RAM 712 KNX
room thermostat for surface-mounted and flush-mounted installation
theben
Version: Dec-10 (subject to change) Page 20 of 65
3.4.3 Setpoint values
Table 12
Designation
Values
Application
loading application
18 °C, 19 °C, 20 °C,
21 °C
, 22 °C, 23 °C,
24 °C, 25 °C
Output setpoint value for
temperature control.
Reduction in standby mode
(during heating)
0.5 K, 1 K, 1.5 K
2 K
, 2.5 K, 3 K
3.5 K, 4 K
operation and a
reduction of 2K, controls
RAM 712 at a setpoint value
of 21 – 2 = 19 °C
Reduction in night mode
(during heating)
3 K, 4 K,
5 K
6 K, 7 K, 8 K
By what value should the
temperature be reduced in
night mode?
Setpoint value for frost
protection operation (during
heating)
3 °C, 4 °C,
5 °C
6 °C, 7 °C, 8 °C
9 °C, 10 °C
Preset temperature for frost
protection operation in
heating mode
(Heat protection operation
applies in cooling mode).
Setpoint value offset only
applies
Only in comfort mode
Setpoint value adjustment:
Is only considered in the
selected mode and is
ineffective in all operating
modes.
With comfort and standby
mode
With comfort, standby and
night mode