent lamps EVG 410 W LED lamps 2 W 75 W LED lamps 2 W 8 W 850 W Pollution degree 2 Rated impulse voltage 4 kV Shortest switching interval if all channels are switched at the same time 3 s 1 With 30 000 switching cycles 2 With 30 000 switching cycles ...

Page 7: ...n the product database Manufacturer Theben AG Product family Output Product type RM 4 H RM 8 H Programme name FIX2 RM 8 H The ETS database can be found on our website www theben de en downloads_en Number of communication objects 83 Number of group addresses 254 Number of associations 255 ...

Page 8: ...2 Logic input in AND gate 1 bit R W C 1 002 Logic input in XOR gate 1 bit R W C 1 002 2 Channel C1 Block 1 bit R W C 1 001 3 Channel C1 Call up save scenes 1 byte R W C T 18 001 4 Channel C1 Block scenes 1 1 bit R W C 1 001 Enable scenes 1 1 bit R W C 1 003 5 Channel C1 Feedback On Off 1 bit R C T 1 001 6 Channel C1 Operating hours feedback 4 bytes R W C T 13 100 Time to next service 4 bytes R W C...

Page 9: ... W C T 1 001 159 C5 C8 Collective feedback 4 bytes R C T 27 001 240 Central permanent ON 1 bit R W C T 1 001 241 Central permanent OFF 1 bit R W C T 1 001 242 Central switching ON OFF 1 bit R W C T 1 001 243 Central scenes Call up save 1 byte R W C T 18 001 250 Version of bus coupling unit Send 14 bytes R C T 16 001 251 Version C1 C4 Send 14 bytes R C T 16 001 252 Version C5 C8 Send 14 bytes R C T...

Page 10: ...IS5 e g CO2 brightness DPT 9 xxx 2 byte floating point number Object 1 Logic input in AND gate in OR gate in XOR gate Only available if link is activated Configuration options parameter page Forms a logical link together with the input object to activate the channel function Object 2 Block Blocks the channel function Responses to setting and cancelling the block can be configured if the block func...

Page 11: ... status of the hour counter Object 7 Service required Only available if the hour counter function has been activated Configuration options parameter page and Type of hour counter Counter for time to next service Reports if the next service is due 0 not due 1 service is due Object 8 Switching with priority reset service reset operating hours The function of the object depends on whether or not the ...

Page 12: ...unction Enables simultaneous switching on of all channels with one single telegram 0 no function 1 permanent ON Participation in this object can be set individually for each channel Configuration options parameter page This object takes top priority As long as it is set the other switch commands will not work on the participating channels Object 241 Central permanent OFF Central switch off functio...

Page 13: ...command Object 243 Call up save central scenes Central object for using scenes This object can be used to save and subsequently call up scenes See appendix Scenes Object 250 Version of bus coupling unit For diagnostic purposes only Sends the bus coupling unit software version after reset or download Can also be read out directly via the ETS Format Axx Hyy Vzzz Code Meaning xx 00 FF Version of appl...

Page 14: ... zzz Firmware version 000 999 EXAMPLE M19 H01 V001 Module 19 RM 4 H RM 8 H Hardware version V01 Firmware version V01 Object 252 Version C5 C8 For diagnostic purposes only Sends the software version firmware of the channel block C5 C8 after reset or download Can also be read out directly via the ETS The version is issued as an ASCII character string Format Mxx Hyy Vzzz Code Meaning xx 19 Module cod...

Page 15: ...ns scenes links etc Contact characteristics Type of contact and status after download bus failure etc Threshold Settings for triggering channel function through exceeding threshold Block function Type of block telegram and response to blocking Scenes Selection of scene numbers relevant to the channel Feedback Status of feedback object etc Hour counter and service Type of hour counter and if requir...

Page 16: ...o Object_78 Manual operation of the channels enabled The channels can be operated via the buttons on the device blocked No manual operation the buttons on the device are blocked Sending collective feedback no No collective feedback object is unavailable report as inactive Object value can be requested only at change Sends whenever a channel status changes cyclically and at change Sends cyclically ...

Page 17: ...ms When a relay switches on the next one can only switch on after the set delay is completed The switch on delay between the first and last relay is calculated according to the following formula Number of channels 1 x delay Example RM 4 H and 60 ms 4 channels 1 60 ms 180 ms Channel C4 switches 180 ms after C1 ...

Page 18: ...ity of the channel Activation of function via Switch object The channel is operated via a 1 bit object Exceeding the threshold The channel is operated through exceeding a 1 or 2 byte threshold See below the Threshold parameter page Adjust block function Yes The block function can be individually adjusted The relevant parameter page is shown no The block function works with the standard parameters ...

Page 19: ...t OFF Which central objects are to be taken into account Central objects enable simultaneous switching on and off of several channels with one single object Adjust feedback Yes The feedback function can be individually adjusted The relevant parameter page is shown no The Feedback function works with the standard parameters not inverted do not transmit cyclically Activate hour counter Yes no Is the...

Page 20: ...ailure OFF the relay switches off ON the relay switches on unchanged the relay remains in the same state as before If several switching operations were executed immediately before the bus failure the energy may not be sufficient for an additional switching operation In this case the relay remains in its previous state regardless of the parameter setting Status with restoration of the bus supply Af...

Page 21: ...tion Switch on delay Hours 0 3 Input of desired switch on delay in hours Minutes 0 60 Input of desired switch on delay in minutes Seconds 0 255 Input of desired switch on delay in seconds Switch off delay Hours 0 3 Input of desired switch off delay in hours Minutes 0 60 Input of desired switch off delay in minutes Seconds 0 255 Input of desired switch off delay in seconds ...

Page 22: ...ion in hours Minutes 0 60 Input of desired pulse duration in minutes Seconds 0 255 Input of desired pulse duration in seconds Pulse can be retriggered with 1 on switch object Yes The pulse can be extended as often as desired via a 1 telegram no The pulse cannot be extended Pulse can be reset with 1 on switch object Yes The pulse can be ended early at anytime via a 0 telegram no The pulse cannot be...

Page 23: ...ten the staircase light time can be extended restarted by pressing the button again Duration of 1st forewarning in s 0 The light switches off immediately once the staircase light time is completed 1 60 Default value 10 Once the staircase light time is completed the light should briefly flash and then stay on for the duration of the forewarning Duration of 2nd forewarning in s 0 No 2nd forewarning ...

Page 24: ...red pulse time in minutes Seconds 0 255 Input of desired pulse time in seconds OFF phase of flash pulse Hours 0 3 Input of desired length of break in hours Minutes 0 60 Input of desired length of break in minutes Seconds 0 255 Input of desired length of break in seconds How often should it flash Until it switches off The channel flashes until a switch off telegram is received 1 x 2 x 3 x 4 x 5 x 7...

Page 25: ...the relay switches on if threshold is exceeded NC contact the relay switches off if threshold is exceeded Parameter for Per cent threshold object Threshold 1 99 Default value 50 Desired threshold Example of NO contact with response as switch object 1 Switches on when Object value threshold Switches off when Object value threshold hysteresis Hysteresis as 1 99 Default value 10 The hysteresis preven...

Page 26: ...ue 5 The hysteresis prevents frequent switching after small fluctuations in readings Parameter for Floating point value DPT 9 e g temperature CO2 threshold object Threshold 671088 64 670760 96 Default value 20 Desired threshold Example of NO contact with response as switch object 1 Switches on when Object value threshold Switches off when Object value threshold hysteresis Hysteresis 0 01 670760 96...

Page 27: ... Block telegram Block with ON telegram 0 cancel block 1 block Block with OFF telegram 0 block 1 cancel block Note The block is always deactivated after reset Response when setting the block OFF Switch off ON Switch on unchanged No response Response when cancelling the block OFF Switch off ON Switch on unchanged No response update Restore normal operation and switch relay accordingly ...

Page 28: ... See appendix Teach in scenes without telegrams Unchanged after download All previously taught in scenes are saved However the scene numbers to which the channel should react can be changed see below Channel reacts to Participation in central scene object No yes Should the device react to the central scene object Channel reacts to No scene number Scene number 1 Scene number 63 First of the 8 possi...

Page 29: ...cene number Scene number 1 Scene number 4 Scene number 63 Fourth of the 8 possible scene numbers Status after download Off On See above Permit teach in No Yes See above Channel reacts to No scene number Scene number 1 Scene number 5 Scene number 63 Fifth of the 8 possible scene numbers Status after download Off On See above Permit teach in No Yes See above Channel reacts to No scene number Scene n...

Page 30: ...ber 7 Scene number 63 Seventh of the 8 possible scene numbers Status after download Off On See above Permit teach in No Yes See above Channel reacts to No scene number Scene number 1 Scene number 8 Scene number 63 Last of the 8 possible scene numbers Status after download Off On See above Permit teach in No Yes See above ...

Page 31: ...el switched on feedback object sends a 1 inverted Channel switched on feedback object sends a 0 Transmit feedback cyclically No yes Send at regular intervals Time for cyclical transmission of feedback 2 minutes 3 minutes 5 minutes 10 minutes 15 minutes 20 minutes 30 minutes 45 minutes 60 minutes At what interval ...

Page 32: ...ion 2 minutes 3 minutes 5 minutes 10 minutes 15 minutes 20 minutes 30 minutes 45 minutes 60 minutes At what interval Counter for time period before next service Service interval x10 h 0 2000 Default value 100 Desired timescale between 2 services Example 10 10 x 10 h 100 hours Reporting of time to service when changing 0 no report 0 100 Default value 10 At what interval is the current meter reading...

Page 33: ...he Logic input in OR gate object appears XOR link The Logic input in XOR gate object appears Block object affects logic object No The block object only affects the input object If required the logic object can activate the channel function despite block with OR and XOR link yes The block object affects the channel object and the logic object The channel function is completely blocked if the block ...

Page 34: ...ed 5 1 2x switching with push button interface 2 push buttons are connected to a TA 2 S push button interface and they control 2 channels on the RM 4 H 5 1 1 Devices RM 4 H 4940212 TA 2 S RM 8 H 4930212 5 1 2 Overview 5 1 3 Objects and links No TA 2 S No RM 4 H Comment Object name Object name 1 Channel I1 1 switching 0 Channel C1 switch object 11 Channel I2 1 switching 20 Channel C2 switch object ...

Page 35: ...Send telegram Value Change over Send after long operation Do not send Send after double click Do not send Channel 2 Activate channel 2 Yes Channel 2 function Push button Button object 1 Object type Switching 1 bit Send after short operation Send telegram Value Change over Send after long operation Do not send Send after double click Do not send RM 4 H Parameter page Parameter Setting Channel C1 Ch...

Page 36: ... to a TA 4 S input and the temperature value is sent to the bus Channel C1 receives the domestic water temperature via a threshold object and switches the heating element to relay output 5 2 1 Devices RM 4 H 4940212 TA 4 S RM 8 H 4930214 100k feed temperature sensor 9070489 5 2 2 Overview 5 2 3 Objects and links No TA 4 S No RM 4 H Comment Object name Object name 21 Temperature actual value of cha...

Page 37: ...ture input Sensor type Floor sensor 9070321 Transmit temperature in the event of change of 2 K RM 4 H channel C1 Parameter page Parameter Setting Configuration options Channel function Switch On Off Activation of function via Exceeding the setpoint Contact characteristics Type of contact NO contact Threshold Type of threshold object Floating point value DPT9 e g temperature CO2 Threshold 50 Hyster...

Page 38: ...scenes for the relevant channel via parameter See Activate scenes parameter and Scenes parameter page The current status is allocated to the appropriate scene number when a scene is saved The previously saved status is restored when a scene number is called up This allows a FIX system to be easily and conveniently integrated into any chosen user scene The scenes are permanently stored and remain i...

Page 39: ...39 13 0C 12 8C 140 14 0D 13 8D 141 15 0E 14 8E 142 16 0F 15 8F 143 17 10 16 90 144 18 11 17 91 145 19 12 18 92 146 20 13 19 93 147 21 14 20 94 148 22 15 21 95 149 23 16 22 96 150 24 17 23 97 151 25 18 24 98 152 26 19 25 99 153 27 1A 26 9A 154 28 1B 27 9B 155 29 1C 28 9C 156 30 1D 29 9D 157 31 1E 30 9E 158 32 1F 31 9F 159 33 20 32 A0 160 34 21 33 A1 161 35 22 34 A2 162 36 23 35 A3 163 37 24 36 A4 1...

Page 40: ... 52 B4 180 54 35 53 B5 181 55 36 54 B6 182 56 37 55 B7 183 57 38 56 B8 184 58 39 57 B9 185 59 3A 58 BA 186 60 3B 59 BB 187 61 3C 60 BC 188 62 3D 61 BD 189 63 3E 62 BE 190 64 3F 63 BF 191 Examples central or channel related Call up status of scene 5 Send 04 to the relevant scene object Save current status with scene 5 Send 84 to the relevant scene object ...

Page 41: ...ach of the 8 possible scene numbers in a channel Status after download parameter The scenes are programmed into the device after the download has been completed Later changes via teach in telegrams are possible if required and they can be permitted or blocked via a parameter 6 2 Conversion of percentages to hexadecimal and decimal values Percentage value 0 10 20 30 40 50 60 70 80 90 100 Hexadecima...