RAM 712 KNX
room thermostat for surface-mounted and flush-mounted installation
theben
Version: Dec-10 (subject to change) Page 23 of 65
3.4.4 Actual value
Table 13
Designation
Values
Application
Calibration value
In 1/10 K (-64 .. 63)
Manual input – 64 ... 63
Positive or negative
adjustment of measured
temperature in 1/10 K
increments.
Examples: a) RAM 712 sends
20.3°C. A room temperature
of 21 °C is measured using a
calibrated thermometer. “7”
(i.e. 7 x 0.1K) must be entered
to increase the temperature of
RAM 712 to 21 °C .
b) RAM 712 sends 21.3°C.
20.5 °C is measured. To
reduce the temperature of
RAM 713 to 20.5 °C,
“8” (i.e. -8 x 0.1K) must be
entered.
Transmission of the actual
value
Not in the event of change
With change of 0.2 K
With change of 0.3 K
With change of 0.5 K
With change of 0.7 K
With change of 1 K
With change of 1.5 K
With change of 2 K
Is the current room
temperature to be transmitted?
If yes, from which minimum
change should this be resent?
This setting keeps the bus
load as low as possible.
Cyclical transmission of the
actual value
Do not send cyclically
Every 2 min., every 3 min.
Every 5 min., every 10 min.
Every 15 min., every 20 min.
Every 30 min
, every 45 min.
Every 60 min.
How often should the values
be sent, regardless of the
temperature changes?