background image

1

LUNA 121 top3 RC

1210130/1210230

LUNA 122 top3 RC

1220130/1220230

307529 01

Digital twilight 

switch

EN

1.  Basic safety information

Danger of death through electric shock or fire!

¾

¾

Installation should only be carried out by a 

qualified electrician!

WARNING

 

The device is designed for installation on DIN top hat 
rails (in accordance with EN 60715)

2.  Proper use

 

The digital twilight switch is used for lighting equipment 
(streets), external stairways, display windows, entrances etc. 

 

Only for use in closed, dry rooms

 

!

Do not use on safety devices, e.g. escape route doors, fire 

safety equipment etc.

Disposal

¾

†

Dispose of device in environmentally sound manner

3.  Installation and connection

Mounting the time switch

Danger of death through electric shock or fire!

¾

¾

Installation should only be carried out by a 

qualified electrician!

WARNING

click

Test connection

45° cable

Spring plug-in 

terminal opener

Bluetooth 

OBELISK top3 

(9070130)

DuoFix spring plug-

in terminal

¾

†

Mount on DIN top hat rails (as defined in EN 60715)

¾

†

Switched voltage-free

¾

†

Ensure device cannot be switched on

¾

†

Check absence of voltage

¾

†

Earth and bypass

¾

†

Cover or shield any adjacent live components

 

C1

1 2 3

N

L

L

L N

Ext1

max

. 100 m

Data

RC DCF

– +

Lux

max

. 100 m

C2

C1

1 2 3

4 5 6

N

L

L

L

N

Data

– +

RC DCF

Lux

max

. 100 m

Connecting the cable

¾

†

Strip cable to 8 mm (max. 9)

¾

†

Insert cable in the open DuoFix plug-in terminal at 45°

 

L

2 cables per terminal position possible

¾

†

To open the DuoFix plug-in terminal, press screwdriver 

downwards

Disconnecting the cable

¾

†

Use the screwdriver to push the load line connection 

opener downwards

Summary of Contents for LUNA 121 top3 RC

Page 1: ...ting the time switch Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING click Test connection 45 cable Spring plug in terminal opener Bluetooth OBELISK top3 9070130 DuoFix spring plug in terminal Mount on DIN top hat rails as defined in EN 60715 Switched voltage free Ensure device cannot be switched on Check absence of voltage ...

Page 2: ...sensor 0 25 1 5 mm2 strip cable by 8 mm max 9 mm max 10mm 8 9 mm ø 5 10 mm 9 mm ca 63mm IP 66 IP 40 Ø 20 mm 4 Device description Display buttons MENU OK OK MENU 0 6 12 18 24 Programmed switching times Date display Channel status C1 C2 ON On OFF Off Time display Days of the week from 1 to 7 Display of the active buttons with the relevant function Activate display Open menu Cancel menu ESC leave men...

Page 3: ...ration 5 Settings and functions Set lux values LIGHT CHANNEL C1 LUX VALUE LUX ON Switch light off in the mornings Switch light on in the evening LUX OFF MONDAY MONDAY MONDAY 15 lx MONDAY 15 lx SAVE COPY COPY ADD TUESDAY ADD TUESDAY DELAY TIME END MENU u u u u u SAVE L LThe device has been preset at 15 lx for the switch on switch off level Press MENU Select LIGHT and press OK to confirm Select CHAN...

Page 4: ...e or seve ral date ranges There are 3 types of date ranges Fixed date range e g start time on 02 04 2018 at 16 00 end time on 24 04 2018 at 10 00 Annually recurring date range e g Christmas start time on 24 12 at 18 00 each year end time on 26 12 at 23 00 each year Easter dependent date range e g Whit Sunday and Whit Monday start time 49 days after Easter at 00 00 end time each year 51 days after ...

Page 5: ...4 light sensors 1 LUNA max 3 light sensors 1 DCF antenna max 10 LUNA Σ max 16 devices LUNA light sensors L LPresetting all connected sensors are active for all chan nels The sensor that sends the lowest lux value is active Activating PIN code The PIN code is set in OPTIONS via the menu L LIf you have forgotten your PIN call the Theben Hotline L LHave the serial number ready OPTIONS NO PIN WITH PIN...

Page 6: ... not be swit ched at the same time The channels can be interlocked in this case LThe channel lock prevents both channels from switching on at the same time If a channel is already switched on the second channel will not switch on until the first channel is switched off and a waiting time of 1 s has passed If both channels are switched on at the same time channel 1 has priority OPTIONS OPERATING HO...

Page 7: ... is selected the day of the week or EVERY DAY can be selected and the switchover hour must then be entered only full hours can be entered Finally the system returns to CHANNEL COMBINATION Hour counter The operating hours of the channel relay are displayed and deleted in the OPTIONS menu If the number of operating hours exceeds the value set in the Service menu SERVICE will appear in the display Ex...

Page 8: ...two way switch Max switching capacity 16 A at 250 V cos ϕ 1 Switching capacity 10 A at 250 V cos ϕ 0 6 Min switching capacity 10 mA 230 V AC 100 mA 24 V AC DC Power reserve 10 years Shortest delay time 1 s Switching accuracy To the second Software Class A Rated impulse voltage 4 kV Pollution degree 2 Glow lamp load 2600 W Halogen lamp load 2600 W Fluorescent lamps KVG uncorrected series corrected ...

Reviews: